Grundfos MP 204 Installation And Operating Instructions Manual

Typ
Installation And Operating Instructions Manual

Nižšie nájdete stručné informácie o zariadení MP 204. Toto zariadenie slúži na ochranu asynchrónnych motorov alebo čerpadiel pred preťažením, podťažením, prehriatím a ďalšími poruchami. MP 204 monitoruje prúd, napätie, teplotu a iné parametre a v prípade prekročenia nastavených limitov automaticky vypne motor. Zariadenie sa dá ovládať a konfigurovať pomocou Grundfos GO Remote alebo cez GENIbus.

Nižšie nájdete stručné informácie o zariadení MP 204. Toto zariadenie slúži na ochranu asynchrónnych motorov alebo čerpadiel pred preťažením, podťažením, prehriatím a ďalšími poruchami. MP 204 monitoruje prúd, napätie, teplotu a iné parametre a v prípade prekročenia nastavených limitov automaticky vypne motor. Zariadenie sa dá ovládať a konfigurovať pomocou Grundfos GO Remote alebo cez GENIbus.

MP 204
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Installation and operating instructions
Other languages
net.grundfos.com/qr/i/96650480
2
3
Table of contents
MP 204
English (GB)
Installation and operating instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
 (BG)
   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
eština (CZ)
Montážní a provozní návod. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Deutsch (DE)
Montage- und Betriebsanleitung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Dansk (DK)
Monterings- og driftsinstruktion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Eesti (EE)
Paigaldus- ja kasutusjuhend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Español (ES)
Instrucciones de instalación y funcionamiento . . . . . . . . . . . . . . . . . . . . . . . . 143
Suomi (FI)
Asennus- ja käyttöohjeet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Français (FR)
Notice d'installation et de fonctionnement. . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
 (GR)
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Hrvatski (HR)
Montažne i pogonske upute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Magyar (HU)
Telepítési és üzemeltetési utasítás. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Italiano (IT)
Istruzioni di installazione e funzionamento . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Lietuviškai (LT)
rengimo ir naudojimo instrukcija . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Latviešu (LV)
Uzstdšanas un ekspluatcijas instrukcija. . . . . . . . . . . . . . . . . . . . . . . . . . . 327
Nederlands (NL)
Installatie- en bedieningsinstructies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Polski (PL)
Instrukcja montau i eksploatacji . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Português (PT)
Instruções de instalação e funcionamento . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
Table of contents
4
MP 204
Român (RO)
Instruciuni de instalare i utilizare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Srpski (RS)
Uputstvo za instalaciju i rad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
Svenska (SE)
Monterings- och driftsinstruktion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465
Slovensko (SI)
Navodila za montažo in obratovanje. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 488
Slovenina (SK)
Návod na montáž a prevádzku . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 511
Türkçe (TR)
Montaj ve kullanım kılavuzu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 534
 (UA)
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 557
中文 (CN)
安装和使用说明书 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 580
 (AR)
   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 626
Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 627
English (GB)
5
English (GB) Installation and operating instructions
Original installation and operating instructions
These installation and operating instructions
describe Grundfos MP 204.
Sections 1-15 provide important information about
the product, information necessary to be able to
unpack, install and start up the product in a safe way.
Sections 16-17 provide important information on fault
finding and disposal of the product.
CONTENTS
Page
1. General information
The symbols and hazard statements below may
appear in Grundfos installation and operating
instructions, safety instructions and service
instructions.
1.1 Hazard statements
The symbols and hazard statements below may
appear in Grundfos installation and operating
instructions, safety instructions and service
instructions.
1. General information
5
1.1 Hazard statements
5
2. Product introduction
6
2.1 Intended use
6
2.2 Features
6
2.3 Applications
6
3. Receiving the product
6
3.1 Transporting the product
6
4. Nameplates
6
5. Product range
7
6. Functions
7
6.1 Factory settings
7
7. Mechanical installation
8
7.1 MP 204 in control cabinet
8
7.2 MP 204 on DIN rail
8
8. Electrical connection
9
8.1 Overview
10
8.2 Input for Pt100/Pt1000
11
8.3 Input for PTC/thermal switch
11
8.4 Backup fuses
11
8.5 Wiring diagrams
12
8.6 External current transformers
15
9. Startup
16
9.1 Operation
16
9.2 Setting on operating panel
17
9.3 Learning function
19
10. Grundfos GO Remote
19
10.1 Infrared communication
19
10.2 Communication
19
10.3 Grundfos GO Remote menus
19
11. MP 204 with GENIbus
20
12. Pump operation with MP 204
21
12.1 Industrial pumps
21
12.2 Submersible pumps
21
12.3 Wastewater pumps
21
13. Curves
22
13.1 Trip class "P"
22
13.2 IEC trip curves
23
14. Technical data
24
15. Electrical data
24
15.1 Outputs
24
15.2 Inputs
24
15.3 Insulation measurement method
24
15.4 Measuring ranges
25
15.5 Setting ranges
25
16. Fault finding
26
16.1 Warning and trip codes
26
16.2 Fault finding the product
27
17. Disposing of the product
27
Read this document before installing the
product. Installation and operation must
comply with local regulations and accepted
codes of good practice.
This appliance can be used by children
aged from 8 years and above and persons
with reduced physical, sensory or mental
capabilities or lack of experience and
knowledge if they have been given
supervision or instruction concerning use
of the appliance in a safe way and
understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not
be made by children without supervision.
English (GB)
6
2. Product introduction
2.1 Intended use
MP 204 is an electronic motor protector, designed for
the protection of an asynchronous motor or a pump.
It must always be installed in a cabinet.
MP 204 is designed for single- and three-phase
motors. In single-phase motors, the start and run
capacitors are also measured. Cos is measured in
both single- and three-phase systems.
MP 204 must only be installed according to the
technical specifications. See the installation and
operating instructions for the product.
2.2 Features
The motor protector consists of the following
components
a cabinet incorporating instrument transformers
and electronics.
an operating panel with operating buttons and
display for reading of data.
MP 204 operates with two sets of limits:
a set of warning limits
a set of trip limits.
If one or more of the warning limits are exceeded,
the motor continues to run, but the warnings will
appear in the MP 204 display.
If one of the trip limits is exceeded, the trip relay
stops the motor. At the same time, the signal relay is
operating to indicate that the limit has been
exceeded.
Some values only have a warning limit.
The warning can also be read by means of Grundfos
GO Remote.
2.3 Applications
MP 204 can be used as a stand-alone motor
protector.
MP 204 may also be incorporated in a Grundfos
Dedicated Controls system in which it functions as a
motor protector and data collection unit transmitting
measured values via Grundfos GENIbus to the
Grundfos CU 362 control unit.
Monitoring of MP 204 is possible via Grundfos
GENIbus.
The power supply to MP 204 is in parallel with the
supply to the motor. Motor currents up to 120 A are
passed directly through MP 204. MP 204 protects the
motor primarily by measuring the motor current by
means of a true RMS measurement. MP 204
disconnects the contactor if, for example, the current
exceeds the preset value.
The pump is protected secondarily by measuring the
temperature with a Tempcon sensor, a Pt100/Pt1000
sensor and a PTC sensor/thermal switch.
3. Receiving the product
3.1 Transporting the product
4. Nameplates
Rating and approvals.
Fig. 1 Nameplate on front cover
These four numbers must be stated when contacting
Grundfos:
Fig. 2 Nameplates on the side of MP 204
CAUTION
Falling objects
Minor or moderate personal injury
- Wear safety shoes and helmet.
CAUTION
Sharp element
Minor or moderate personal injury
- Wear protective gloves to avoid being
cut by the sharp edges of the
packaging.
TM03 1472 0806
Pos. Description
1 Product number
2 Version number
3 Serial number
4 Production code
TM07 4599 2019
Prod. No.
96079927
Serial No.
P. c .
V01
0001
0442
IP 20
2
4
1
3
MP 204 IP 20
Vin nom. 100-480 V~50/60HZ Ifuse max 160 A
Current 3-120 A~ Pint. 5 W <10kA
IEC/EN
60947
UL508
25BZ
Ta -20°C to 60°C
-20°C to 40°CTa
Type
Ic
24V 2A DC-13, L/R=40ms, 48W
400V 2A AC-15, 400VA
Pilot Duty R150=
Pilot Duty 400V 2A~
rating IEC
Relay Contact
rating UL
Relay Contact
N2042
Made in Estonia
DK-8850 Bjerringbro, Denmark
Industrial Control Equipment
English (GB)
7
5. Product range
MP 204
external current transformers up to 1000 A.
6. Functions
Phase-sequence monitoring
indication of current or temperature (user
selection)
input for PTC/thermal switch
indication of temperature in °C or °F (user
selection)
4-digit, 7-segment display
setting and status reading with Grundfos GO
Remote
setting and status reading via GENIbus.
Tripping conditions
Overload
underload (dry running)
temperature (Tempcon sensor, PTC/thermal
switch and Pt sensor)
missing phase
phase sequence
overvoltage
undervoltage
power factor (cos φ)
current unbalance.
Warnings
Overload
underload
temperature (Tempcon, see section
12.2 Submersible pumps, and Pt sensor)
overvoltage
Undervoltage
power factor (cos φ)(in connection with single-
and three-phase connection)
run capacitor (single-phase operation)
start capacitor (single-phase operation)
loss of communication in network
harmonic distortion.
Learning function
Phase sequence (three-phase operation)
run capacitor (single-phase operation)
start capacitor (single-phase operation)
identification and measurement of Pt100/Pt1000
sensor circuit.
6.1 Factory settings
Current limit: 0 A
Nominal voltage: 400 V
Class: P (trip delay: 5 seconds)
Trip delay: 5 seconds
Number of phases: 3, non-earthed
Power-on delay: 5 seconds Learning function: Active
Active trip limits
Overload according to class
Underload: - 40 %
Overvoltage: + 20 %
Undervoltage: - 20 %
Phase-sequence monitoring
Current unbalance: 10 %
PTC/thermal switch
Active warnings
Run capacitor, low: - 50 %
Start capacitor, low: - 50 %
The overvoltage and undervoltage trip
limits are deactivated automatically if the
temperature monitoring with Tempcon or
Pt100/Pt1000 is set to active.
English (GB)
8
7. Mechanical installation
7.1 MP 204 in control cabinet
MP 204 is designed for mounting in a control
cabinet, either on a mounting plate or on a DIN rail.
7.2 MP 204 on DIN rail
Mounting and removal of MP 204 mounted on a DIN
rail is shown in figs 3 and 4.
Fig. 3 Mounting
Fig. 4 Removal
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product,
make sure that the power supply has
been switched off and that it cannot be
accidentally switched on.
- Ensure that the sensor and power
cables are separated when installing
sensors and switches.
- Always install the product inside a
suitable cabinet.
TM03 0179 4404
34
21
TM03 0179 4404
1 2
English (GB)
9
8. Electrical connection
DANGER
Electric shock
Death or serious personal injury
- All cables taken through the product
and the current transformers must be
insulated.
- Insulation between the cabinet and the
product must have a suitable insulation
resistance or the cabinet must be
connected to protective earth.
- Ensure that the trip/signal relay output
is maximum 400 V AC.
WARNING
Electric shock
Death or serious personal injury
- Before starting any work on the product,
make sure that the power supply has
been switched off and that it cannot be
accidentally switched on.
- Ensure that the power and sensor
cables are separated when mounting
the relay output connections.
- Make sure that the wiring polarity
matches the installation instructions.
WARNING
Cause of fire
Death or serious personal injury
- The product must not be supplied with
pump voltage if it exceeds the rating
mentioned on the nameplate.
- Ensure that the branch circuit fuse is
maximum 8 A.
English (GB)
10
8.1 Overview
Fig. 5 Cable entries
Fig. 6 Terminals
*
10 mm
2
with cable terminal
**
4 mm
2
with cable terminal
TM03 0181 4404
Pos. 1
TM03 0181 4505
MP 204
Pos. 2
Pos. 3
Pos. 6Pos. 4 Pos. 5
Pos. 7
Pos. Designation Three-phase connection Single-phase connection Cable
1
I1 Entry for phase L1 to motor Entry for neutral
Max. 16I2 Entry for phase L2 to motor Entry for phase
I3 Entry for phase L3 to motor Entry for auxiliary winding
2
L1/N Supply: L1 Supply: Neutral
Max. 6 mm
2 *
L2/L Supply: L2 Supply: Phase
L3/A Supply: L3 Auxiliary winding
FE Functional earth
5 Insulation measurement
3
T1
PTC/thermal switch
Max. 2.5 mm
2 **
T2
4
A GENIbus data A
Y Reference/screen
B GENIbus data B
5
+
Pt100/Pt1000 sensorC
C
SH Screen
6
95
Trip relay NC
96
7
97
Signal relay NO
98
UL requirement.
For field wiring terminals, minimum 60/75
°C stranded copper conductors must be
used.
English (GB)
11
8.2 Input for Pt100/Pt1000
See fig. 6, pos. 5.
For examples of Pt100/Pt1000 connection, see figs 7
and 8.
Fig. 7 Two-core Pt100/Pt1000 connection
8.3 Input for PTC/thermal switch
See fig. 6, pos. 3.
If not used, short-circuit the PTC input using a wire,
or deactivate it with Grundfos GO Remote.
8.4 Backup fuses
Maximum backup fuse sizes which may be used for
MP 204 appear from the table below:
At motor currents up to and including 120 A, the
cables to the motor can be taken directly through the
L1-L2-L3 of MP 204.
At motor currents above 120 A, current transformers
must be used. See fig. 5, pos. 1.
If backup fuses above 50 A are used, the L1-L2-L3
and "5" to MP 204 must be protected separately with
maximum 10 A fuses. See fig. 8.
If current transformers are used, the L1-L2-L3 and
"5" to MP 204 must be protected with maximum 10 A
fuses.
For installation examples, see figs 8 to 12.
Terminal
designation
Description
+ Resistance input.
C
Correction for conductor
resistance.
To be connected by means of a
three-core Pt100/Pt1000
connection, otherwise the two "C"
terminals are to be short-circuited.
C
Correction for conductor
resistance.
To be connected by means of a
three-core Pt100/Pt1000
connection, otherwise the two "C"
terminals are to be short-circuited.
SH 0 V (screen).
TM03 1397 2205
Terminal
designation
Description
T1
Connection of PTC/thermal switch
T2
Pt100
E1
L1
L2
L3
+
C
C
I1
I2
I3
T1
T2
FE
5
A
Y
B
MP 204
Pt100/Pt1000
MP 204
Maximum size
[A]
Type
Without external current
transformer
120 RK5
With 200/5 external
current transformer
200 RK5
With 300/5 external
current transformer
300 RK5
With 500/5 external
current transformer
500 RK5
With 750/5 external
current transformer
750 RK5
With 1000/5 external
current transformer
1000 RK5
English (GB)
12
8.5 Wiring diagrams
8.5.1 Three-phase system
The wiring diagram, fig. 8, shows an example of a
three-phase pump with insulation measurement.
The connections to L1, L2, L3 and "5" can be made
with a cable of up to 10 mm
2
. A special fuse unit up
to approximately 50 A is therefore not required.
If larger backup fuses are used, the voltage to the
L1, L2 and L3 must be protected separately. We
recommend a maximum of 10 A or less.
Fig. 8 Three-phase connection
TM03 0122 2205
1
2
35
46
13
14
S1
K1
S0
22
21
13
14
K1
96
95
E1
K1
A1
A2
L
1
L
2
L
3
3
~
Pt100
E1
L1
L2
L3
+
C
C
I1
I2
I3
T1
T2
FE
5
A
Y
B
Maximum 10 A
MP 204
English (GB)
13
8.5.2 Three-phase system with external current transformers
Fig. 9 Three-phase connection with current transformers
Fig. 10 Five windings per phase through MP 204
TM03 0123 2205
1
2
35
46
K1
13
14
S1
K1
S0
22
21
13
14
R1
96
95
E1
A1
A2
+
C
C
T1
T2
FE
Pt100
E1
L1
L2
L3
I1
I2
I3
5
A
Y
B
L
1
L
2
L
3
3
~
Maximum 10 A
MP 204
Pt100/Pt1000
TM03 1398 1905
English (GB)
14
8.5.3 Single-phase system with start and run capacitors
Fig. 11 Single-phase connection
TM03 0124 2205
1
2
3
4
13
14
S1
K1
S0
22
21
13
14
K1
96
95
E1
K1
E1
L1
L2
L3
+
C
C
I1
I2
I3
T1
T2
FE
5
A
Y
B
A1
A2
MA
Pt100
CC
L
1
N
1
~
run
start
MP 204
Pt100/Pt1000
English (GB)
15
8.6 External current transformers
At motor currents above 120 A, external current
transformers must be used. Fit the transformers as
shown in fig. 12.
Take the three measuring cables through the three
holes in MP 204 five times per phase. See fig. 13.
The three current transformers must be fitted in the
same direction, and the measuring cables must be
connected in the same way.
Fig. 12 Current transformers
Fig. 13 Five windings per phase through MP 204
TM03 0172 4304
TM03 1398 1905
Current transformer
ratio
I
max.
P
max.
200:5 200 A 5 VA
300:5 300 A 5 VA
500:5 500 A 5 VA
750:5 750 A 5 VA
1000:5 1000 A 5 VA
x5
x5
x5
L
1
L
2
L
3
English (GB)
16
9. Startup
A basic setting of MP 204 can be made on the
operating panel.
Additional functions must be set with Grundfos GO
Remote or PC Tool Water Utility.
9.1 Operation
Fig. 14 Operating panel
9.1.1 Button (Test)
Press the button to open trip relay connection
95-96 and close signal relay connection 97-98. The
red "Trip" indicator light is on. The function is
identical to the overload trip.
9.1.2 Button (Reset)
Press the button to change the tripped state to
normal state with trip relay connection 95-96 closed
and signal relay connection 97-98 open. The red
"Trip" indicator light is off. This implies that the
tripped state has actually ceased. The button
also resets warnings, if any.
9.1.3 Button (+)
Normally the actual current or temperature appears
on the display. Press the button to show
information on the display, according to the following
sequence:
Fig. 15 Sequence on the display
The trip code only appears if MP 204 has tripped.
Switches between "trip" and trip code.
The warning code only appears if the limit value
of one or more warnings has been exceeded, and
if warning code indication has been activated.
Temperatures only appear if the matching
sensors have been connected and activated. If
no Tempcon signal is received, "----" appears on
the MP 204 display.
•Cos φ only appears if this menu has been
enabled with Grundfos GO Remote.
When the motor is operating, the display shows the
actual value.
When the motor stops, the display shows the last
measured value.
9.1.4 Button (-)
Only used in connection with the basic setting of MP
204.
TM03 0181 4404
Pos. 1
"Power"
indicator light
Flashes green until
MP 204 is ready for
operation (power-on
delay).
Is permanently
green when MP 204
is ready for
operation.
Flashes red when
communicating with
Grundfos GO
Remote.
Pos. 2
"Trip" indicator
light
Is red when the trip
relay is activated.
Pos. 3 Display
4 digits, for basic
setting and data
reading.
Pos. 4 IR field
Grundfos GO Remote
communication.
Pos. 5
Operating
buttons
Setting and operation.
MP 204
Pos. 1
Pos. 2
Pos. 4
Pos. 2
Pos. 5
Pos. 3
R
R
R
x5
x5
x5
L
1
L
2
L
3
Trip code (flashing)
Warning code no. 1-n
Current
Voltage
Temperature Tempcon
Temperature Pt sensor
Phase angle cos
English (GB)
17
9.2 Setting on operating panel
Press the and buttons simultaneously for a
minimum of 5 seconds to open the programming
mode. When the display shows three dots, the
buttons can be released.
The set value, e.g. "4.9 A", appears. The unit symbol
"A" is flashing.
Enter these values:
rated current
nominal voltage
trip class
number of phases.
Note: Insulation measurement is only possible of
earthed three-phase systems.
If no buttons are activated, the voltage appears after
10 seconds.
After an additional 10 seconds, the set voltage is
stored automatically, and the programming mode
ends. See fig. 16.
Note: Changes in rated current must be finished by
pressing to store the change.
9.2.1 Rated current
Set the rated motor current with the and
buttons. See the motor nameplate.
Press to store the setting and continue.
Press to cancel the change and finish.
The programming mode ends automatically after 10
seconds, and the change is cancelled. See fig. 16.
9.2.2 Nominal voltage
Set the nominal voltage with the and buttons.
Press to store the setting and continue.
Press to store the setting and finish.
The programming mode ends automatically after 10
seconds, and the change is stored. See fig. 16.
9.2.3 Trip class
Set the trip class with the and buttons.
For submersible pumps, manual setting of the trip
delay, class "P", is normally selected. The time is
factory-set to 10 seconds. It can be changed with
Grundfos GO Remote.
For other pumps, the required IEC trip class (1-45) is
to be set. Normally class 10 is selected. For trip
curves, see page 23.
Press to store the setting and continue.
Press to store the setting and finish.
The programming mode ends automatically after 10
seconds, and the change is stored. See fig. 16.
R
R
R
English (GB)
18
9.2.4 Number of phases
Set the number of phases with the and buttons (1 phase, 3 phases (non-earthed) or 3 phases with FE
(functional earth)).
Press to store the setting and continue.
Press to store the setting and finish.
The programming mode ends automatically after 10 seconds, and the change is stored. See fig. 16.
Fig. 16 Example of basic setting
R
Status display
Set rated current
Set nominal voltage
Set trip class
+
Set number of phases
Press and hold for
approximately 5 seconds
10 seconds
10 seconds
The value is stored
10 seconds
The value is stored
10 seconds
The value is stored
R
The value is stored
R
The value is not stored
R
The value is stored
R
The value is stored
The value is not stored
English (GB)
19
9.3 Learning function
The learning function is factory-set to "Enabled".
After 2 minutes of continuous motor operation, "LRN"
appears on the display for approximately 5 seconds,
while the values are being stored in MP 204. See fig.
14, pos. 3.
If, for instance, a Pt sensor or capacitor has been
replaced, reactivate the learning function by pressing
the and buttons for a minimum of 10 seconds.
The dot in the right side of the display is flashing. MP
204 is waiting for current to pass through the unit for
a minimum of 120 seconds. Then the phase
sequence is measured and stored.
In single-phase systems, MP 204 measures the
capacity of the start and run capacitors and stores
the values as reference.
If a Pt100/Pt1000 sensor is installed, the cable
impedances to the sensor are measured and stored
as reference.
10. Grundfos GO Remote
The product is designed for infrared communication
with Grundfos GO Remote. MP 204 must be
configured using Grundfos GO Remote.
Grundfos GO Remote enables setting of functions
and gives access to status overviews, technical
product information, alarm logs and actual operating
parameters.
Fig. 17 Grundfos GO Remote communication
via infrared connection, IR
Grundfos MI 301
Separate module enabling radio or infrared
communication. Use the module together with an
Android or iOS-based smart device with Bluetooth
connection.
10.1 Infrared communication
When communicating via infrared light, Grundfos GO
Remote must be pointed at the operating panel.
10.2 Communication
If a Grundfos Communication Interface Unit (CIU) is
to be used, we recommend you to fit it according to
the wiring diagram and layout supplied with the
Control MP 204.
All variants can be extended with external
communication as an option.
10.3 Grundfos GO Remote menus
"Status and limits"
"Average current"
"Average voltage"
"Tempcon motor temperature"
"Pt sensor temperature"
"Current unbalance"
"Insulation resistance"
•"Cos "
"Power consumption"
"Energy consumption"
"Energy trip counter"
"Phase information"
"Operating hours"
"Number of starts"
"Trip counter"
"Harmonic distortion"
"Alarms and warnings"
"Alarm log"
TM07 4665 2119
R
+
English (GB)
20
"Settings"
"Mains connection"
"Trip IEC class"
"Trip class delay"
"Trip delay"
"Rated voltage"
"External CT factor"
"Power-on delay"
"Automatic restarting"
"Tempcon temperature"
"PT sensor"
"Insulation measurement"
"PTC sensor/thermal switch"
"Restarts per 24 hours"
"Display units"
"Display setup"
"Show cos "
"Show warning"
"Number"
"Learning"
•"Service"
"Service warning"
"Starts per hour"
"Reset trip counter"
"Reset energy counter"
"Reset start counter"
"Reset hours counter"
"Reset all trip counters"
"Store settings"
"Recall settings"
"Undo"
"Unit configuration"
11. MP 204 with GENIbus
If several MP 204 units are connected to the same
GENIbus, the connection is to be made as shown in
fig. 18.
Leave the screen as close to the conductive support
as possible.
If GENIbus has been in use, and bus communication
monitoring has been activated, MP 204 continues to
monitor the bus activity. If MP 204 does not receive
GENIbus telegrams, MP 204 presumes that the
GENIbus connection has been disconnected and
indicates a fault on the individual units.
Each of the units in the chain must be assigned an
identification number with Grundfos GO Remote.
For further information about GENIbus, see
Grundfos Product Center at www.grundfos.com.
Fig. 18 GENIbus
DANGER
Electric shock
Death or serious personal injury
- Ensure that the sensor and power
cables are separated when installing
GENIbus.
- Insulation between the cabinet and the
product must have a suitable insulation
resistance or the cabinet must be
connected to protective earth.
- All cables taken through the product
and the current transformers must be
insulated.
TM05 1096 2111
MP 204 MP 204
AYB
C
C
SH
T
R
95 96 97
98
AYB
C
C
CC
SH
95 96 97
98
Power PowerTrip Trip
L1/N
L2/L
L3/A FG
5
L1/N
L2/L
L3/A FG
5
T1
T2
T1
T2
A
Y
B
CU 361
CU 362
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350
  • Page 351 351
  • Page 352 352
  • Page 353 353
  • Page 354 354
  • Page 355 355
  • Page 356 356
  • Page 357 357
  • Page 358 358
  • Page 359 359
  • Page 360 360
  • Page 361 361
  • Page 362 362
  • Page 363 363
  • Page 364 364
  • Page 365 365
  • Page 366 366
  • Page 367 367
  • Page 368 368
  • Page 369 369
  • Page 370 370
  • Page 371 371
  • Page 372 372
  • Page 373 373
  • Page 374 374
  • Page 375 375
  • Page 376 376
  • Page 377 377
  • Page 378 378
  • Page 379 379
  • Page 380 380
  • Page 381 381
  • Page 382 382
  • Page 383 383
  • Page 384 384
  • Page 385 385
  • Page 386 386
  • Page 387 387
  • Page 388 388
  • Page 389 389
  • Page 390 390
  • Page 391 391
  • Page 392 392
  • Page 393 393
  • Page 394 394
  • Page 395 395
  • Page 396 396
  • Page 397 397
  • Page 398 398
  • Page 399 399
  • Page 400 400
  • Page 401 401
  • Page 402 402
  • Page 403 403
  • Page 404 404
  • Page 405 405
  • Page 406 406
  • Page 407 407
  • Page 408 408
  • Page 409 409
  • Page 410 410
  • Page 411 411
  • Page 412 412
  • Page 413 413
  • Page 414 414
  • Page 415 415
  • Page 416 416
  • Page 417 417
  • Page 418 418
  • Page 419 419
  • Page 420 420
  • Page 421 421
  • Page 422 422
  • Page 423 423
  • Page 424 424
  • Page 425 425
  • Page 426 426
  • Page 427 427
  • Page 428 428
  • Page 429 429
  • Page 430 430
  • Page 431 431
  • Page 432 432
  • Page 433 433
  • Page 434 434
  • Page 435 435
  • Page 436 436
  • Page 437 437
  • Page 438 438
  • Page 439 439
  • Page 440 440
  • Page 441 441
  • Page 442 442
  • Page 443 443
  • Page 444 444
  • Page 445 445
  • Page 446 446
  • Page 447 447
  • Page 448 448
  • Page 449 449
  • Page 450 450
  • Page 451 451
  • Page 452 452
  • Page 453 453
  • Page 454 454
  • Page 455 455
  • Page 456 456
  • Page 457 457
  • Page 458 458
  • Page 459 459
  • Page 460 460
  • Page 461 461
  • Page 462 462
  • Page 463 463
  • Page 464 464
  • Page 465 465
  • Page 466 466
  • Page 467 467
  • Page 468 468
  • Page 469 469
  • Page 470 470
  • Page 471 471
  • Page 472 472
  • Page 473 473
  • Page 474 474
  • Page 475 475
  • Page 476 476
  • Page 477 477
  • Page 478 478
  • Page 479 479
  • Page 480 480
  • Page 481 481
  • Page 482 482
  • Page 483 483
  • Page 484 484
  • Page 485 485
  • Page 486 486
  • Page 487 487
  • Page 488 488
  • Page 489 489
  • Page 490 490
  • Page 491 491
  • Page 492 492
  • Page 493 493
  • Page 494 494
  • Page 495 495
  • Page 496 496
  • Page 497 497
  • Page 498 498
  • Page 499 499
  • Page 500 500
  • Page 501 501
  • Page 502 502
  • Page 503 503
  • Page 504 504
  • Page 505 505
  • Page 506 506
  • Page 507 507
  • Page 508 508
  • Page 509 509
  • Page 510 510
  • Page 511 511
  • Page 512 512
  • Page 513 513
  • Page 514 514
  • Page 515 515
  • Page 516 516
  • Page 517 517
  • Page 518 518
  • Page 519 519
  • Page 520 520
  • Page 521 521
  • Page 522 522
  • Page 523 523
  • Page 524 524
  • Page 525 525
  • Page 526 526
  • Page 527 527
  • Page 528 528
  • Page 529 529
  • Page 530 530
  • Page 531 531
  • Page 532 532
  • Page 533 533
  • Page 534 534
  • Page 535 535
  • Page 536 536
  • Page 537 537
  • Page 538 538
  • Page 539 539
  • Page 540 540
  • Page 541 541
  • Page 542 542
  • Page 543 543
  • Page 544 544
  • Page 545 545
  • Page 546 546
  • Page 547 547
  • Page 548 548
  • Page 549 549
  • Page 550 550
  • Page 551 551
  • Page 552 552
  • Page 553 553
  • Page 554 554
  • Page 555 555
  • Page 556 556
  • Page 557 557
  • Page 558 558
  • Page 559 559
  • Page 560 560
  • Page 561 561
  • Page 562 562
  • Page 563 563
  • Page 564 564
  • Page 565 565
  • Page 566 566
  • Page 567 567
  • Page 568 568
  • Page 569 569
  • Page 570 570
  • Page 571 571
  • Page 572 572
  • Page 573 573
  • Page 574 574
  • Page 575 575
  • Page 576 576
  • Page 577 577
  • Page 578 578
  • Page 579 579
  • Page 580 580
  • Page 581 581
  • Page 582 582
  • Page 583 583
  • Page 584 584
  • Page 585 585
  • Page 586 586
  • Page 587 587
  • Page 588 588
  • Page 589 589
  • Page 590 590
  • Page 591 591
  • Page 592 592
  • Page 593 593
  • Page 594 594
  • Page 595 595
  • Page 596 596
  • Page 597 597
  • Page 598 598
  • Page 599 599
  • Page 600 600
  • Page 601 601
  • Page 602 602
  • Page 603 603
  • Page 604 604
  • Page 605 605
  • Page 606 606
  • Page 607 607
  • Page 608 608
  • Page 609 609
  • Page 610 610
  • Page 611 611
  • Page 612 612
  • Page 613 613
  • Page 614 614
  • Page 615 615
  • Page 616 616
  • Page 617 617
  • Page 618 618
  • Page 619 619
  • Page 620 620
  • Page 621 621
  • Page 622 622
  • Page 623 623
  • Page 624 624
  • Page 625 625
  • Page 626 626
  • Page 627 627
  • Page 628 628
  • Page 629 629
  • Page 630 630
  • Page 631 631
  • Page 632 632

Grundfos MP 204 Installation And Operating Instructions Manual

Typ
Installation And Operating Instructions Manual

Nižšie nájdete stručné informácie o zariadení MP 204. Toto zariadenie slúži na ochranu asynchrónnych motorov alebo čerpadiel pred preťažením, podťažením, prehriatím a ďalšími poruchami. MP 204 monitoruje prúd, napätie, teplotu a iné parametre a v prípade prekročenia nastavených limitov automaticky vypne motor. Zariadenie sa dá ovládať a konfigurovať pomocou Grundfos GO Remote alebo cez GENIbus.

v iných jazykoch