PACB29HP

Whirlpool PACB29HP Návod na obsluhu

  • Dobrý deň! Prečítal som si návod na použitie pre klimatizačné jednotky Whirlpool. Môžem Vám pomôcť s otázkami o funkciách, inštalácii, údržbe alebo riešením problémov. Návod obsahuje informácie o rôznych modeloch, ako aj o funkciách, ako je 6th Sense režim a tichý režim. Opýtajte sa ma čokoľvek!
  • Ako zapnem klimatizáciu?
    Ako vyčistím filter?
    Čo robiť, ak sa klimatizácia vypne a zobrazí sa chybový kód E5?
    Aká je minimálna vzdialenosť od horľavých povrchov?
Instructions for use
Gebrauchsanweisung
Directives d’utilisation
Gebruiksaanwijzing
Libretto di istruzioni
Instrucciones de uso
Instruções de utilização
Инструкции за използване
Návod k obsluze
Brugsanvisninger
Käyttöohjeet
Οδηγίες χρήσης
Használati útmutató
Bruksanvisning
Instrukcja użytkownika
Návod na používanie
Instrucţiuni de utilizare
Инструкция по эксплуатации
Bruksanvisning
Інструкції з використання
-3-
PACW29COL
PACW29CO BK
PACW29HP
PACW29HP BK
PACW212CO
PACW212HP
PACB29CO
PACB29HP
PACB212HP
ENGLISH Instructions for use Page 4
DEUTSCH Bedienungsanleitung Seite 19
FRANÇAIS Consignes d’utilisation Page 34
NEDERLANDS Gebruiksaanwijzing Pagina 49
ITALIANO Istruzioni per l’uso Pagina 64
ESPAÑOL Instrucciones de uso Página 79
PORTUGUÊS Instruções de utilização Página 94
БЪЛГАРСКИ Инструкциизаизползване Страница109
ČESKY Návod k obsluze Strana 124
DANSK Brugsanvisninger Side 139
SUOMI Käyttöohje Sivu 154
ΕΛΛΗΝΙΚΑ Οδηγίεςχρήσης Σελίδα169
MAGYAR Használati útmutató 184. oldal
NORSK Brukerveiledning Side 199
POLSKI Instrukcjaużytkownika Strona214
SLOVENSKÝ Návodnapoužívanie Strana229
ROMÂNĂ Instrucţiunideutilizare Pagina244
РУССКИЙ Инструкцияпоэксплуатации Страница259
SVENSKA Bruksanvisning Sidan 274
УКРАЇНСЬКА Інструкціїзвикористання стор.289
-4-
SAFETY INSTRUCTIONS
IMPORTANT TO BE READ AND OBSERVED
Download the complete instruction manual on docs.whirlpool.eu or call the phone
number shown on the warranty booklet.
Before using the appliance, read these safety instructions. Keep them nearby for future
reference.
These instructions and the appliance itself provide important safety warnings, to be
observed at all times. The manufacturer declines any liability for failure to observe
these safety instructions, for inappropriate use of the appliance or incorrect setting of
controls.
The appliance uses flammable refrigerant (R290),the maximum refrigerant charged
amount is 0.3kg.The appliance shall be installed,operated and stored in a room with a
floor area larger than 14.5m
2
. And the room should higher than 2.2 m.
The appliance was tested within 0.95 MPa - 1.05 MPa of external static pressures.
Very young children (0-3 years) should be kept away from the appliance. Young
children (3-8
years) should be kept away from the appliance unless continuously
supervised. Children from 8
years old and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and knowledge can use this
appliance only if they are supervised or have been given instructions on safe use and
understand the hazards involved. Children must not play with the appliance. Cleaning
and user maintenance must not be carried out by children without supervision.
PERMITTED USE
CAUTION: the appliance is not intended to be operated by means of an external
switching device, such as a timer, or separate remote controlled system.
This appliance is intended to be used in household and similar applications such as:
hotels and working offices.
This appliance is not for professional use.
Always turn off the air conditioner by remote control or power button on product
panel first.
Do not use the power supply circuit breaker or pull off the plug to turn it off.
Disconnect the air conditioner from the power supply if it is to be left unused for a long
period of time or during a hunder/lightning storm.
-5-
SAFETY INSTRUCTIONS
Never insert obstacle in the air outlet-risk of injury. Keep ventilation openings clear
of any obstruction.
INSTALLATION
The appliance must be handled and installed by two or more persons - risk of injury.
Use protective gloves to unpack and install - risk of cuts.
Installation, including electrical connections, and repairs must be carried out by a
qualified technician according to national wiring rules.
Do not repair or replace any part of the appliance unless specifically stated in the user
manual.
Keep children away from the installation site. After unpacking the appliance, make sure
that it has not been damaged during transport.
In the event of problems, contact the dealer or your nearest After-sales Service.
Once installed, packaging waste (plastic, styrofoam parts etc.) must be stored out of
reach of children - risk of suffocation.
The appliance must be disconnected from all remote power supply before any
installation operation - risk of electric shock.
During installation, make sure the appliance does not damage the power cable - risk
of fire or electric shock. Only activate the appliance when the installation has been
completed.
The flexible exhaust hose allows placement of the air conditioner between 23” and
67” (60 cm and 170 cm) from window or door. The appliance with supplementary heater
needs to be kept a minimum distance of 100 cm from the combustible surface.
-6-
SAFETY INSTRUCTIONS
Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
Disconnect power cord before moving the appliance.
ELECTRICAL WARNINGS
The power supply must be of rated voltage with special circuitry for the appliance.
The diameter of the power cord must comply with requirements.
It must be possible to disconnect the appliance from the power supply by unplugging.
The appliance must be earthed in conformity with national electrical safety standards.
The use of a time-delay fuse or time-delay circuit breaker is recommended. All
wiring must comply with local and national electrical regulations and be installed by a
qualified electrician.
Do not use extension leads, multiple sockets or adapters. The electrical components
must not be accessible to the user after installation. Do not use the appliance when you
are wet or barefoot. Do not operate this appliance if it has a damaged power cable or
plug, if it is not working properly, or if it has been damaged or dropped.
If the supply cord is damaged, it must be replaced with an identical one by the
manufacturer, its service agent or similarly qualified persons in order to avoid a hazard-
risk of electrical shock.
Ensure safe grounding and a grounding wire connected with the special grounding
system of the building, installed by professionals. The appliance must be fitted with
electrical leakage protection switch and an auxiliary circuit breaker with sufficient
capacity. The circuit breaker must also have a magnetic and a thermal tripping function
to ensure protection in case of short-circuit and overload.
Model 9K & 12K
Required capacity of circuit breaker 16A (Fuse Type: 9k A+ HP,T3.15A/250VAC; Others,T5A/250VAC)
CLEANING AND MAINTENANCE
WARNING: Ensure that the appliance is switched off and disconnected from the
power supply before performing any maintenance operation; never use steam cleaning
equipment - risk of electric shock.
DISPOSAL OF PACKAGING MATERIALS
The packaging material is 100% recyclable and is marked with the recycle symbol . The various parts of the packaging must
therefore be disposed of responsibly and in full compliance with local authority regulations governing waste disposal.
DISPOSAL OF HOUSEHOLD APPLIANCES
This appliance is manufactured with recyclable or reusable materials. Dispose of it in accordance with local waste disposal
regulations. For further information on the treatment, recovery and recycling of household electrical appliances, contact your
local authority, the collection service for household waste or the store where you purchased the appliance. This appliance is
marked in compliance with European Directive 2012/19/EU, Waste Electrical and Electronic Equipment (WEEE). By ensuring this
product is disposed of correctly, you will help prevent negative consequences for the environment and human health.
The symbol
on the product or on the accompanying documentation indicates that it should not be treated as domestic
waste but must be taken to an appropriate collection center for the recycling of electrical and electronic equipment.
DECLARATION OF CONFORMITY
The refrigerant gas being in a hermetically sealed system (R290, GWP 3 ).Please refer to the rating label for detailed information.
-7-
SAFETY INSTRUCTIONS
Explanation of symbols displayed unit.
WARNING
This symbol shows that this appliance uses a flammable
refrigerant.
If the refrigerant is leaked and exposed to an external ignition
source, there is a risk of fire
CAUTION
This symbol shows that the operation manual should be read
carefully
CAUTION
This symbol shows that a service personnel should be handling
this equipment with reference to the installation manual
CAUTION
This symbol shows that information is available such as the
operating manual or installation manual
SAFETY INSTRUCTIONS FOR SERVICING APPLIANCE WITH SPESIFIC REFRIGERANT
Download the complete manual for detailed installation, servicing, maintenance and
reparing methods on docs.whirlpool.eu.
Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer.
The appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specified for operation; without continuously
operating ignition sources (such as; open flames, an operating gas appliance or an
operating electric heater).
Do not pierce or burn. Be aware that the refrigerants may not contain an odor.
Any person who is involved with working on or breaking into a refrigerant circuit
should hold a current valid certificate from an industry-accredited assessment
authority, which authorizes their competence to handle refrigerants safely in
accordance with an industry recognized assessment specification. Servicing shall only
be performed as recommended by the equipment manufacturer. Maintenance and
repair requiring the assisstance of other skilled personnel shall be carried out under the
supervision of the person competent in the use of flammable refrigerants. Appliance
shall be installed, operated and stored in a room with a floor area larger than 14.5 m
2
. The
installation of pipe-work shall be kept to a room with a floor area larger than 14.5 m
2
. The
pipe-work shall be compliance with national gas regulations. The maximum refrigerant
charge amount is 0.3 kg.
When flared joints are reused , the flare part shall be re fabricated.
1. Transport of equipment containing flammable refrigerants shall be compliant with the
transport regulations.
2. Marking of equipment using signs shall be compliant with local regulations.
3. Disposal of equipment using flammable refrigerants shall be compliant with national
regulations.
Caution, risk of fire
C
-8-
SAFETY INSTRUCTIONS
4. The storage of equipment / appliances should be in accordance with the
manufacturers instructions.
5. Storage of packed (unsold) equipment Storage package protection should be
constructed such that mechanical damage to the equipment inside the package
will not cause a leak of the refrigerant charge. The maximum number of pieces of
equipment permitted to be stored together will be by local regulations.
6. Information on servicing.
6-1 Checks to the area
Prior to beginning work on system containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating
system the following precautions shall be complied with prior to conducting work on
the system.
6-2 Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of
flammable gas or vapour being present while the work is being performed.
6-3 General work area
All maintenance staff and others working in the local area shall be instructed on the
nature of work being carried out. Work in confied spaces shall be avoided.
6-4 Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during
work, to ensure the technician is aware of prtentially flammable atmospheres. Ensure
that hte leak detection equipment being used is suitable for use with flammable
refrigerants, i.e. non-sparking adequately sealed or intrinsically safe.
6-5 Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated
partsappropriate fire extinguishing equipment shall be avalaible to hand. Have a dry
powder or CO2 fire extinguisher adjacent to the charging area.
6-6 No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing
any pipe work that contains or has contained flammable refrigerant shall use any
sources of ignition in such a manner that it may lead to the risk of fire or explosion.
All possible ignition sources, including cigarette smoking, should be kept sufficiently
far away from the site of installation, repairing, removing and disposal, during which
flammable refrigerant can possibly be released to the surrounding space. Prior to work
taking place, the area around the equipment is to be surveyed to make sure that there
are no flammable hazards or ignition risks. “No Smoking signs shall be displayed.
6-7 Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into
the system or conducting any hot work. A degree of ventilation shall continue during
the period that the work is carried out. The ventilation should safely disperse any
released refrigerant and preferably expel it externally into the atmosphere.
-9-
SAFETY INSTRUCTIONS
6-8 Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose
and to the correct specification. At all times the manufacturer’s maintenance and
service guidelines shall be followed. If in doubt consult the manufacturers technical
department for assistance. The following checks shall be applied to installations using
flammable refrigerants:
- The actual refrigerant charge is in accordance with the room size within which the
refrigerant containing parts are installed;
- The ventilation machinery and outlets are operating adequately and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked
for the presence of refrigerant;
- Marking to the equipment continues to be visible and legible. Markings and signs that
are illegible shall be corrected;
- Refrigerating pipe or components are installed in a position where they are unlikely to
be exposed to any substance which may corrode refrigerant containing components,
unless the components are constructed of materials which are inherently resistant to
being corroded or are suitably protected against being so corroded.
6-9 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then
no electrical supply shall be connected to the circuit until it is satisfactory dealt with. if
the fault cannot be corrected immediately but it is necessary to continue operation, an
adequate temporary solution shall be used. This shall be reported to the owner of the
equipment so all parts are advised. Initial safety checks shall include:
- That capacitors are discharged: this shall be done in a safe manner to avoid possibility
of sparking;
- That there no live electrical components and wiring are exposed while charging,
recovering or purging the system;
- That there is continuity of earth bonding.
7. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from
the equipment being worked upon prior to any removal of sealed electrical supply to
equipment during servicing, then a permanently operating form of leak detection shall be
located at the most critical point to warn of a potentially hazardous situation. Particular
attention shall be paid to the following to ensure that by working on coelectrical
components. The casing is not altered in such a way that the level of protection is
affected. This shall include damage to cables, excessive number of connections, terminals
not made to original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely. Ensure that seals or sealing materials
have not degraded such that they no longer serve the purpose of preventing the
ingress of flammable atmospheres. Replacement parts shall be in accordance with the
manufacturers specifications.
NOTE:
The use of silicon sealant may inhibit the effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to be isolated prior to working on them.
8. Repair to intrinsically safe components
-10-
SAFETY INSTRUCTIONS
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring
that this will not exceed the permissible voltage and current permitted for the equipment
in use. Intrinsically safe components are the only types that can be worked on whilelive in
the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components onlywith parts specified by the manufacturer. Other parts may result
in the ignition of refrigerant atmosphere from a leak.
9. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects.The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or fans.
10. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
10. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants:
- Electronic leak detectors shall be used to detect flammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibration (Detection equipment shall
be calibrated in a refrigerant-free area.)
- Ensure that the detector is not a potential source of ignition and is suitable for the
refrigerant used.
- Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and
shall be calibrated to the refrigerant employed and the appropriate percentage of gas
(25% maximum) is confirmed.
- Leak detection fluids are also suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
- If a leak is suspected, all naked flames shall be removed/ extinguished.
- If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall
be recovered from the system, or isolated (by means of shut off valves) in a part of the
system remote from the leak.
11. Removal and evacuation
- When breaking into the refrigerant circuit to make repairs - or for any other purpose
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration.
The following procedure shall be adhered to:
- Remove refrigerant;
- Purge the circuit with inert gas;
- Evacuate;
- Purge with inert gas;
- Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.The system
shall be purged with OFN to render the appliance safe for flammable refrigerants. This
process may need to be repeated several times. Compressed air or oxygen shall not be
-11-
SAFETY INSTRUCTIONS
used for this task. Purging shall be achieved by breaking to fill until the working pressure is
achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process
shall be repeated until no refrigerant is within the system. When the final charge is used,
the system shall be vented down to atmospheric pressure to enable work. This operation
is absolutely vital if brazing operations, on the pipe-work are to take place. Ensure that the
outlet for the vacuum pump is not close to any potential ignition sources and there is the
vacuum in the system with OFN and continuing ventilation available.
12. Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed:
- Ensure that contamination of different refrigerants does not occur when using charging
equipment.
- Hoses or lines shall be as short as possible to minimize the amount of refrigerant
contained in them.
- Cylinders shall be kept in an appropriate position according to the instructions.
- Ensure that the refrigerating system is earthed prior to charging the system with
refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to overfill the refrigerating system. Prior to recharging the
system it shall be pressure tested with OFN.
The system shall be leak tested on completion of charging but prior to commissioning.
A follow up leak test shall be carried out prior to leaving the site.
13. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants
are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall
be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential
that electrical power is available before the task is commenced.
a. Become familiar with the equipment and its operation.
b. Isolate system electrically.
c. Before attempting the procedure ensure that:
- Mechanical handling equipment is available, if required, for handling refrigerant
cylinders;
- All personal protective equipment is available and being used correctly;
- The recovery process is supervised at all times by a competent person;
- Recovery equipment and cylinders conform to the appropriate standards.
d. Pump down refrigerant system, if possible.
e. If a vacuum is not possible, make a manifold so that refrigerant can be removed from
various parts of the system.
f. Make sure that cylinder is situated on the scales before recovery takes place.
g. Start the recovery machine and operate in accordance with instructions.
h. Do not overfill cylinders. (No more than 80 % volume liquid charge).
i. Do not exceed the maximum working pressure of the cylinder, even temporarily.
j. When the cylinders have been filled correctly and the process completed, make sure that
the cylinders and the equipment are removed from site promptly and all isolation valves
-12-
SAFETY INSTRUCTIONS
on the equipment are closed off.
k. Recovered refrigerant shall not be charged into another refrigerating system unless it
has been cleaned and checked.
14. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied
of refrigerant. The label shall be dated and signed. Ensure that there are labels on the
equipment stating the equipment contains flammable refrigerant.
15. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely. When transferring
refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for holding the total system charge
is available. All cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders
shall be complete with pressure relief valve and associated shutoff valves in good working
order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery
occurs. The recovery equipment shall be in good working order with a set of instructions
concerning the equipment that is at hand and shall be suitable for the recovery of
flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and
in good working order. Hoses shall be complete with leak free disconnect couplings and in
good condition. Before using the recovery machine, check that it is in satisfactory working
order, has been properly maintained and that any associated electrical components are
sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in
doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct
recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants
in recovery units and especially not in cylinders. If compressors or compressor oils are to be
removed, ensure that they have been evacuated to an acceptable level to make certain that
flammable refrigerant does not remain within the lubricant. The evacuation process shall be
carried out prior to returning the compressor to the suppliers. Only electric heating to the
compressor body shall be employed to accelerate this process. When oil is drained from a
system, it shall be carried out safely. When moving or relocating the air conditioner, consult
experienced service technicians for disconnection and reinstallation of the unit. Do not
place any other electrical products or household belongings under indoor unit or outdoor
unit. Condensation dripping from the unit might get them wet, and may cause damage
or malfunction of your property. To keep ventilation openings clear of obstruction. The
appliance shall be stored in a well-ventilated area where the room size corresponds
to the room area as specified for operation. The appliance shall be stored in a room without
continuously operating open flames (for example an operating gas appliance) and ignition
sources (for example an operating electric heater). Reusable mechanical connectors and
flared joints are not allowed.
-13-
User Interface
Start to use your air conditioner
1. Press the power button to start or stop the
operation of your appliance.
2. Press the mode button to select the
operation mode in sequence of Cool Dry,
Fan or Heat.
3. Press the temperature adjustment button to
set the desired temperature.
4. Press the FAN button to choose the desired
fan speed in sequence of High, Mid or Low.
Filter Reset
1. When the Filter Reset indicator light is lit,
remove, clean and replace the air filter. See
“Cleaning the Air Filter.
2. Press and release FILTER button after
replacing the air filter.
NOTE: After 360 hours of fan operating time,
the Filter indicatorlight will turn on. It will
remain on for 180 hours or until you press
FILTER button.
After 180 hours, it will turn off automatically.
IMPORTANT NOTE:
* When the air conditioner is turned on for the first time
after its plugged in, it will run in the 6th Sense Mode.
* The air conditioner display shows the setting
temperature.
Only on standby mode, the display shows the ambient
temperature.
* When changing modes while the air conditioner is
operating, the compressor will stop for 3 to 5 minutes
before restarting.
If a button is pressed during this time, the compressor
will not restart for another 3 to 5 minutes.
* In Cooling or Dry mode, the compressor and
condenser fan will stop when the room temperature
reaches the set temperature
* In Fan Only mode, the temperature can NOT be set.
* Heating is NOT available for Cooling only air
conditioner.
* Below operation modes can only be set by remote
controller.
* In the event of a power failure, your air conditioner will
operate at the previous settings when the power is
restored.
* If the unit is operating in UNLIKELY VERY HUMIDITY
environment, water will be collected in the tank inside
the unit. The air conditioner will stop once the water
tank is full, and the screen will display “E5 to inform
you to empty the internal container. There is a plasic
tube at the back of the appliance, move the appliance
to a safe place, lay down the plastic tube for water
drain.
-14-
Remote controller
Insert the batteries into RC
1. Insert a pin and gently press down on the battery
cover and push in the direction of the arrow to
remove, as shown.
2. Insert 2 AAA batteries (1.5V) into the compartment.
Ensure that “+ and “- polarity is correctly positioned.
3. Close the battery cover on the remote control.
Remote Control presetting
Each time the batteries are replaced in the remote
controller, the remote controller pre-set at Heat Pump
mode. The heat pump AC remote controller can be used
to control the cool only AC models.
The remote control will operate the air conditioner at a
distance of up to 7m.
Use RC to control the appliance
To operate the appliance by remote control, point the
remote control at the receiving device on the indoor
unit, to ensure receiving sensibility.
To send a message from remote control, the symbol
will flash for 1 second. On receipt of the message, the
appliance will emit a beep.
Note: please follow the intruction which matches to the remote controller you receive for Air Conditioner
operation.
Function description of buttons
1.
ON OFF BUTTON
Starts and/or Stops the appliance by pressing this button.
2. MODE BUTTON
Used to select the operation mode.
3. FAN BUTTON
Used to select fan speed in sequence auto, high, medium or low.
4-5. TEMPERATURE BUTTON
Used to select the room temperature. Used to set time in timer mode and real
time clock.
6. 6th SENSE BUTTON
Sets or cancels 6th Sense operation.In this mode,temperature and fan speed are
automatically set based on the actual room temperature.
7. SWING BUTTON
Stops or starts horizontal adjustment louver swinging and sets the
desired up/down airflow direction.
8. SLEEP BUTTON
1) Short press,sets or cancels Sleep Mode operation.Sleep Mode can be set in Cooling
Heating or Dry operation mode,this function gives you a more comfortable
environment for sleep.
2) Long press,press 3 senconds to turn on or turn off display light on unit.
9. AROUND U BUTTON
Used to start or cancel Around U function.When you press this button,remote control
transmits the actual room temperature around it to the indoor unit,and the appliance
will operate according this temperature to let you feel more comfortable.
10. TIMER BUTTON
Used to set or cancel the timer on operation.
Used to set or cancel the timer off operation.
11. SILENT BUTTON
Used to set or cancel the Silent operation.Press silent button to let the unit operate at low noise level to get quiet and
comfortable room environment.
Note:Under extreme environmental conditions,it is possible to notice a temporary slight increase in noise due to the need of reaching the comfort
temperature quickly.
Symbols on RC display
Cooling indicator Auto fan speed 6th Sense indicator Signal transmission
Dry indicator High fan speed Sleep indicator Display set timer
Fan only indicator Medium fan speed Around U indicator Display set temperature
Heating indicator Low fan speed Silent indicator
Signal receptor
-15-
Maintenance
Draining the Air Conditioner
(Please connect the drain hose on heating mode,otherwise
the unit will stop running after reachs warning level.)
1. Press ON/OFF to turn off the air conditioner.
2. Unplug air conditioner or disconnect power.
3. Move the appliance gently and stably to a draining
location or outside to drain water. Do not move the unit
before water is drained out completely.
4. Remove the secondary drain plug and drain water
completely.
5. Remove the primary drain hose from the hose clip.
Remove the drain hose plug from the end of the primary
drain hose and drain water completely.
NOTE: If air conditioner will be stored after use, see “Storing
After Use“.
6. Reinstall the drain hose plug and the secondary drain
plug.
7. Reattach the primary drain hose to the drain hose clip.
8. Reposition the air conditioner.
9. Plug in air conditioner or reconnect power.
10. Press ON/OFF to start the air conditioner.
Cleaning the Air Filter
1. Press ON/OFF to turn off the air conditioner.
2. Open the filter panel door on the back of the air
conditioner and remove it.
3. Remove the air filter from the filter panel door.
4. Use a vacuum cleaner to clean the filter. If filter is very
dirty, wash filter in warm water with a mild detergent.
NOTE: Do not wash filter in the dishwasher or use any
chemical cleaners.
5. Air dry filter completely before replacing to ensure
maximum efficiency.
6. Reattach the air filter to the filter panel door.
7. Reinstall filter panel door.
8. Press ON/OFF to start the air conditioner.
Cleaning the Outside
1. Unplug air conditioner or disconnect from power.
2. Remove the air filter and clean separately.
See“Cleaning the Air Filter.
3. Wipe outside of the air conditioner with a soft, damp
cloth.
4. Plug in air conditioner or reconnect power.
5. Press ON/OFF to start the air conditioner.
Disposal of the batteries
To protect natural resources and to promote material reuse, please separate batteries from other types of waste and
recycle them through your local, free battery return system.
Storing After Use
1. Drain the water (see the “Draining the Air
Conditioner”)
2. Run the air conditioner set to Fan Only for
approximately 12 hours to dry the air conditioner.
3. Unplug air conditioner.
4. Remove flexible exhaust hose and store with air
conditioner in a clean, dry area. See “Installation
Instructions.
5. Remove window kit and store with air conditioner
in a clean, dry area. See “Installation Instructions.
6. Remove the filter and clean. See “Cleaning the Air
Filter.
7. Clean the outside of air conditioner. See “Cleaning
the Outside.
8. Reinstall filter.
9. Remove the batteries and store the remote control
with air conditioner in a clean, dry area.
A. Secondary drain plug
B. Drain hose plug
A. Filter panel door
B. Air filter
-16-
Installation instruction
Tools and Parts
Gather the required tools and parts before starting
installation. Read and follow the instructions provided
with any tools listed here.
1. Tools needed
Phillips screwdriver
Saw
Cordless drill and 1/8” bit
Scissors
Pencil
2. Parts Supplied
The company provides only one plan to install local air
conditioner. See “Install local Air Conditioner.
Location Requirements
NOTES:
The flexible exhaust hose allows placement of the air
conditioner between 23 1/2” and 67” (60 cm and 170 cm) from
window or door.
The appliance with supplementary heater needs to keep a
minimum distance of 100 cm from the combustible surfaces.
The appliance shall be installed,operated and stored in a room
which floor area larger than 14.5 m² and higher than 2.2 m.
Local air conditioners are designed as supplemental cooling
to local areas within a room.
To ensure proper ventilation, keep the required distance from
the return air outlet to the wall or other obstacles at least
23 1/2” (60 cm).
Do not block air outlet.
Provide easy access to grounded outlet.
Electrical Requirements
The local air conditioner should be connected to a
220-240V / 50Hz, 20-amp fused grounded outlet.
The use of a time-delay fuse or time-delay circuit breaker is
recommended.
All wiring must comply with local and national electrical
regulations and be installed by a qualified electrician.
If you have any questions, contact a qualified electrician.
Use your power supply cord:
Plug power supply cord into a grounded outlet.
NOTES:
A damaged power supply cord must be replaced with a new
power supply cord obtained from the product manufacturer
and must not be repaired.
Working temperature of Cooling 21°C- 35°C
Working temperature of Heating 7°C-27°C
For detail installation information, please download from: docs.whirlpool.eu
A. Flexible exhaust hose
B. Window exhaust adapter
C. Outer slider section
D. Rain Cover
E. Inner slider section
Vertical
Silde Window
Horizontal
Silde Window
combustible surfaces
100 cm
60 cm - 170 cm
combustible surfaces
100 cm
60 cm - 170 cm
-17-
Troubleshooting
Operation problems are often due to minor causes, please check and refer to the following chart before
contacting the service. This may save time and unnecessary expenses.
Trouble Analysis
Air conditioner does
not operate
The power supply cord is unplugged. Plug into a grounded outlet. See “Electrical Requirements.
A household fuse has blown, or a circuit breaker has tripped. Replace the fuse, or reset the circuit
breaker. See “Electrical Requirements.
The On/Off button has not been pressed. Press ON/OFF.
The local power has failed. Wait for power to be restored.
Time-delay fuse or circuit breaker of the wrong capacity is being used. Replace with a time delay
fuse or circuit breaker of the correct capacity. See “Electrical Requirements.
Air conditioner blows
fuses or trips circuit
breakers
Too many appliances are being used on the same circuit. Unplug or relocate appliances that share
the same circuit.
You are trying to restart the air conditioner too soon after turning off air conditioner. Wait at least
3 minutes after turning off air conditioner before trying to restart it.
You have changed modes. Wait at least 3 minutes after turning off air conditioner before trying to
restart the appliance.
Air conditioner seems
to run too much
Is there a door or window open? Keep doors and windows closed.
In cooling mode: the air conditioner is in a heavily occupied room, or heat producing appliances
are in use in the room. Use exhaust vent fans while cooking or bathing and try not to use heat
producing appliances during the hottest part of the day. Local air conditioners are designed
as supplemental cooling to local areas within a room. A higher capacity air conditioner may be
required, depending on the size of the room being cooled.
In heating mode: the air conditioner is in a very cool room. Local air conditioners are designed
as supplemental heating to local areas within a room. A higher capacity air conditioner may be
required, depending on the size of the room being heated up.
Air conditioner runs for
a short time only, but
room is not cool or hot
Set temperature is close to room temperature. Lower or Higher set temperature.
See “Operating mode description.
Display error code If the unit display error code E5, it is water full in the unit, you should drain the water,
see “Draining the air conditioner”. After draining, you can operate the unit.
If the unit display error code EI/E2/E3/E6/E7/EA, please contact customer service.
Air conditioner runs,
but does not cool/hot
The filter is dirty or obstructed by debris. Clean the filter.
Air outlet is blocked. Clear air outlet.
The setting temperature is not compatible. In cooling mode: set temperature is too high.
Lower set temperature. In heating mode: set temperature is too low. Higher set temperature
Air conditioner cycles
on and off too much
The air conditioner is not properly sized for your room. Check the cooling/heating capabilities of
your local air conditioner. Local air conditioners are designed as supplemental cooling/heating to
local areas within a room.
The filter is dirty or obstructed by debris. Clean the filter.
In cooling mode there is excessive heat or moisture (open container cooking, showers,
etc.) in the room. Use a fan to exhaust heat or moisture from the room. Try not to use heat-
producing appliances during the hottest part of the day. In heating mode the temperature
of the environment is too high. Do not use your air conditioner when the temperature of the
environment is too high.
The louvers are blocked. Install the air conditioner in a location where the louvers are free from
curtains, blinds, furniture, etc.
The outside temperature is below 18°C. Do not try to operate your air conditioner in the cooling
mode when the outside temperature is below I8°C.
Note: If the problems still have, turn off the appliance and disconnect from power supply, then contact the
nearest Whirlpool Authorized Service Center. Do not attempt to move, repair, disassemble, or modify the
appliance by yourself.
-18-
AFTER SALES SERVICE
Before contacting the Customer Care Centre:
1. Try to solve the problem yourself based on the
descriptions given in the Troubleshooting.
2. Turn the appliance off and restart it to see if the fault
persists.
If after carrying out the above checks, the fault
persists, contact the Customer Care Centre.
Please give:
a short description of the fault;
the exact model of the air conditioner;
the service number (this is the number found below
the word Service on service sticker which is located on
the side or on the bottom of the indoor unit).
The service number can also be found in the warranty
booklet;
your full address;
your telephone number.
If repair work has to be carried out, contact the
Customer Care Centre (Use of original spare parts and a
proper repair is guarenteed).
You will need to present the original invoice.
Failure to comply with these instructions could
compromise the safety and quality of your product.
Note: if you want the full manual for your appliance, please help to download it from websit throught below
link: docs.whirlpool.eu using QR code
Whirlpool EMEA
Via Pisacane 1
20016 PERO (MI) ITALY
-19-
SICHERHEITSHINWEISE
DIESE MUSS GELESEN UND BEACHTET WERDEN
Laden Sie die komplette Bedienungsanleitung auf docs.whirlpool.eu runter oder rufen
Sie die Telefonnummer auf dem Garantieheft an.
Diese Sicherheitsanweisungen vor dem Gebrauch durchlesen. Diese Anweisungen zum
Nachschlagen leicht zugänglich aufbewahren.
In diesen Anweisungen sowie auf dem Gerät selbst werden wichtige
Sicherheitshinweise angegeben, die durchgelesen und stets beachtet werden
müssen. Der Hersteller übernimmt keine Haftung für die Nichtbeachtung dieser
Sicherheitshinweise, für unsachgemäße Verwendung des Geräts oder falsche
Bedienungseinstellung.
Das Gerät verwendet ein entzündliches Kältemittel (R290), die maximale Füllmenge
für das Kältemittel beträgt 0,3kg. Das Gerät sollte in einem Raum mit einer Grundfläche
von mehr als 14.5m
2
installiert, betrieben und gelagert werden. Zudem sollte der Raum
höher als 2,2 m sein.
Das Gerät wurde im verfügbaren externen statischen Druckbereich von 0,95 MPa -
1,05
MPa getestet.
Babys und Kleinkinder (0-3 Jahre) müssen vom Gerät ferngehalten werden. Jüngere
Kinder (3-8
Jahre) müssen vom Gerät ferngehalten werden, es sei denn, sie werden
ständig beaufsichtigt. Dieses Gerät darf von Kindern ab 8
Jahren sowie Personen mit
herabgesetzten physischen, sensorischen oder geistigen Fähigkeiten und Mangel an
Erfahrung und Kenntnissen nur unter Aufsicht oder nach ausreichender Einweisung
durch eine für ihre Sicherheit verantwortliche Person verwendet werden. Kinder dürfen
nicht mit dem Gerät spielen. Die Reinigung und Pflege des Gerätes darf von Kindern
nicht ohne Aufsicht durchgeführt werden.
ZUGELASSENE VERWENDUNG
VORSICHT Das Gerät ist nicht für den Betrieb mit einem externen Schalter, wie
Timer, oder separatem Fernbedienungssystem konstruiert.
Dieses Gerät ist für Haushaltsanwendungen und ähnliche Anwendungen konzipiert,
zum Beispiel: Hotels und Büros.
Dieses Gerät eignet sich nicht für den professionellen Einsatz.
Schalten Sie das Klimagerät immer erst über die Fernbedienung oder die POWER-
Taste am Bedienfeld des Geräts aus.
Schalten Sie dazu nicht den Leitungsschutzschalter aus und ziehen Sie nicht den
Stecker aus der Steckdose.
Trennen Sie das Klimagerät vor einem längeren Nichtgebrauch und bei Gewitter/Sturm
vom Stromnetz.
-20-
SICHERHEITSHINWEISE
Stecken Sie keine Gegenstände in den Luftauslass der Außeneinheit -
Verletzungsgefahr. Die Lüftungsöffnungen dürfen nicht behindert werden.
INSTALLATION
Zum Transport und zur Installation des Gerätes sind zwei oder mehrere Personen
erforderlich - Verletzungsgefahr. Schutzhandschuhe zum Auspacken und zur
Installation verwenden - Risiko von Schnittverletzungen.
Die Installation, einschließlich elektrischer Anschlüsse und Reparaturen
müssen von einem qualifizierten Techniker entsprechend den vor Ort geltenden
Sicherheitsvorschriften durchgeführt werden.
Das Gerät nicht selbst reparieren und tauschen keine Teile austauschen, wenn dies von
der Bedienungsanleitung nicht ausdrücklich vorgesehen ist.
Kinder vom Installationsort fern halten. Prüfen Sie das Gerät nach dem Auspacken auf
Transportschäden.
Bei auftretenden Problemen wenden Sie sich bitte an Ihren Händler oder den
Kundendienst.
Nach der Installation müssen Verpackungsabfälle (Kunststoff, Styroporteile usw.)
außerhalb der Reichweite von Kindern aufbewahrt werden - Erstickungsgefahr.
Das Gerät vor Installationsarbeiten von der netzfernen Stromversorgung trennen -
Stromschlaggefahr.
Während der Installation sicherstellen, das Netzkabel nicht mit dem Gerät selbst
zu beschädigen - Brand- oder Stromschlaggefahr. Das Gerät erst starten, wenn die
Installationsarbeiten abgeschlossen sind.
Dank des flexiblen Abluftschlauchs kann das Klimagerät in einer Entfernung von
23” und 67” (60 cm und 170 cm) vom Fenster oder der Tür aufgestellt werden. Bei einem
Gerät mit Zusatzheizung muss ein Mindestabstand von 100 cm von der entzündlichen
Oberfläche eingehalten werden.
Betreiben Sie das Klimagerät nicht in einem Nassraum wie Badezimmer oder
Waschküche.
Vor dem Umsetzen des Geräts das Netzkabel abziehen.
/