Grundfos Multilift MSS Installation And Operating Instructions Manual

Typ
Installation And Operating Instructions Manual
Multilift MSS
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Other languages
http://net.grundfos.com/qr/i/98042530
2
Table of contents
3
Multilift MSS
English (GB)
Installation and operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Български (BG)
Упътване за монтаж и експлоатация . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Čeština (CZ)
Montážní a provozní návod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Deutsch (DE)
Montage- und Betriebsanleitung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Dansk (DK)
Monterings- og driftsinstruktion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Eesti (EE)
Paigaldus- ja kasutusjuhend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Español (ES)
Instrucciones de instalación y funcionamiento. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Suomi (FI)
Asennus- ja käyttöohjeet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Français (FR)
Notice d'installation et de fonctionnement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Ελληνικά (GR)
Οδηγίες εγκατάστασης και λειτουργίας . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Hrvatski (HR)
Montažne i pogonske upute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Magyar (HU)
Telepítési és üzemeltetési utasítás . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Italiano (IT)
Istruzioni di installazione e funzionamento. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Lietuviškai (LT)
Įrengimo ir naudojimo instrukcija . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Latviešu (LV)
Uzstādīšanas un ekspluatācijas instrukcija . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Nederlands (NL)
Installatie- en bedieningsinstructies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Polski (PL)
Instrukcja montażu i eksploatacji . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Português (PT)
Instruções de instalação e funcionamento. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Română (RO)
Instrucţiuni de instalare şi utilizare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Srpski (RS)
Uputstvo za instalaciju i rad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
Svenska (SE)
Monterings- och driftsinstruktion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 305
Slovensko (SI)
Navodila za montažo in obratovanje . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Slovenčina (SK)
Návod na montáž a prevádzku . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Türkçe (TR)
Montaj ve kullanım kılavuzu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Table of contents
4
Multilift MSS
Українська (UA)
Інструкції з монтажу та експлуатації . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
English (GB)
5
English (GB) Installation and operating instructions
Original installation and operating instructions
CONTENTS
Page
1. Symbols used in this document
2. Scope of delivery
Grundfos Multilift MSS lifting stations are supplied complete with
collecting tank, pump, level sensor, non-return valve (depending
on type) and LC 220 controller. Both sensor and pump are
connected to the controller with 4 or 10 m hose and cable.
An accessories bag containing the following items is also
included:
1 x installation and operating instructions
1 x outlet adapter flange, DN 80, with connection piece, DN
100 (outer diameter, 110 mm)
1 x flexible hose, DN 100, and two clamps to connect the
outlet pipe
1 x flexible hose, DN 50, and two clamps to connect the
venting pipe
2 x screw and expansion anchor for tank fixation
1 x socket seal, DN 100
1 x socket seal, DN 50, for diaphragm pump, 1 1/2" connection
or inlet, DN 50
1 x gasket kit, DN 80, 4 bolts M16, nuts and washers
(galvanised).
1. Symbols used in this document
5
2. Scope of delivery
5
3. General description
6
3.1 Applications
6
4. Transportation and storage
6
5. Product description
6
5.1 Lifting station
7
5.2 LC 220 controller
9
6. Installation of lifting station
12
6.1 General description
12
6.2 Guidelines for installation of lifting station
13
6.3 Recommended steps for mechanical installation of
lifting station
13
7. Installation of LC 220 controller
14
7.1 Location
14
7.2 Mechanical installation
14
7.3 Electrical connection
15
7.4 Setting of LC 220
15
7.5 Wiring diagrams
16
8. Startup
16
9. Maintenance and service
17
9.1 Electrical maintenance
17
9.2 Cleaning the level sensor
17
9.3 Contaminated lifting station or components
17
10. Fault finding
18
11. Technical data
19
11.1 Lifting station
19
11.2 LC 220 controller
19
12. Disposal
19
Warning
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
Warning
The use of this product requires experience with and
knowledge of the product.
Persons with reduced physical, sensory or mental
capabilities must not use this product, unless they
are under supervision or have been instructed in the
use of the product by a person responsible for their
safety.
Children must not use or play with this product.
Warning
If these safety instructions are not observed, it may
result in personal injury.
Warning
These instructions must be observed for
explosion-proof pumps.
Caution
If these safety instructions are not observed, it may
result in malfunction or damage to the equipment.
Note
Notes or instructions that make the job easier and
ensure safe operation.
English (GB)
6
3. General description
Grundfos Multilift MSS lifting stations are supplied complete with
collecting tank, pump, level sensor, LC 220 controller and
connection accessories. Depending on the variant, a non-return
valve is included.
The following gives a description of the components.
Fig. 1 Multilift MSS, front and rear view
3.1 Applications
Grundfos Multilift MSS lifting stations are designed for the
collection and pumping of domestic wastewater with no free flow
to sewer level. Grundfos Multilift MSS lifting stations are designed
for the collection and pumping of the following liquids:
domestic wastewater
grey wastewater without faeces
black water with faeces and discharge from water closets
sludge-containing water.
The lifting stations are capable of pumping liquids containing
fibres, textiles, faeces, etc., below sewer level from minor
buildings such as private dwellings, flats, holiday homes etc.
Do not pump rainwater with the Multilift MSS lifting stations for
these two reasons:
The motors of the lifting stations are not designed for
continuous operation which may be necessary in case of
heavy rainfall.
Rainwater must not be discharged into a lifting station inside a
building according to EN 12056-4.
If in doubt, please contact Grundfos for advice.
Do not discharge the following substances/types of wastewater
via a lifting station:
solid matter, tar, high content of sand, cement, ash, cardboard,
debris, garbage etc.
wastewater from sanitary installations situated above the flood
level (this must be drained away via a free flow drainage
system according to EN 12056-1)
wastewater containing substances such as large amounts of
greasy wastewater from deep fryers or similar appliances.
4. Transportation and storage
For long periods of storage, the LC 220 controller must be
protected against moisture and heat.
After a long period of storage, the pump must be inspected before
it is started up again. Make sure that the impeller can rotate
freely.
5. Product description
The MSS Multilift lifting stations are described in the following
sections:
section 5.1 Lifting station describing lifting station, collecting
tank, pump, non-return valve and level sensor
section 5.2 LC 220 controller describing the controller as well
as the functions of the controller.
In section 6. Installation of lifting station and the following
sections, the above components are described as one unit.
TM05 1331 2611
Pos. Description
1 Pump with vortex impeller
2 Carrying handle for the pump
3 Collecting tank (44 litres)
4 Nameplate
5
Non-return valve with inspection cover and drain
screw to lift up the valve flap. See fig. 4.
NOTE: MSS is also available with adapter flange
only for connection to an external standard
non-return valve.
6
Screw cap for pressure tube and tank inspection
opening
7
Outlet adapter flange, DN 80, with connection piece,
DN 100 (outer diameter, 110 mm)
8
Flexible connection hose, DN 100 (internal diameter,
110 mm) with two clamps
9
Horizontal inlets in the back, DN 100, 180 or 250 mm
above the floor
10 Horizontal inlets from the side, DN 50/DN 100
11 Vertical inlets, DN 50/DN 100
12 Vent port, DN 50 (outer diameter, 52 mm), open
13
Port for manually operated diaphragm pump, DN 50
(internal diameter, 50 mm)
14 Fixing point
Warning
The motor carrying handle is only intended for lifting
the motor. Never lift or lower the lifting station by
means of the carrying handle.
Note
Lift the lifting station by the collecting tank.
English (GB)
7
5.1 Lifting station
The Grundfos Multilift MSS lifting stations are supplied complete
with single- or three-phase submersible pumps connected to the
LC 220 controller incorporating a level sensor.
Type key, lifting station
Nameplate, lifting station
Fig. 2 Nameplate, lifting station
5.1.1 Collecting tank
The gas-, odour- and pressure-tight collecting tank is made of
wastewater resistant polyethylene (PE) and has all necessary
ports for the connection of inlet pipes, outlet pipe, venting pipe
and a manually operated diaphragm pump, which is available as
an accessory.
Thus the collecting tank offers five horizontal inlets from the back
and the sides of the tank (4 x DN 100, 1 x DN 50) and two vertical
inlet connections at the top of the tank (1 x DN 100, 1 x DN 50).
The side and back inlets are 180 and 250 mm above the floor for
connection to direct wall-hung or floor-standing toilet according to
EN 33 and EN 37. Further sanitary appliances can be connected
to the other ports.
The tank volume and effective volume (volume between start and
stop) of the collecting tank appear from the following table:
Setting to the relevant inlet level can be made via a DIP switch on
the control panel of the controller. See section 7.4 Setting of LC
220.
The factory-set inlet level is 250 mm above the floor.
To minimise sedimentation, the tank bottom is chamfered to lead
the wastewater to the pump.
5.1.2 Pump
The pump impeller is designed as a free-flow vortex impeller,
ensuring almost unchanged performance throughout the entire
life of the pump.All parts in contact with the pumped liquid are
made of stainless steel. The pump has a mechanical shaft seal.
See more technical data in section 11. Technical data.
Single-phase motors have run capacitors.
Single- and three-phase motors are protected by a thermal switch
in the windings and an additional thermal circuit breaker to cut out
the motor in case of overload.
Three-phase motors:
If the phase sequence is wrong, the controller indicates fault and
prevents the pump from starting. For correction of phase
sequence, see section 5.2.2 Control elements and indicator lights
and fig. 8.
Performance curves are available in the databooklet, which you
can download via the QR code or link below:
Example M SS .11 .3 .2
Multilift lifting station
SS = one pump
Output power, P
2
/ 100 [W]
1 = single-phase motor
3 = three-phase motor
2 = 2-pole motor
4 = 4-pole motor
TM04 7639 2210
Pos. Description
1 Type designation
2 Product number
3 Production code, year and week
4 Frequency [Hz]
5 Number of phases + voltage [V]
6 Voltage [V]
7 Full-load current [A]
8 Motor input power P1 [kW]
9 EAC and CE marks
10 Duty type
11 Serial number
12 Maximum flow rate [m
3
/h]
13 Minimum head [m]
14 Maximum head [m]
15 Maximum liquid temperature [°C]
16 Maximum ambient temperature [°C]
17 Weight [kg]
18 Identification code of the European standard
19 Notified body
20 Reference number for the declaration of performance
Typ
Prod.-Nr.
P. c.
fHz
Serial no.
Phases
UV
A
kW
Gkg
m
m
98127055
0197
I
1/1
P1
Qmax
Hmin
Hmax
T
Med
max
T
Amb
max
m /h
3
C
C
Made in Germany
96075419
DK - 8850 Bjerringbro, Denmark
1
2
3
4
5
6
10
11
12
13
14
15
16
17
18
20
19
7
8
9
Inlet level [mm] 180 250
Total tank volume [l] 44 44
Effective tank volume [l] 20 28
Note
If the motor is overloaded, it will stop automatically.
When it has cooled to normal operating temperature,
it will restart automatically.
http://net.grundfos.com/qr/i/98288126
English (GB)
8
Nameplate, pump
The nameplate is printed on the pump.
Fig. 3 Nameplate, pump
5.1.3 Non-return valve
The DN 80 non-return valve includes a drain screw to lift up the
internal flap in order to drain the outlet pipe in case of
maintenance or service. The valve is designed and tested
according to EN 12050-4. See fig. 4.
Fig. 4 Non-return valve
5.1.4 Level sensor
The piezoresistive pressure sensor placed in the controller is
connected via a hose to a pressure tube in the tank. The screw
cap where the hose is connected includes a connection for a DN
100 tube. This tube, the pressure tube, extends down into the
tank. The rising liquid level compresses the air inside the
pressure tube and hose, and the piezoresistive sensor transforms
the changing pressure into an analogue signal. The control box
uses the analogue signal to start and stop the pump and to
indicate high water-level alarm. The pressure tube is fixed
underneath the screw cap and can be taken out for maintenance,
service and for cleaning the inside of the tube. An O-ring ensures
tightness.
The hose is supplied in lengths of 4 or 10 m. The hose must be
connected to the controller.
Fig. 5 Screw cap with hose, DN 100 tube
TM05 1194 2411
Pos. Description
1 Type designation
2 Product number
3 Rated voltage
4 Frequency
5 Rated current
6 Rated speed
7 Rated power input
8 Weight
9 Maximum flow rate
10 Maximum head
11 Approvals
12 Production week, year and day
13 Maximum liquid temperature
14 Maximum installation depth
15 Power factor
16 Insulation class
17 Enclosure class
Note
Loosen the lock nut a little before turning the drain
screw.
TM05 0340 1011
Drain screw
TM05 0332 1011
English (GB)
9
5.2 LC 220 controller
The level controller switches the MSS Multilift pump on and off
according to the liquid level measured by the piezoresistive,
analogue level sensor. When the start level is reached, the pump
will start, and when the liquid level has been lowered to the stop
level, the pump will be stopped by the controller. An alarm will be
indicated in case of high water level in the tank, sensor failure
etc.
Fig. 6 LC 220 level controller for Multilift MSS
The LC 220 controller has the following functions:
on/off control of one wastewater pump based on a continuous
signal from a piezoresistive, analogue level sensor
automatic test runs during long periods of inactivity (24 hours
after last operation)
battery backup in case of mains supply failure (accessory)
selection of automatic alarm resetting (via DIP switch)
selection between two inlet levels (via DIP switch)
operating indication of:
- power on
- pump running
- time for service/maintenance (selectable via DIP switch).
alarm indication of:
- too high liquid level, which triggers a high-level alarm
- wrong phase or phase sequence detection for three-phase
pumps
- sensor failure
- external level alarm
- runtime monitoring.
As standard, the LC 220 controller has one alarm signal output
for common alarm and three signal inputs for connecting the
piezoresistive sensor, an additional float switch functioning as
backup for the analogue sensors and an additional level switch
for flood detection outside the Multilift MSS. Lifting stations are
often installed in a sump inside the basement - the lowest point in
the building. In case of e.g. groundwater inflow or water pipe
burst, an alarm will be indicated by the controller. If the liquid
level in the sump rises above the high-level alarm level, the
corresponding alarm LED will be on and the built-in buzzer will be
activated.
A battery (accessory) can be installed to activate an acoustic
alarm (buzzer). The buzzer will be activated as long as the fault
exists as it cannot be reset.
In case of power failure, the common alarm output, which is a
potential-free changeover contact, can forward the alarm signal
to a control room by means of an external power source.
A PC Tool can be connected in order to implement updates and
further adjustments.
Furthermore, a log of the last 20 faults can be read out, as well as
the number of starts and operating hours (accessory).
Type key, LC 220 controller
Nameplate, LC 220 controller
The actual controller type, voltage variant, etc., are stated in the
type designation on the nameplate situated on the side of the
controller cabinet.
Fig. 7 Example of an LC 220 nameplate
5.2.1 Design
The LC 220 level controller incorporates the necessary
components such as relays and a control panel with indicator
lights for indication of operating conditions and fault indications.
Furthermore, it has a level input which is activated directly via the
pressure tube inside the collecting tank. Finally, it has terminals
for power supply, connection to the pump and an alarm signal
output for common alarm.
The front cover is closed by four bayonet fastenings with quarter
turn locks. On the left side, the locks are extended and connected
to the cabinet bottom with hinge strings.
TM05 1276 2511
Example LC 220 .1 .230 .1 .8
LC 220 = controller type
1 = one-pump controller
2 = two-pump controller
Voltage [V]
1 = single-phase
3 = three-phase
Maximum operating current per pump [A]
TM05 1351 2611
Pos. Description
1 Type designation
2 Product number
3 Version number
4 Rated voltage
5 Power consumption
6 Maximum backup fuse
7 Weight
8 Maximum pump input current
9 Production year and week
10 Serial number
11 Maximum voltage at contactor
12 Maximum current at contactor
Type
Prod. No.
U
N
max
Fuse max
G
P.c.
Serial No.
Contact max
Contact max
Amb.: 0 to 40 C
Pump max
< 10 kA IP55
LC 220.1.400.3.4
98167897 V01
3x 380-415V~ 50/60Hz
3W
4A
16A
1226
8888
250V
2A
1,8kg
Made in Germany
132
4
6
5
7
9
11
10
12
8
English (GB)
10
5.2.2 Control elements and indicator lights
The table below gives a description of the function of the various
control elements and indicator lights:
Fig. 8 Changing phases of a three-phase controller with
phase inverter
Element Function Description
Selection of
operating
mode
The operating mode is selected by the
ON-OFF-AUTO selector switch which
has three different positions:
POS I:
Starts the pump manually.
POS O:
Stops the pump manually
Resets alarm indications.
POS AUTO:
Automatic operation. The pump will
start and stop according to the signal
from the level sensor.
Indication
of power
supply
status
Green indicator light, indicating that
the power supply is on.
Indication
of pump
status
Red and green indicator lights,
indicating pump status:
Green: Pump is running.
Red: Pump fault.
High-level
alarm
Red indicator light, indicating high
water level. The LED lights up if the
level sensor measures a certain level
in the collecting tank during automatic
mode.
Phase-
sequence
fault
Red indicator light, indicating wrong
phase sequence (three-phase pumps).
Change phase sequence by following
the instruction in fig. 8.
Sensor
failure
alarm
Red indicator light, indicating that the
signal is the out of the measuring
range of around 1000 mm. The pump
has been started and a high-level
alarm is activated.
External
level alarm
Red indicator light, indicating an alarm
from an external level switch.
Indication
of time for
service
Yellow indicator light, indicating that it
is time for service. This function can
be switched on and off by the DIP
switch. The factory setting is one year
according to EN 12056-4.
TM05 3455 0616
English (GB)
11
5.2.3 Internal layout of LC 220
Figure 9 shows the internal layout of LC 220.
Fig. 9 Internal layout of LC 220
TM05 1406 2711 - TM05 3719 1712
82 81
HIGH
LOW
Note: Cable connection for pos. 10:
Use a cable tie if leads protrude more than 20 mm
from the cable sheath.
Pos. Description Terminal numbers
1 Terminals for power supply PE, N, L3, L2, L1
2 Terminals for connecting the pump W1, V1, U1, N, PE
3 Terminals for connecting an external level switch 230 V, NO 13, 14
4 Terminals for "common alarm" output signal
Potential-free changeover contacts NO/NC with
max. 250 V / 2 A
31, 32, 33
5
PCB with piezoresistive analogue pressure
sensor
0-5 V
6 DIP switch
1. Inlet height:
ON = HIGH = 250 mm (factory setting)
OFF = LOW = 180 mm
2. Reset setting:
ON = Automatic (factory setting)
OFF = Manual
3. Service interval:
ON = 1 year
OFF = None (factory setting)
4. Reset setting (only in case of sensor
replacement)
ON = Safe (normal position, factory setting)
OFF = Switch briefly to OFF for the sensor to
adjust to the ambient pressure. See service
instructions.
7 Software service connector (PC Tool) 6-pole connector
8 Control circuit fuse, fine-wire fuse 100 mAT/20 mm x 5
9 Battery (non-rechargeable) 9 V
10
Terminals for additional high water-level alarm
(inside the tank), digital
81, 82
English (GB)
12
6. Installation of lifting station
6.1 General description
Before installing the Multilift MSS lifting station, make sure that all
local regulations covering venting, access to the stations, etc. are
observed.
6.1.1 Installation sketch
Fig. 10 Installation sketch
TM05 1346 2611
4
3
5621 7
Pos. Accessories Product number
1 Socket seal, DN 100 97726942
2 Socket seal, DN 50 98079669
3 Diaphragm pump, 1 1/2" 96003721
4 PVC isolating valve, DN 100 96615831
5 Cast iron isolating valve, DN 80 96002011
6
Gasket kit, DN 80, with bolts, nuts
and washers
96001999
7 External float switch 00ID7805
English (GB)
13
6.2 Guidelines for installation of lifting station
Guidelines for correct mechanical installation of lifting
station according to EN 12056-4
See section 6.1.1 Installation sketch.
Install the lifting station in a properly lit and vented room with
60 cm free space around all parts to be serviced and operated.
Provide a pump sump below the floor level. If a lifting station is
installed in a basement with the risk of penetrating
groundwater, it is advisable (in certain countries required) to
install a drainage pump in a separate pump sump below floor
level in order to drain the room. See fig. 10.
All pipe connections must be flexible to reduce resonance.
Lifting stations must be secured against uplift and twist.
All outlet pipes (lifting station, diaphragm pump and drainage
pump) must have a loop above the local backwater level. The
highest point of the goose neck/reversed water seal must be
above street level.
For outlet pipes, DN 80 and upwards, install an isolating valve
in the outlet pipe. Also provide an isolating valve in the inlet
line.
Surface water must not be discharged into the lifting station
inside the building. It must have its own pumping station
outside the building.
Lifting stations must be provided with an approved non-return
valve according to EN 12050-4.
The volume of the outlet pipe above the non-return-valve up to
the backwater level must be smaller than the effective tank
volume.
In general, a lifting station for black wastewater must be
vented above roof level. However, it is permitted to lead the
ventilation, as a secondary ventilation, into the main building
ventilation system.
If the wastewater is discharged into a collecting line, this
collecting line must have a filling ratio of at least h/d = 0.7.
The collecting line must be at least one nominal diameter
bigger after the outlet pipe connection.
Use a diaphragm pump for simple, manual draining of the
collecting tank in case of pump failure (not obligatory).
6.3 Recommended steps for mechanical installation of
lifting station
1. Checking the scope of delivery. For scope of delivery, see
section 2. Scope of delivery.
2. Preparing the inlets by cutting out the required holes. Use cup
drills 100 for DN 100 and 43 for DN 50 inlets. The cutting
line is recessed. To avoid sharp cutting edges, the holes must
be deburred. The socket seals are provided with collars.
3. Preparing the connection for diaphragm pump (optional). Use
cup drill, 43, for DN 50 connection socket. To avoid sharp
cutting edges, the hole must be deburred.
Fig. 11 Cutting or drilling of connection holes
4. Connecting the inlet pipe to the tank. Install an isolating valve
between inlet pipe and lifting station to avoid inflow during
maintenance and service. We recommend an easy-to-handle
PVC isolating valve.
Fig. 12 Installation of isolating valve
Note
The collecting tank, pump and cables may be flooded
(max. 2 m for 7 days).
Caution
The controller must be installed in a dry and well
ventilated place.
TM05 1242 2511
TM03 3614 0406
Caution
Make sure that weight from inlet, outlet and vent
pipes does not rest on the tank. Long pipe sections,
valves, etc. must be supported.
Warning
Never step on the lifting station.
DN 50 - 43
DN 100 - 100
DN 150 - 150
English (GB)
14
5. Connecting the outlet pipe.
Install an isolating valve between the non-return valve and the
supplied flexible connection hose, DN 100 (internal diameter
110 mm). A flexible connection can be ensured if a distance of
approx. 5 cm is left between the pipe ends of the inlet, outlet
and vent pipes and the ports of the lifting station.
Fig. 13 Isolating valve on top of non-return valve
6. Connecting the venting pipe.
The DN 50 vent port on top of the tank is open. Connect the
venting pipe to the vent port via a flexible connection piece.
The venting pipe must be led out above the roof into the open
air in accordance with local regulations. A flexible connection
can be ensured if a distance of approx. 3 cm is left between
the venting pipe end and the vent port.
7. Connecting the diaphragm pump (optional).
Fit the diaphragm pump on the outlet side. To facilitate
servicing of the diaphragm pump, we recommend fitting a 1
1/2" isolating valve to the tank port.
8. Fixing the tank to the floor.
Fig. 14 Fixing point for fixation of tank to the floor
7. Installation of LC 220 controller
The installation must be carried out by authorised personnel in
accordance with local regulations.
7.1 Location
LC 220 can be installed at ambient temperatures ranging from
0 °C to +40 °C.
Enclosure class: IP56.
Install the controller as close as possible to the lifting station.
When installed outdoors, LC 220 must be placed in a protective
shed or enclosure. LC 220 must not be exposed to direct sunlight.
7.2 Mechanical installation
Proceed as follows:
Mount LC 220 on a plane wall surface.
Mount LC 220 with the cable entries pointing downwards
(additional cable entries, if required, must be fitted in the
bottom plate of the cabinet).
Mount LC 220 with four screws through the mounting holes in
the back plate of the cabinet. Drill the mounting holes with a
6 mm drill using the drilling template supplied with the
controller. Fit the screws into the mounting holes and tighten
securely.
Fit the plastic caps.
Fig. 15 Mounting of controller on the wall
TM05 1347 2611TM05 0334 1011
Warning
Before making any connections in LC 220 or working
on pump, pit, etc., make sure that the power supply
has been switched off and that it cannot be
accidentally switched on.
Warning
Do not install the LC 220 controller in explosion
hazard areas.
Warning
When drilling the holes, take care not to damage any
cables or water and gas pipes. Ensure a safe
installation.
Note
LC 220 can be mounted without removing the front
cover.
TM05 1405 2711
English (GB)
15
7.3 Electrical connection
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the
electricity supply on which it will be used.
All cables/wires must be fitted through the cable entries and
gaskets (IP65).
The power supply socket must be placed near the cabinet as the
controller is supplied with a 1.5 m cable, a Schuko plug for
single-phase and a CEE plug for three-phase pumps.
Maximum backup fuse is stated on the controller nameplate.
If required according to local regulations, install an external mains
switch.
7.4 Setting of LC 220
LC 220 has a 4-contact DIP switch. See fig. 16.
To make the settings, open the cabinet cover by means of the
bayonet fastener locks. The locks on the left side have hinge
strings.
The DIP switch has the following functions:
setting of start level (switch 1). The factory setting is set to
inlet 250 mm above the floor to get the highest effective tank
volume. For floor standing toilets, the setting must be changed
to 180 mm. Starts and stops will be adjusted automatically.
selection of automatic alarm resetting (switch 2)
selection of service interval (switch 3)
selection of sensor (switch 4).
The DIP-switch factory setting is shown in fig. 16.
Each individual switch (1 to 4) of the DIP switch can be set to
position OFF or ON.
When the DIP-switch setting is changed, the controller must be
switched off for at least 10 seconds!
Set the switches 1 to 4 as follows:
Switch 1 (start level):
Switch 2 (automatic alarm reset):
Switch 3 (service interval):
Switch 4: (sensor resetting):
Fig. 16 DIP switch
Warning
LC 220 must be connected in accordance with the
rules and standards in force for the application in
question.
Warning
Before opening the cover, switch off the mains
supply.
Note
During setting, the controller must be off circuit for at
least 10 seconds to ensure the correct configuration
during startup after change of the DIP-switch setting.
Pos. Description
ON
The pump starts when the level in the collecting tank
reaches 250 mm.
OFF
The pump starts when the level in the collecting tank
reaches 180 mm.
Pos. Description
ON
The fault indication will be reset after the fault has
disappeared, meaning the indicator lights will be turned
to off and the alarm signals to external alarm devices
and the built-in buzzer will be deactivated.
OFF
The alarm signal must be reset manually by switching
the selector switch to position "0".
Pos. Description
ON
The function for reminding that it is time for
maintenance is activated. The yellow indication light will
be on when it is time for maintenance work.
The maintenance interval is 1 year (fixed value).
OFF
The function for reminding that it is time for
maintenance is deactivated.
Pos. Description
ON Safe (normal position, factory default)
OFF
Switch briefly to OFF for the sensor to adjust to the
ambient pressure. See service instructions.
TM05 1404 2711
HIGH
LOW
English (GB)
16
7.5 Wiring diagrams
Fig. 17 Wiring diagram for Multilift MSS, single-phase
Fig. 18 Wiring diagram for Multilift MSS, three-phase
8. Startup
Prior to startup, the connection and DIP-switch setting must have
been carried out according to sections 7.3 Electrical connection
and 7.4 Setting of LC 220.
Startup must be carried out by authorised personnel.
Proceed as follows:
1. Check all connections.
2. Open the isolating valves in outlet and inlet lines.
3. Switch on the power supply.
4. Activate a sanitary appliance connected to the inflow of the
Multilift MSS and monitor the increasing water level in the tank
up to the start level. Check the starts and stops at least twice,
and then change the ON-OFF-AUTO selector switch to
automatic mode.
TM05 1402 2711TM05 1403 2711
Warning
Before starting any work on a pump used for
pumping liquids which could be hazardous to health,
clean and vent the pump, pit, etc., thoroughly
according to local regulations.
Warning
Before making any connections in LC 220 or working
on pump, pit, etc., make sure that the power supply
has been switched off and that it cannot be
accidentally switched on.
English (GB)
17
9. Maintenance and service
The Multilift MSS requires a minimum of maintenance.
According to EN 12056-4, lifting stations in single-family houses
must be checked once a year. During the check, local regulations
must be observed.
The periodic checks of the lifting station must be carried out by
authorised personnel and must comprise electrical and
mechanical maintenance.
Check the following points:
Outlet and inlet connections
Check all connections to the lifting station for tightness and
leakages. Make sure that weight from the inlet, outlet and
venting pipes does not rest on the tank. Long pipe sections,
valves, etc. must be supported.
Power consumption
See nameplate.
Cable entry
Make sure that the cable entry is watertight and that the
cables are not bent sharply and/or pinched.
Pump parts
Check that the vent hole of the pump housing is clear by
dismantling the pump from the support flange.
We recommend replacing the O-ring sealing between pump
and support flange.
Make a test run with clean water. In case of noise, vibration or
abnormal running, contact Grundfos.
Shaft seal
Check the shaft seal, O-ring and oil. The oil chamber contains
60 ml non-poisonous oil. Used oil must be disposed of in
accordance with local regulations. This work must be carried
out by the manufacturer or an authorised service workshop.
See service instructions.
Cleaning the non-return valve (if required)
Proceed as follows:
1. Close the isolating valves in the outlet pipe and in the inlet
pipe (if fitted) or drain the outlet pipe by tightening the drain
screw on the side of the non-return valve.
See section 5.1.3 Non-return valve.
2. Clean the non-return valve via its inspection cover.
Replace the gasket of the inspection cover when
reassembling the non-return valve.
9.1 Electrical maintenance
Check the gaskets of the LC 220 cabinet front cover and of the
cable entries.
Check the cable connections.
Check the controller functions.
Check and clean the pressure tube. See section 9.2 Cleaning
the level sensor.
If LC 220 is installed in a particularly moist environment in a
basement, we recommend checking the terminals on the PCB
in order to identify possible corrosion. In typical installations,
the contacts will work for many years and do not require any
inspection.
Replace the 9 V battery, if fitted, in connection with annual
service.
9.2 Cleaning the level sensor
1. Push the ON-OFF-AUTO selector switch to position OFF ( ).
See section 5.2.2 Control elements and indicator lights.
2. Loosen the screw cap by turning it counterclockwise.
See fig. 19.
3. Lift the pressure tube carefully out of the collecting tank.
Do not lift it by means of the hose.
4. Check for possible deposits on or in the pressure tube. See
section 5.1.4 Level sensor.
5. Scrape off any deposits. If necessary, remove the hose from
the controller and rinse the tube and hose with clean water at
low pressure. Make sure no water remains in the hose.
6. Refit the pressure tube by screwing the screw cap on to the
tank. Reconnect the hose to the controller.
7. Check the sensor by test running Multilift MSS.
Fig. 19 Removing the pressure tube
9.3 Contaminated lifting station or components
If Grundfos is requested to service the lifting station, Grundfos
must be contacted with details about the pumped liquid, etc.
before the lifting station is returned for service. Otherwise
Grundfos can refuse to accept the lifting station for service.
Lifting stations which have been in contact with the pumped liquid
must be thoroughly cleaned before they are returned to Grundfos.
Any costs of returning the lifting station are to be paid by the
customer.
However, any application for service (no matter to whom it may
be made) must include details about the pumped liquid if the
lifting station has been used for liquids which are injurious to
health or toxic.
Warning
Before carrying out maintenance and service on
lifting stations used for pumping liquids which might
be hazardous to health, make sure that the lifting
station has been thoroughly flushed with clean water
and that the outlet pipe has been drained. Rinse the
parts in water after dismantling. Make sure that the
isolating valves have been closed. The work must be
carried out in accordance with local regulations.
Warning
Before making any connections in LC 220 or working
on lifting stations, make sure that the power supply
has been switched off and that it cannot be
accidentally switched on.
Note
Do not loosen the support flange. It is screwed and
sealed to the collecting tank. Loosen the four
stainless steel clamps instead.
Note
The above list is not complete. LC 220 may be
installed in environments which require thorough and
frequent maintenance.
TM05 0545 1011
Warning
If a Multilift lifting station has been used for a liquid
which is injurious to health or toxic, it will be
classified as contaminated.
English (GB)
18
10. Fault finding
Warning
Before carrying out any work on lifting stations used for pumping liquids which might be hazardous to health, make sure that
the lifting station has been thoroughly flushed with clean water and that the outlet pipe has been drained. Rinse the parts in
water after dismantling. Make sure that the isolating valves have been closed.
The work must be carried out in accordance with local regulations.
Before making any connections in LC 220 or working on lifting stations, etc., make sure that the power supply has been
switched off and that it cannot be accidentally switched on.
Fault Cause Remedy
1. The pump does not run. a) No power supply.
Without battery backup:
None of the indicator lights are on.
With battery backup:
See section 5.2 LC 220 controller.
Switch on the power supply.
b) The ON-OFF-AUTO selector switch is in
position OFF ( ). See section 5.2.2 Control
elements and indicator lights.
Push the ON-OFF-AUTO selector switch into position
ON ( ) or AUTO ( ).
c) Control circuit fuses are blown. Check and eliminate the cause. Replace the control
circuit fuses.
d) The thermal switch has cut out the pump. Allow the pump to cool. After cooling, the pump will
restart automatically unless LC 220 has been set to
manual restarting (see section 7.4 Setting of LC 220).
If so, push the ON-OFF-AUTO selector switch into
position OFF ( ) for a short period.
e) Motor/supply cable is defective. Check and replace motor and cable, if necessary.
f) The power circuit board or the LED board is
defective.
Replace the power circuit board or LED board.
g) The new DIP-switch setting does not work
correctly.
Switch off the power supply to the controller for 1 minute
and switch it on again (normal procedure). See section
7.4 Setting of LC 220.
2. The sensor signal is out
of range.
All pumps are started
and high-level alarm is
on.
a) Not all outlet valves are open. Open all outlet valves.
b) There is a blockage in the tank or pump. Remove the blockage.
c) The pump is not vented correctly. The pump
cannot build up pressure.
Remove any blockage from the vent hole underneath
the pump.
d) The lifting station is undersized. Recalculate the inflow parameters and compare the
result with the tank volume and pump performance. If
you need a new product, contact the nearest Grundfos
sales company.
3. The pump starts and
stops too frequently
even if there is no
inflow.
a) The level sensor is blocked. Clean the level sensor (see section 9.2 Cleaning the
level sensor).
b) The ventilation of the inner pump housing is
blocked and the pump cannot build up
pressure.
Check the pump housing and remove any impurities.
4. The pump starts
sometimes without
visible reason.
a) Test run 24 hours after last operation. No action necessary. It is a safety function that prevents
the shaft seal from seizing up.
English (GB)
19
11. Technical data
11.1 Lifting station
11.1.1 Collecting tank
11.1.2 Pump
11.1.3 Level sensor
11.2 LC 220 controller
12. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
Subject to alterations.
Weight:
Depending on variant.
See nameplate
Temperature range:
0-40 °C
For short periods up to 60 °C
(max. 5 minutes per hour)
Flood conditions: Max. 2 m for 7 days
Sound pressure level
< 70 dB(A) according to
EN 12050-1 and the Machinery
Directive
Material: Polyethylene (PE)
Motor:
Mains supply: 1 x 230 V, 50 Hz
Insulation class: F (155 °C)
Impeller type: Vortex
Enclosure class: IP68
pH range: 4-10
Starts per hour: max. 60
Max. density of liquid: 1100 kg/m
3
Component Material
DIN
W.-Nr.
AISI
Pump housing Stainless steel 1.4301 304
Impeller Stainless steel 1.4301 304
Protective cap Novolene 2360 Kx
Motor unit
complete
Parts in contact with
liquid: Stainless steel 1.4401 316
Pump shaft - wet
end
Stainless steel 1.4301 304
Motor cable Neoprene
O-rings NBR rubber
Oil Shell Ondina 15, non-toxic
Voltage supply: 12 V
Signal output: 0-5 V
Controller
Voltage variants, rated voltages: 1 x 230 V, 3 x 400 V
Voltage tolerances for LC 220:
- 15 %/+ 10 % of rated
voltage
Mains frequency for LC 220: 50/60 Hz
Supply system earthing: For TN systems
Controller power consumption: 7 W
Backup fuse:
Depending on variant.
See nameplate
Control circuit fuse:
Fine-wire fuse:
100 mA / 20 mm x 5
Ambient temperature:
During operation:
In stock:
0 to +40 °C (must not be
exposed to direct sunlight)
-30 to +60 °C
Enclosure class: IP56
Cabinet of LC 220
External dimensions:
Height = 195 mm
Width = 250 mm
Depth = 110 mm
Material:
ABS (acrylonitrile butadiene
styrene)
Weight:
Depending on variant.
See nameplate
Outputs for alarm devices:
Max. 250 VAC / max.
2 A / min. 10 mA / AC1
Multilift MSS Duty
Voltage
[V]
Power P1 / P2
[kW]
I
1/1
/ I
start
[A]
RPM
[min
-1
]
Number of
poles
Plug type
MSS.11.1.2
S3 -10 %, 1 min.
1 x 230 V
1.8 / 1.1
8 / 22.5
2760 2
Schuko
MSS.11.3.2 3 x 400 V 3.2 / 16 CEE 3P+N+E, 16 A
Български (BG)
20
Български (BG) Упътване за монтаж и експлоатация
Превод на оригиналната английска версия
СЪДЪРЖАНИЕ
Стр.
1. Символи в този документ
2. Съдържание на доставяния комплект
Подемните станции Grundfos Multilift MSS се доставят
фабрично сглобени с колекторен резервоар, помпа, сензор за
ниво, възвратен вентил (в зависимост от типа) и контролер
LC 220. Сензорът и помпата са свързани към контролера чрез
4 или 10 m маркуч и кабел.
Комплектът съдържа също и следните аксесоари:
•1 x инструкции за монтаж и експлоатация
•1 x нагнетателен адаптерен фланец, DN 80, със
съединение, DN 100 (
външен диаметър, 110 mm)
•1 x гъвкаво съединение, DN 100, и две скоби за свързване
на нагнетателната тръба
•1 x гъвкаво съединение, DN 50, и две скоби за свързване
на вентилационната тръба
•2 x винта и анкерен болт за фиксиране на резервоара
•1 x уплътнение за порт, DN 100
•1 x уплътнение за порт, DN 50, за диафрагмена помпа,
1 1/2" връзка или вход, DN 50
•1 x комплект уплътнение, DN 80, 4 болта M16, гайки и
шайби (галванизирани
).
1. Символи в този документ
20
2. Съдържание на доставяния комплект
20
3. Общо описание
21
3.1 Приложения
21
4. Транспортиране и съхранение
21
5. Описание на продукта
21
5.1 Подемна станция
22
5.2 Контролер LC 220
24
6. Монтаж на подемната станция
27
6.1 Общо описание
27
6.2 Указания за монтаж на подемна станция
28
6.3 Препоръчителни стъпки за механичен монтаж на
подемната станция
28
7. Инсталиране на контролер LC 220
29
7.1 Местоположение
29
7.2 Механичен монтаж
29
7.3 Електрическо свързване
30
7.4 Настройка на LC 220
30
7.5 Схеми за свързване
31
8. Пуск
31
9. Поддръжка и сервизно обслужване
31
9.1 Електрическа поддръжка
32
9.2 Почистване на сензора за ниво
32
9.3 Замърсена подемна станция или компоненти от нея
32
10. Откриване на неизправности
33
11. Технически данни
34
11.1 Подемна станция
34
11.2 Контролер LC 220
34
12. Отстраняване на отпадъци
34
Предупреждение
Преди монтажа, прочетете тези инструкции за
експлоатация иработа. Монтажът
и експлоатацията трябва да съответстват на
местните правила и наредби и инженерната
практика.
Предупреждение
Използването на този продукт изисква познанеие
иопит в работата стози продукт.
Хора с намалени физически, осезателни или
умствени способности не трябва да използват
този продукт, ако не са под наблюдение или не са
инструктирани относно използването на продукта
от човека, отговорен за тяхната безопсаност.
Не се разрешава употребата на този продукт или
играта снего от деца.
Предупреждение
Ако тези инструкции за безопасност не се спазват,
това може да доведе до наранявания.
Предупреждение
Тези инструкции трябва да се спазват при работа
свзривообезопасени помпи.
Внимание
Неспазването на тези инструкции за безопасност
може да доведе до неизправност или повреда на
оборудването.
Указание
Бележки и инструкции, които улесняват работата
и осигуряват безопасна работа.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350
  • Page 351 351
  • Page 352 352
  • Page 353 353
  • Page 354 354
  • Page 355 355
  • Page 356 356
  • Page 357 357
  • Page 358 358
  • Page 359 359
  • Page 360 360
  • Page 361 361
  • Page 362 362
  • Page 363 363
  • Page 364 364
  • Page 365 365
  • Page 366 366
  • Page 367 367
  • Page 368 368
  • Page 369 369
  • Page 370 370
  • Page 371 371
  • Page 372 372
  • Page 373 373
  • Page 374 374
  • Page 375 375
  • Page 376 376
  • Page 377 377
  • Page 378 378
  • Page 379 379
  • Page 380 380
  • Page 381 381
  • Page 382 382
  • Page 383 383
  • Page 384 384
  • Page 385 385
  • Page 386 386
  • Page 387 387
  • Page 388 388
  • Page 389 389
  • Page 390 390
  • Page 391 391
  • Page 392 392
  • Page 393 393
  • Page 394 394
  • Page 395 395
  • Page 396 396
  • Page 397 397
  • Page 398 398
  • Page 399 399
  • Page 400 400

Grundfos Multilift MSS Installation And Operating Instructions Manual

Typ
Installation And Operating Instructions Manual

v iných jazykoch