Gorenje REA53IN TT Návod na obsluhu

Typ
Návod na obsluhu
USERS AND INSTALLATION MANUAL INDOOR UNIT R32
NAVODILA ZA UPORABO IN NAMESTITEV NOTRANJA ENOTA R32
UPUTSTVO ZA UPOTREBU I POSTAVLJANJE UNUTRAŠNJA JEDINICA R32
UPUTSTVO ZA UPOTREBU I POSTAVLJANJE UNUTRAŠNJA JEDINICA R32
UPUTSTVO ZA UPOTREBU I POSTAVLJANJE UNUTRAŠNJA JEDINICA R32
РЪКОВОДСТВО ЗА УПОТРЕБА И МОНТАЖ - ВЪТРЕШНО ТЯЛО R32
PRÍRUČKA POUŽÍVATEĽOV A INŠTALAČNÁ PRÍRUČKA
- VNÚTORNÁ JEDNOTKA R32
Thank you very much for purchasing this Air Conditioner. Please read this
use and installation instructions carefully before installing and using this
appliance and keep this manual for future reference.
FRANÇAIS
NEDERLANDS
USERS AND INSTALLATION MANUAL INDOOR UNIT R32
Thank you very much for purchasing this Air Conditioner. Please read this
use and installation instructions carefully before installing and using this
appliance and keep this manual for future reference.
ITALIANO
ESPAÑOL
DEUTSCH
ENGLISH
FRANÇAIS
PORTUGUÊS
NEDERLANDS
РУССКИЙ ЯЗЫК
safety instructions
1
Preparation before use
2
Safety Precautions
3
Identification of parts
12
Indoor unit
12
Outdoor unit
12
Display introduction
13
Maintenance
14
Protection
15
Troubleshooting
16
Installation instructions
17
Installation diagram
17
Select the installation locations
17
Indoor unit installation
18
Caution: Risk of fire/
flammable materials
WARNING: Servicing shall only be performed as recommended by the
equipment manufacturer. Maintenance and repair requiring the assistance of
other skilled personnel shall be carried out under the supervision of the
person competent in the use of flammable refrigerants.
Remote controller operating instructions. See "remote controller
instructions".
Contents
EN
To guarantee the unit work normally, please read the manual carefully before installation,
and try to install strictly according to this manual.
Do not let air enter the refrigeration system or discharge refrigerant when moving the
air conditioner.
Properly ground the air conditioner into the earth.
Check the connecting cables and pipes carefully, make sure they are correct and firm
before connecting the power of the air conditioner.
There must be an air-break switch.
After installing, the consumer must operate the air conditioner correctly according
to this manual, keep a suitable storage for maintenance and moving of the air
conditioner in the future.
Fuse of indoor unit: T 3.15A/5A 250VAC.
For 2,6kW~3,5kW models, fuse of outdoor unit: T 15A 250VAC
For 5,3kW models,
fuse of outdoor unit: T 20A 250VAC
The installation instructions for appliances that are intended to be permanently
connected to fixed wiring and have a leakage current that may exceed 10 mA,
shall state that the installation of a residual current device (RCD) having a rated
residual operating current not exceeding 30 mA is advisable.
Warning: Risk of electric shock can cause injury or death: Disconnect all remote
electric power supplies before servicing.
The maximum length of the connecting pipe between the indoor unit and outdoor
unit should be less than 5 meters. It will affect the efficiency of the air conditioner
if the distance longer than that length.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning use of the
appliance in a safe way and understand the hazards involved. Children shall not
play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.
The batteries in remote controller must be recycled or disposed of properly.
Disposal of Scrap Batteries --- Please discard the batteries as sorted municipal
waste at the accessible collection point.
If the appliance is fixed wiring, the appliance must be fitted with means for
disconnection from the supply mains having a contact separation in all poles that
provide full disconnection under over voltage category
111
conditions, and these
means must be incorporated in the fixed wiring in accordance with the wiring rules.
If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons to avoid a hazard.
The appliance shall be installed in accordance with national wiring regulations.
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be
carried out under the supervision of the person competent in the use of flammable
refrigerants.
The appliance shall not be installed in the laundry.
-1-
2
EN
For the multi system, the refrigerant refers to the multi outdoor unit.
When charging refrigerant into the system, make sure to charge in liquid state, if the
refrigerant of the appliance is R32.Otherwise, chemical composition of refrigerant
(R32) inside the system may change and thus affect performance of the air conditioner.
According to the character of refrigerant (R32, the value of GWP is 675), the
pressure of the tube is very high, so be sure to be careful when you install and repair
the appliance.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons to avoid a hazard.
Installation of this product must be done by experienced service technicians
professional installers only in accordance with this manual.
The temperature of refrigerant circuit will be high, please keep the
interconnection cable away from the copper tube.
Before using the air conditioner, be sure to check and preset the following.
Remote Control presetting
Each time after the remote control is replaced with new batteries or is energized, remote control auto presetting
heat pump. If the air conditioner you purchased is a Cooling Only one, heat pump remote controller can also be used.
Back-light function of Remote Control(optional)
Hold down any button on remote control to activate the back light. It automatically shuts off 10 seconds later.
Note: Back-light is an optional function.
Auto Restart Presetting
The air conditioner has an Auto-Restart function.
This appliance is made of recyclable or re-usable material. Scrapping must be carried out in compliance with local
waste disposal regulations. Before scrapping it, make sure to cut off the mains cord so that the appliance cannot
be re-used.
For more detailed information on handling and recycling this product, contact your local authorities who
deal with the separate collection of rubbish or the shop where you bought the appliance.
SCRAPPING OF APPLIANCE
This appliance is marked according to the European Directive 2012/19/EC,
Waste Electrical and Electronic Equipment (WEEE).
This marking indicates that this product should not be disposed
with other household wastes throughout the EU. To prevent possible harm to
the environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To return
your used device, please use the return and collection systems or contact the
retailer where the product was purchased. They can take this product for
environmentally safe recycling.
Preparation before use
Note
Preset
3
EN
Symbols in this Use and Care Manual are interpreted as shown below.
Be sure not to do.
Pay attention to such a situation.
Grounding is essential.
Warning: Incorrect handling could
cause a serious hazard, such as death,
serious injury, etc.
Use correct power supply in
accordance with the rating plate
requirement. Otherwise, serious
faults or hazard may occur, or a
fire maybe break out.
Keep the power supply circuit
breaker or plug from dirt.
Connect the power supply cord
to it firmly and correctly, lest an
electric shock or a fire break out
due to insufficient contact.
Do not use the power supply
circuit breaker or pull off the plug
to turn it off during operation.
This may cause a fire due to
spark, etc.
It is harmful to your health if the cool
air reaches you for a long time. It is
advisable to let the air flow be
deflected to all the room.
Prevent the air flow from reaching
the gas burners and stove.
Do not touch the operation buttons
when your hands are wet.
Never insert a stick or similar obstacle
to the unit. Since the fan rotates at high
speed, this may cause an injury.
Do not repair the appliance by yourself.
If this is done incorrectly, it may cause
an electric shock, etc.
Do not put any objects on the outdoor
unit.
ON
OFF
SMART MOD E
TEMP.
SUPER
FAN S P EED
TEMP.
FEEL SLEE P
It is the user's responsibility to
make the appliance be grounded
according to local codes or
ordinances by a licensed
technician.
CLOCK TI MER ON TI MER O FF
QUI ET D IM MER ECONO M Y
Turn off the appliance by remote control
firstly before cutting off power supply if
malfunction occurs.
ON
OFF
ON
OFF
4
EN
Do not knit, pull or press the
power supply cord, lest the
power supply cord be broken. An
electric shock or fire is probably
caused by a broken power
supply cord.
5
EN
Safety precautions
Precautions for using R32 refrigerant
For the multi system, the refrigerant refers to the multi outdoor unit. The basic installation work procedures
are the same as the conventional refrigerant (R410A). However, pay attention to the following points:
CAUTION
1.
Transport of equipment containing flammable refrigerants
Compliance with the transport regulations
2.
Marking of equipment using signs
Compliance with local regulations
3.
Disposal of equipment using flammable refrigerants
Compliance with national regulations
4.
Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer's
instructions.
5.
Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical
damage to the equipment inside the package will not cause a leak of the
refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together will
be determined by local regulations.
6.
Information on servicing
6-1 Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimized. For repair
to the refrigerating system, the following precautions shall be complied with
prior to conducting work on the system.
6-2 Work procedure
Work shall be undertaken under a controlled procedure to minimize the risk of
flammable gas or vapor being present while the work is being performed.
6-3 General work area
All maintenance staff and others working in the local area shall be instructed on
the nature of work being carried out. Work in confined spaces shall be avoided.
The area around the workspace shall be sectioned off. Ensure that the
conditions within the area have been made safe by control of flammable
material.
6-4 Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and
during work, to ensure the technician is aware of potentially flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with
flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically
safe.
6
EN
CAUTION
6-5 Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available
to hand.
Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
6-6 No ignition sources
No person carrying out work in relation to a refrigeration system which involves
exposing any pipe work that contains or has contained flammable refrigerant shall
use any sources of ignition in such a manner that it may lead to the risk of fire or
explosion.
All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and disposal,
during which flammable refrigerant can possibly be released to the surrounding
space.
Prior to work taking place, the area around the equipment is to be surveyed to make
sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall
be displayed.
6-7 Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work.
A degree of ventilation shall continue during the period that the work is carried out.
The ventilation should safely disperse any released refrigerant and preferably
expel it externally into the atmosphere.
6-8 Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification.
At all times the manufacturer's maintenance and service guidelines shall be
followed. If in doubt consult the manufacturer's technical department for
assistance.
The following checks shall be applied to installations using flammable
refrigerants:
The charge size is in accordance with the room size within which the
refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not
obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
7
EN
CAUTION
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
6-9 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures.
If a fault exists that could compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment, so all parties are advised. Initial
safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking;
That there no live electrical components and wiring are exposed while
charging, recovering or purging the system;
That there is continuity of earth bonding.
7.
Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected
from the equipment being worked upon prior to any removal of sealed covers, etc.
If it is necessary to have an electrical supply to equipment during servicing, then a
permanently operating form of leak detection shall be located at the most critical
point to warn of a potentially hazardous situation.
Attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is
affected.
This shall include damage to cables, excessive number of connections, terminals
not made to original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer
serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer's specifications.
NOTE:
The use of silicon sealant may inhibit the effectiveness of some types of
leak detection equipment. Intrinsically safe components do not have to be
isolated prior to working on them.
8.
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that this will not exceed the permissible voltage and current permitted for
the equipment in use.
Intrinsically safe components are the only types that can be worked on while
8
EN
CAUTION
live in the presence of a flammable atmosphere. The test apparatus shall be at the
correct rating.
Replace components only with parts specified by the manufacturer.
Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
9.
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects.
The check shall also consider the effects of aging or continual vibration
from sources such as compressors or fans.
10.
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks.
A halide torch (or any other detector using a naked flame) shall not be used.
11.
Leak detection methods
The following leak detection methods are deemed acceptable for systems
containing flammable refrigerants:
Electronic leak detectors shall be used to detect flammable refrigerants, but
the sensitivity may not be adequate, or may need re-calibration. (Detection
equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is suitable
for the refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the
refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use
of detergents containing chlorine shall be avoided as the chlorine may react
with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both
before and during the brazing process.
12.
Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other
purpose conventional procedures shall be used.
However, it is important that best practice is followed since flammability is a
consideration.
The following procedure shall be adhered to:
Remove refrigerant;
Purge the circuit with inert gas;
9
EN
CAUTION
Evacuate;
Purge again with inert gas;
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be “flushed” with OFN to render the unit safe. This
process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved, then venting to atmosphere,
and finally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system. When
the final OFN charge is used, the system shall be vented down to atmospheric
pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe-work are to take
place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and
there is ventilation available.
13.
Charging procedures
In addition to conventional charging procedures, the following requirements shall
be followed:
Ensure that contamination of different refrigerants does not occur when
using charging equipment.
Hoses or lines shall be as short as possible to minimize the amount of
refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure tested with OFN.
The system shall be leak tested on completion of charging but prior to
commissioning.
A follow up leak test shall be carried out prior to leaving the site.
14.
Decommissioning
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail.
It is recommended good practice that all refrigerants are recovered safely. Prior to the
task being carried out, an oil and refrigerant sample shall be taken in case analysis is
required prior to re-use of reclaimed refrigerant. It is essential that electrical power is
available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
10
EN
CAUTION
c) Before attempting the procedure ensure that:
Mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
All personal protective equipment is available and being used correctly;
The recovery process is always supervised by a competent person;
Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes
place.
g) Start the recovery machine and operate in accordance with manufacturer's
instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
I) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and
all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system
unless it has been cleaned and checked.
15.
Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of
refrigerant.
The label shall be dated and signed.
Ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
16.
Recovery
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the total system charge
is available.
All cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant).
Cylinders shall be complete with pressure relief valve and associated shut- off
valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before
recovery occurs.
The recovery equipment shall be in good working order with a set of
11
EN
CAUTION
instructions concerning the equipment that is at hand and shall be suitable for the
recovery of flammable refrigerants.
In addition, a set of calibrated weighing scales shall be available and in good
working order.
Hoses shall be complete with leak-free disconnect couplings and in good
condition.
Before using the recovery machine, check that it is in satisfactory working order, has
been properly maintained and that any associated electrical components are sealed
to prevent ignition in the event of a refrigerant release. Consult manufacturer if in
doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the
correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not
mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor to the
suppliers.
Only electric heating to the compressor body shall be employed to accelerate this
process.
When oil is drained from a system, it shall be carried out safely.
CAUTION
When moving or relocating the air conditioner, consult experienced service
technicians for disconnection and reinstallation of the unit.
Do not place any other electrical products or household belongings under indoor unit
or outdoor unit. Condensation dripping from the unit might get them wet and may
cause damage or malfunction of your property.
Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer.
The appliance shall be stored in a room without continuously operating ignition sources
(for example, open flames, an operating gas appliance or an operating electric heater).
Do not pierce or burn.
Be aware that refrigerants may not contain an odor.
To keep ventilation openings, clear of obstruction.
The appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specified for operation.
The appliance shall be stored in a room without continuously operating open
flames (for example an operating gas appliance) and ignition sources (for example
an operating electric heater).
12
EN
CAUTION
Any person who is involved with working on or breaking into a refrigerant circuit
should hold a current valid certificate from an industry-accredited assessment
authority, which authorizes their competence to handle refrigerants safely in
accordance with an industry recognized assessment specification.
Servicing shall only be performed as recommended by the equipment
manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be
carried out under the supervision of the person competent in the use of flammable
refrigerants.
Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer.
Appliance shall be installed, operated and stored in a room with a floor area
larger than 10 m
2
.
The installation of pipe-work shall be kept to a a room with a floor area larger than
10 m
2
.
The pipe-work shall be compliance with national gas regulations. The maximum
refrigerant charge amount is 2.5 kg.
Mechanical connectors used indoors shall comply with ISO 14903. When
mechanical connectors are reused indoors, sealing parts shall be renewed. When
flared joints are reused indoors, the flare part shall be re-fabricated. The
installation of pipe-work shall be kept to a minimum.
Mechanical connections shall be accessible for maintenance purposes.
Explanation of symbols displayed on the indoor unit or outdoor unit.
WARNING
This symbol shows that this appliance uses a flammable
refrigerant.
If the refrigerant is leaked and exposed to an external
ignition source, there is a risk of fire
CAUTION
This symbol shows that the operation manual should be
read carefully.
CAUTION
This symbol shows that a service personnel should be
handling this equipment with reference to the
installation manual.
CAUTION
This symbol shows that information is available such as the
operating manual or installation manual.
13
EN
Identification of parts
Front Panel
Air Intake
Display Panel
Emergency Panel
Air Outlet
Vertical Adjustment
Louver
Horizontal Adjustment
Louver
Air Filter
Remote Controller
Air Intake
Pipes and Power
Connection Cord
Drain Hose
Note: Condensate water drains
at COOLING or DRY operation.
Air Outlet
The figures in this manual are based on the external view of a standard model.
Consequently, the shape may differ from that of the air conditioner you have selected.
Indoor unit
Outdoor unit
The symbols may be different from these models, but the functions are similar.
13
Display introduction
Temperature indicator
Display set temperature.
It shows FC after 200 hours of usage as reminder to clean the filter.
After filter cleaning press the filter reset button located on the indoor unit behind the front
panel to reset the display. (optional)
Running indicator
Run
Timer
Sleep
Comp.
It lights up when the AC is running.
It flashes during defrosting.
Timer indicator
It lights up during set time.
Sleep indicator
It lights up in sleep mode.
Compressor indicator
It lights up when the compressor is on.
Super indicator
It lights up in super mode.
Mode indicator
Heating displays orange,others display white
Fan speed indicator
8
Signal Receptor
Smart WIFI indicator 10
It lights up during WIFI is on.
NANOE indicator
It lights up in NANOE mode.
9
5
4
3
2
VG/VL series
1
11
1
2
3
4
5
6
9
7
The symbols may be different from these models, but the functions are similar.
13
9
4
2
1
5
VT series
3
9
5
4
3
2
1
SF/DG (Right side)
series
9
4
2
1
5
3
SE series
The symbols may be different from these models, but the functions are similar.
13
NS/DE series
NT series
4
2
1
5
3
VQ/TE/TF/DA/DG(Middle)/DH/DL(Right side) series
The symbols may be different from these models, but the functions are similar.
13
VM series
4
5
1
2
4
2
3
5
1
2
4
9
NM/DF series
3
NK series
3
6
TA/TC series
1
TQ/TR series
9
optional
9
2
3
10
3
1
optional
4
9
9
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194

Gorenje REA53IN TT Návod na obsluhu

Typ
Návod na obsluhu