inches
ENGLISH
IECEx DEK 20.0005U
DEKRA 20ATEX0011U II 2 G Ex eb IIC Gb
II 2 D Ex tb IIIC Db
Hazardous Locations
, AEx e IIC
Class I, Div. , Groups A, B, C, D
Class II, Div. , Groups F, G
Class III
Ex e IIC Gb U Ex tb IIIC Db U
Ta –55°C…+150°C Power ON IP66
Ta –55°C …+200°C Power OFF
Rated Voltage: V
Rated Current: A
Schedule of limitations
The maximum surface temperature depends on the
configuration of the heat tracing system, determined in
accordance with IEC/IEEE --.
Minimum ambient temperature: –°C
Maximum ambient temperature: +°C
Maximum operating temperature, power “on”: +°C
Maximum exposure temperature, power “off”: +°C
Installation instruction for low profile insulation splice kit
nVent RAYCHEM S-. For use with nVent RAYCHEM BTV,
QTVR, XTV and KTV heating cables.
WARNING: To prevent electrical shock or fire, this
product must be installed correctly. Water ingress must be
avoided before and during the installation.
De-energise circuits before installation or servicing.
Maximum nominal current rating of over-current protection: A
Persons involved in the installation and testing of electric
heat tracing systems shall be suitably trained in all special
techniques required. Installation shall be carried out under
the supervision of a qualified person
Ground fault equipment protection must be used on each
heating cable circuit as arcing may not be stopped
by conventional circuit breakers. Before installing this
product, read the instructions completely.
Keep ends of heating cables and kit components dry before
and during installation.
The electrically conductive covering (braid) of the heating
cable shall be connected to a suitable earthing terminal.
The presence of the heating cables shall be made evident
by the posting of caution signs or markings at appropriate
locations and/or at frequent intervals along the circuit
The insulation resistance of the heating cable shall be
measured and recorded after installation and shall not be
less than MOhm.
®
CAUTION: Prolonged or repeated contact with the
sealant in the core sealer may cause skin irritation. Wash
hands thoroughly. Overheating or burning the sealant will
produce fumes that may cause polymer fume fever. Avoid
contamination of cigarettes or tobacco. Consult MSDS VEN
for further information.
DEUTSCH
IECEx DEK 20.0005U
DEKRA 20ATEX0011U II 2 G Ex eb IIC Gb
II 2 D Ex tb IIIC Db
Ex-Bereiche:
®
, AEx e IIC
Class I, Div. , Groups A, B, C, D
Class II, Div. , Groups F, G
Class III
Ex e IIC Gb U Ex tb IIIC Db U
Ta –55°C…+150°C eingeschaltet IP66
Ta –55°C …+200°C ausgeschaltet
Bemessungsspannung: V
Nennstrom: A
Liste der Einschränkungen
Die maximale Oberflächentemperatur hängt von der
Konfiguration des Begleitheizungssystems ab, die gemäß
IEC/IEEE -- bestimmt wird“.
Minimale Umgebungstemperatur: –°C
Maximale Umgebungstemperatur: +°C
Maximale Betriebstemperatur, eingeschaltet: +°C
Maximale Einsatztemperatur, ausgeschaltet: +°C
Montageanleitung für die Flachprofil-
Verbindungsgarnitur S-
nVent RAYCHEM-Heizbändern BTV, QTVR, XTV und KTV.
und Bränden muß dieses Produkt vorschriftsmäßig montiert
werden. Das Eindringen von freuchtigkeit muß vor und
während der Montage vermieden werden.
Schalten Sie vor der Installation oder Wartung alle
Stromkreise spannungsfrei.
Maximale Nennstrombelastbarkeit des Überstromschutzes: A
Personen, die mit der Installation und Prüfung von
elektrischen Begleitheizungssystemen befasst sind, müssen
in allen erforderlichen Spezialtechniken entsprechend
geschult sein. Der Einbau muss unter der Aufsicht einer
sachkundigen Person durchgeführt werden.
Alle Heizkreise müssen über FI-Schutzschalter abgesichert
werden, da ein herkömmlicher Sicherungsautomat bei
Funkenbildung unter Umständen nicht anspricht.
Lesen Sie die Montageanleitung sorgfältig und vollständig,
bevor Sie mit der Montage beginnen.
Halten Sie die Enden der Heizkabel und die Komponenten
vor und während der Installation trocken.
Die elektrisch leitende Ummantelung (Geflecht) des
Heizkabels ist an eine geeignete Erdungsklemme
anzuschließen.
S-150
nVent.com/RAYCHEM | 3