Nibe NIBE GBM 10-15 Installer And User Manual

Typ
Installer And User Manual
LEK
NIBE GBM 10-15
EN Installer and user manual
DE Installations- und bedienungsanleitung
Manuel d’installation et d’utilisation
F
Návod na instalaci a použití
CZ
SK Návod na inštaláciu a použitie
PL Instrukcja obsługi i instalacji kotła gazowego
Installations- og brugervejledning
DK
IHB GB 1312-1
231963
EN
DE
F
CZ
NIBE GBM 10-15 boilers comply with the essential requirements of the
following Directives:
- Gas Appliance Directive 2009/142/EC
- E ciency Directive 92/42/EEC
- Electromagnetic Compatibility Directive 2004/108/EC
- Low Voltage Directive 2006/95/EC
and therefore bears the EC marking
Installer manual 4
User guide 10
Technical data 12
Control panel 77
Appliance functional elements 80
Hydraulic circuit 82
Wiring diagrams 83
Circulator residual head 86
Les chaudières NIBE GBM 10-15 sont conformes aux principales condi-
tions requises des directives suivantes :
- Directive Gaz 2009/142/CE
- Directive Rendement 92/42/CEE
- Directive Compatibilité électromagnétique 2004/108/CE
- Directive basse tension 2006/95/CE
et donc elles portent le marquage CE
Manuel d’installation 14
Manuel de l’utilisateur 24
Données techniques 26
Panneau de commande 77
Éléments fonctionnels de la chaudière 81
Circuit hydraulique 83
Schémas électriques 84
Prévalence résiduelle du circulateur 87
NIBE GBM 10-15 Kessel erfüllen die wesentlichen Anforderungen der
folgenden Richtlinien:
- Gasgeräterichtlinie 2009/142/EG
- Richtlinie 92/42/EWG über die Wirkungsgrade von Warmwas-
serheizkesseln;
- Richtlinie 2004/108/EG über die elektromagnetische Verträglichkeit;
- Niederspannungsrichtlinie 2006/95/EG;
und tragen deshalb die EG-Kennzeichnung
Installateurshandbuch 25
Anwenderhandbuch 32
Technische Daten 34
Bedienfeld 77
Kesselbestandteile 81
Wasserkreis 83
Schaltpläne 84
Restförderhöhe der Umwälzvorrichtung 87
Kotle NIBE GBM 10-15 jsou ve shodě se základními požadavky níže uve-
dených směrnic:
- Směrnice pro plynová zařízení 2009/142/ES
- Směrnice o účinnosti 92/42/EHS
- Směrnice o elektromagnetické kompatibilitě 2004/108/ES
- Směrnice o nízkém napětí 2006/95/ES,
a proto jsou vybaveny označením CE (ES)
Manuál pro instalatéra 36
Manuál pro uživatele 42
Technické parametry 44
Ovládací pane 77
vládací prvky kotle 81
Hydraulický okruh 83
Elektrická schemata 84
Použitelná síla čerpadla 87
0694
0694BU1240
SK PL
DK
Kotle NIBE GBM 10-15 sú v zhode so základnými požiadavkami nižšie
uvedených smerníc:
- Smernica pre plynové zariadenia 2009/142/ES
- Smernica o účinnosti 92/42/EHS
- Smernica oelektromagnetickej kompatibilite 2004/108/ES
- Smernica o nízkom napätí 2006/95/ES
a preto sú vybavené označením CE (ES)
Návod pre inštalatéra 46
Užívateľský návod 52
Technické údaje 54
Ovládací panel 77
Funkčné prvky zariadenia 81
Rozvod vody 83
Schémy elektrického zapojenia 84
Zvyšková výtlačná výška cirkulátora 87
Kotły NIBE GBM 10-15 spełniają podstawowe wymagania następujących
dyrektyw:
- Dyrektywa 2009/142/WE odnosząca się do urządzeń spalających pa-
liwa gazowe
- Dyrektywa 92/42/EWG w sprawie wymogów sprawności kotłów
- Dyrektywa 2004/108/WE w sprawie kompatybilności elektroma-
gnetycznej (EMC)
- Dyrektywa niskonapięciowa (LVD) 2006/95/WE
i w związku z powyższym posiadają oznaczenie CE
Instrukcja montażu urządzenia 56
Podręcznik użytkownika 63
Dane techniczne 65
Panel sterowania 77
Podzespoły kotła odpowiedzialne za jego działanie 81
Obwód hydrauliczny 83
Schemat podłączenia przewodów 84
Wysokość podnoszenia pompy obiegowej 87
NIBE GBM 10-15 kedlerne er i overensstemmelse med de grundlæg-
gende krav i følgende Direktiver:
- Gasdirektiv 2009/142/EF
- E ektivitetsdirektiv 92/42/EØF
- Direktiv om Elektromagnetisk Kompatibilitet 2004/108/EF
- Lavspændingsdirektiv 2006/95/EF
og er således udstyret med CE-mærke
installationsvejledning 67
brugervejledning 73
tekniske speci kationer 75
Betjeningspanel 77
Funktionselementer på kedlen 81
Hydraulisk kredsløb 83
Multiledning ledningsdiagram 84
Resterende løftehøjde for cirkulator 87
0694
0694BU1240
4
1  WARNINGS AND SAFETY
The boiler is built with great attention to detail and every component is
checked in order to protect users and installers from injury. After work-
ing on the product, quali ed personnel must check the electrical wiring,
in particular the stripped part of conductors, which must not stick out
from the terminal board, avoiding possible contact with live parts of said
conductor.
This instruction manual, are integral parts of the product: make sure it
remains with the appliance, even if it is transferred to another owner or
user, or moved to another heating system. In case of loss or damage,
please contact your local Technical Assistance Service for a new copy.
Boiler installation and any other assistance and maintenance operations
must be carried out by quali ed personnel according to the provisions
of the legislation in force.
The installer must instruct the user about the operation of the appliance
and about essential safety regulations.
This boiler must only be used for the application it was designed for.
The manufacturer declines all contractual and non-contractual liability
for injury to persons or animals or damage to property deriving from
errors made during installation, adjustment and maintenance and from
improper use.
After removing the packaging, make sure the contents are in good
condition and complete. Otherwise, contact the dealer from whom you
purchased the appliance.
The safety valve outlet must be connected to a suitable collection and
venting system. The manufacturer declines all liability for any damage
caused due to any operation carried out on the safety valve.
Dispose of all the packaging materials in the suitable containers at the
corresponding collection centres.
Dispose of waste by being careful not to harm human health and without
employing procedures or methods which may damage the environment.
During installation, inform the user to:
- in the event of water leaks, the water supply must be shut o and the
Technical Assistance Service must be contacted immediately.
- it is necessary to periodically check that the operating pressure of
the hydraulic system is above 1 bar. If necessary, reset the pressure as
indicated in the paragraph entitled “Filling the system
- if the boiler is not used for a long time, the following operations are
recommended:
- turn the main switch of the appliance and the main switch of the system
to the “o position
- close the fuel and water taps of the heating system
- drain the heating system to prevent freezing.
For safety, always remember that:
the boiler should not be used by children or unassisted disabled people
it is dangerous to activate electrical devices or appliances (such as
switches, home appliances, etc.) if you smell gas or fumes. In the event
of gas leaks, ventilate the room opening doors and windows; close the
main gas tap; contact the Technical Assistance Service or professionally
quali ed personnel immediately
do not touch the boiler while barefoot, or if parts of your body are wet
or damp
before any cleaning operations, disconnect the boiler from the mains
power supply by turning the two-position system switch and the main
control panel switch to the “OFF” position
do not modify safety and adjustment devices without the manufacturer's
permission and relative instructions
do not pull, disconnect or twist the electric cables coming out of the
boiler, even when it is disconnected from the mains power supply
avoid covering or reducing the size of the ventilation openings in the
installation room
do not leave in ammable containers and substances in the installation
room
keep packaging materials out of the reach of children
it is forbidden to obstruct the condensate drainage point.
In some parts of the manual, some symbols are used:
WARNING = for actions requiring special care and adequate preparation
FORBIDDEN = for actions that MUST NOT be performed
INSTALLATION MANUAL
2  DESCRIPTION
Wall-mounted gas- red condensing boiler unit as a back-up heater for the NIBE
heat pump.
In a heating system with a heat pump, additional energy will be required when
outside temperatures are extremely low.
Instead of using an electric back-up heater, the required energy can be supplied
with the new gas- red condensing unit NIBE GBM 10-15. It backs up the heat
pump when required, so there is no need for additional electric heaters.
This signi cantly reduces the primary energy requirement for back-up heating
and increases the energy e ciency of the heat pump.
NIBE GBM 10-15 is a gas- red condensing boiler which modulates its output va-
riably in the range from 3.5 to 15 kW, so the required output is always adjusted
variably in accordance with current needs.
An external manager device performs all the relevant energy management fun-
ctions, switching the NIBE GBM 10-15 o and on through a control contact. So
you can be sure that there is always enough heat to warm your rooms and heat
your hot water – and that the entire system will be running at optimum e -
ciency.
This combination is ideal for renovations where there are existing gas connec-
tions or in new buildings where electrical connections are limited.
The NIBE GBM 10-15 gas- red condensing boiler unit is supplied ready-to-con-
nect, with integrated circulation pump and mounting kit.
An improper set up and installation would void the manufacturer’s guarantee.
Should you have any questions, please do not hesitate to contact our Technical
Customer Service.
3  INSTALLATION
3.1 - Installa tion regulations
Installation must be carried out by quali ed personnel, in accordance with the
local regulations. The boiler has protection that guarantees correct operation
with a temperature range from 0 °C to 60 °C.
The site of installation for the condensing back-up heater must satisfy the fol-
lowing minimum requirements:
Installation position
NIBE GBM 10-15 must be installed near the tank according the installation
drawing (see page. 17).
In order to allow access to the inside of the boiler for routine maintenance
operations, the minimum installation distances must be observed: at least 50
mm on each side ( g. 9).
Install the heater on a solid wall using the wall mounted platesupplied
Installation room
There are no special conditions for ventilation of the installation room for
ventilation-independent operations (using a concentric air/ ue gas system).
In limited ventilation-independent and ventilation-dependent operations,
the installation room must have a ventilation opening into open air according
to legislation.
For conditionally ventilation-independent and for ventilation-dependent
operations, the installation room must be free from aggressive vapours (e.g.
hair spray, perchlore ethylene, carbon tetrachloride), heavy dust formation
and high atmospheric humidity (e.g. washhouse).
3.2 Installing the unit
Assumption:
The site of installation follows country-speci c regulations, as well as the mi-
nimum requirements described in paragraph 3.1.
Installation:
NIBE GBM 10-15 is type C wall-mounted condensation boiler, this appliance is
designed for use only with the tank and it can be installed in any kind of room
and there are no limits as to ventilation or volume. For the installation refer to
draft in page 17.
Depending on which fumes discharge accessory is used, it is classi ed in the
following categories B23P; B53P; C13,C13x; C23; C33,C33x; C43,C43x; C53,C53x;
C63,C63x; C83,C83x, C93,C93x.
To position the boiler correctly, bear in mind that:
it must not be  tted over a cooker or other cooking appliance
it is forbidden to leave in ammable substances in the room
suitably insulate heat-sensitive walls (e.g.: in wood)
The position and size of the water connectors are shown in detail:
M water tank delivery 3/4”
G gas connection 3/4”
R water tank return 3/4”
Install as follows ( g. 8):
put the boiler support plate (A) to the wall and use a spirit level to check they
are perfectly horizontal
mark out 4 holes for  xing the boiler support plate
check the measurements and then drill the holes in the wall using a drill and
EN
5
the correct size of bit
–  x the plate to the wall
hook the boiler on the support plate
assembly the hydraulic pipes and gas tap using the gasket
connect the appliance
It is recommended to interpose water taps between boiler and tank for
maintenance operations.
3.3 Characteristics of heating circuit water
Make sure the characteristics of the water satisfy the parameters indicated in
the table.
Parameters um Water in HPSU tank
PH 7÷8
Hardness °F 15÷20
Appearance limpid
It is advised to  ll the tank with softened water at the  rst water  lling.
3.4 Condensate collection
During normal operation the boiler produces condense which is collected in a
trap located in theair box of the boiler.
Use the supplied rubber hose to connect the outlet of the trap to a suitable wa-
ste water collection and discharge system, in compliance with current legisla-
tion. The outlet connection line must have a guaranteed seal.
The manufacturer is not responsible for any damage caused by the lack of a col-
lection system.
Gas connection
Before connecting appliance to gas pipe network, check the following:
Regulations in force are met.
Gas type used is the same as set for appliance operation.
Pipes are clean.
Gas must be piped externally. It is recommended to install an appropriately si-
zed  lter on the gas line in case gas from the mains contains some small solid
particles. After installation make sure that all the joints have been made airtight
conforming to standard installation practices.
3.5 Electric connection ( g. 4)
To access the electrical wiring and terminal proceed as follows:
– turn o the main switch on the system
undo the  xing screws (D) on the housing ( g. 10)
move the base of the housing forwards and then upwards to unhook it from
the chassis
undo the  xing screw (E) from the instrument panel ( g. 11)
lift then turn the instrument panel towards you
detach the cover on the board casing ( g. 12)
the terminal for the control contact is located on the left side, connect it to the
manager device ( g. 12)
The contact must be potential free for low voltage input.
Reassemble the cover on the instrument panel and connect the appliance to
the mains power supply with a switch featuring a distance of at least 3,5 mm (EN
60335-1, category III) between each wire.
The appliance operates with an alternating current of 230 Volt/50 Hz, has a po-
wer input of 55 W and complies with EN 60335-1 standard.
Connect the boiler to an safe earth circuit according to current legislation.
Use the power cable supplied to connect the boiler to the mains power supply.
If the power cable needs to be replaced, use a cable of the HAR H05V2V2-F type,
3 x 0.75 mm2, with a maximum external diameter of 7 mm.
The installer is responsible for ensuring the appliance is suitably earthed;
the manufacturer declines all liability for any damage deriving from
incorrect or omitted earthing.
Live and neutral (L-N) connections should also be respected.
The earth conductor must be of 2 cm longer than the others.
The boiler can operate with phase-neutral or phase-phase power supply.
For  oating power supply, without an earth-bonded conductor, it is necessary to
use an insulation transformer with secondary anchored to ground.
Gas and/or water pipes may not be used to earth electrical equipment.
3.6 Filling the heater
Heater  lling
After making the hydraulic connections,  ll the tank; this must be done while
the installation is cold.
The  lling of the heater will be done automatically when the tank is  lled.
- Fill the tank using the proper instruction
- Open the water taps between heater and tank
- Connect the thin hose supplied with the boiler to the valve located over the
air box (B -  g. 15) in order to discharge the water into an external container.
- Power the boiler leaving the gas tap closed.
- The heater starts an automatic cycle for air discharge inside the circuit
- Use a CH11 wrench to open slowly the manual breather valve located over the
air distribution box ( g. 15)
- Leave water and air bubbles exit from the valve
- Just water exits from the hose close the manual valve.
- Open the gas tap and switch on the boiler.
Note: the boiler is bled automatically via the two automatic bleed valves A and
E ( g. 14), positioned on the circulator and inside the air distribution box respec-
tively. If you encounter problems bleeding the boiler, proceed as described in
paragraph 3.11.
3.7 Draining the heater
Before starting to drain the heater switch o the electrical supply by turning o
the main switch of the system.
Close any hydraulic taps between heater and tank
Manually loosen the system drain valve (D) and using the hose supplied drain
the boiler.
3.8 Bleeding the air from the heating circuit and heater
During the initial installation phase, or in the event of extraordinary maintenan-
ce, you are advised to perform the following sequence of operations:
1. Use a CH11 spanner to open the manual air vent valve located above the air
distribution box ( g.15). Connect the tube (supplied with the boiler) to the
valve, so the water can be drained into an external container.
2. Open the system  lling tap located on the hydraulic unit and wait until wa-
ter begins to drain out of the valve.
3. Switch on the electricity supply to the boiler, leaving the gas tap turned o .
4. Activate a heat request via the control input from the manager device.
5. Carry on with the sequence until only water leaks out of the manual air vent
valve, and the air  ow has stopped. Close the manual air vent valve.
6. Check the system pressure level is correct (the ideal level is 1 bar).
7. Turn o the system  lling tap.
8. Turn on the gas tap and ignite the boiler.
3.9 Flue gas discharge and air suction
Observe local legislation regarding  ue gas discharge.
Flue gases are discharged from a centrifugal fan located inside the combustion
chamber and the control board constantly checks that this is working correctly.
The boiler is supplied without the  ue gas discharge/air suction kit, since it is
possible to use the accessories for appliance with a forced draught sealed cham-
ber that better adapts to the installation characteristics.
For  ue gas extraction and the restoration of boiler combustion air, it is essential
to only use certi ed piping. Connection must be carried out correctly as indica-
ted in the instructions supplied as standard with the  ue gas accessories.
Multiple appliances can be connected to a single smoke pipe provided that each
is a sealed chamber-type appliance.
The boiler is a Type C appliance (sealed chamber), and must therefore have a
safe connection to the  ue gas discharge pipe and to the combustion air suction
pipe; these both carry their contents outside, and are essential for the operation
of the appliance.
We recommend using the corresponding NIBE  ue gas. They satisfy all require-
ments and are also  tted with special acid proof seals.
POSSIBLE OUTLET CONFIGURATIONS FIG. 21
B23P/B53P Suction indoors and discharge outdoors
C13-C13x Discharge via concentric wall outlet. The pipes may leave the boiler
independently, but the outlets must be concentric or su ciently close together
to be subjected to similar wind conditions (within 50 cm)
C23 Discharge via concentric outlet in common smoke pipe (suction and di-
scharge in the same pipe)
C33-C33x Discharge via concentric roof outlet. Outlets as for C13
C43-C43x Discharge and suction in common separate smoke pipes, but
subjected to similar wind conditions
C53-C53x Separate discharge and suction lines on wall or roof and in areas with
di erent pressures. The discharge and suction lines must never be positioned
on opposite walls
C63-C63x Discharge and suction lines using pipes marketed and certi ed se-
parately (1856/1)
C83-C83x Discharge via single or common smoke pipe and wall suction line
C93-C93x Discharge on roof (similar to C33) and air suction from a single exi-
sting smoke pipe
“FORCED OPEN” INSTALLATION TYPE B23P/B53P
Flue gas discharge pipe ø 80 mm ( g. 17)
The  ue gas discharge pipe can be directed to the most suitable direction accor-
ding to installation requirements. For installation, follow the instructions sup-
plied with the kit.
In this con guration, the boiler is connected to the  ue gas discharge pipe (ø 80
mm) through an adaptor (ø 60-80 mm).
In this case, the combustion air is picked up from the boiler installation
room (which must be a suitable technical room with proper ventilation).
Uninsulated ue discharge outlet pipes are potential sources of danger.
Arrange the  ue gas discharge pipe so it slopes by 1% towards the boiler.
The boiler automatically adapts the purging to the type of installation
and the length of the pipe.
6
Suction pipe length (m)
Discharge pipe length (m)
maximum length* of the  ue gas
discharge pipe ø 80 mm
pressure drop
45° bend 90° bend
115 m 1 m 1,5 m
* Straight length” means without bends, drainage terminals or joints.
“SEALED” INSTALLATION TYPE C
The boiler must be connected to concentric or twin  ue gas discharge pipes
and air suction pipes, both leading outdoors. The boiler must not be operated
without them.
Concentric pipes (ø 60-100 mm) ( g.18)
The concentric pipes can be placed in the most suitable direction according to
installation requirements, complying with the maximum lengths indicated in
the table.
Arrange the  ue gas discharge pipe so it slopes by 1% towards the boiler.
Non-insulated outlet pipes are potential sources of danger.
The boiler automatically adapts the purging to the type of installation
and the length of the pipe.
Do not obstruct or choke the combustion air suction pipe in any way.
For installation, follow the instructions supplied with the kit.
Horizontal
straight length *
concentric pipe ø 60-100 mm
pressure drop
45° bend 90° bend
7,8 m 1,3 m 1,6 m
* Straight length” means without bends, drainage terminals or joints.
Vertical
straight length *
concentric pipe ø 60-100 mm
pressure drop
45° bend 90° bend
8,8 m 1,3 m 1,6 m
* Straight length” means without bends, drainage terminals or joints.
Concentric pipes (ø 80-125)
For this con guration, the special adaptor kit must be  tted. The concentric pi-
pes can face in the direction most suitable for installation requirements. For in-
stallation, follow the instructions supplied with the speci c condensing boilers
kits.
straight length *
concentric pipe ø 80-125 mm
pressure drop
45° bend 90° bend
14,85 m 1,0 m 1,5 m
* Straight length” means without bends, drainage terminals or joints.
Twin pipes (ø 80 mm) ( g. 19)
The twin pipes can face in the direction most suited to the installation require-
ments.
For installation, follow the instructions supplied with the speci c accessory kit
for condensing boilers.
Arrange the  ue gas discharge pipe so it slopes by 1% towards the boiler.
The boiler automatically adapts the purging to the type of installation
and the length of the pipes. Do not obstruct or choke the pipes in any
way.
Refer to the graphs to  nd the maximum lengths of the single pipe.
The use of longer pipes reduces the boiler output.
maximum straight* length
twin pipes ø 80 mm
pressure drop
45° bend 90° bend
70+70 m 1,0 m 1,5 m
* Straight length” means without bends, drainage terminals or joints.
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170
4  STARTUP AND OPERATION
NIBE GBM 10-15 wall-mounted condensation boiler is designed for the produc-
tion of heating hot water for close vent tank
The control panel ( g. 9) contains the main boiler control and management fun-
ctions.
The heater must be controlled by the manafer device by means of
a controlcontact.
The appliance comes ready to be connected to the manager device,
therefore if this cable is not connected there is no possibility to switch
on the heater.
When the cable is connected to heater the manager device becomes
the master control for on and o status of the heater.
The main input given to the heater is only the on-o signal; the target  ow tem-
perature of the heater is 80 °C not modi able.
The reset of the alarms must be done directly on the heater control board rota-
ting the main selector as described in the speci c section.
4.1 - Switching on the appliance
Switch on the boiler as follows:
- open the gas tap under the heater by turning it anti-clockwise
- open any water taps installed between heater and tank
- turn on the general switch of the system and then turn the function selector
to ON position.
After being powered, the boiler begins an automatic vent cycle lasting approxi-
mately 2 minutes.
During this phase the three LEDs light up alternatively and the symbol is
shown on the display ( g. 22).
Working the boiler
The heater remains on stand-by until the burner ignites as a result of a demand
for heat from the manager device.
The indicator LED (1 -  g. 1), located on the left-hand side of the panel, lights up
with a  xed green light to indicate the  ame is present.
The heater continues to work until the temperature (80 °C) -  g. 24 - have been
reached and the demand for heat remains activated, then returns to “stand-by”.
In the event of a starting or operating fault, the boiler performs a “SAFETY STOP”:
the green indicator LED on the control panel goes out, a fault code  ashes on
the display control board and a red indicator LED ( g. 27) lights up in the event
of a shutdown.
To identify the fault codes and reset the boiler, consult the light symbols and
faults section .
Reset function
To reset the boiler, turned the function selector (3 -  g. 1) to , wait for 5-6 se-
conds and then move it to the ON position and check that the red indicator LED
has gone out ( g. 27).
At this point, the boiler starts automatically if correct operating conditions have
been restored; when the burner ignites, the indicator led lights up wit  xed gre-
en light and the display indicates the instantaneous operating temperature.
If the boiler continues not to work, call in the local Technical Assistance Service.
4.2 Switching o
Temporary switch-o
In case of absence for short periods of time, set the function selector (3 -  g. 1)
to (OFF).
In this way (leaving the electricity and fuel supplies enabled), the boiler is pro-
tected by the following systems:
Anti-frost device: when the temperature of the water in the boiler falls below
7
5°C, the circulator and, if necessary, the burner are activated at minimum output
levels to bring the water temperature back to the values for safety (35°C). During
the anti-frost cycle, the symbol ( g. 28) appears on the digital monitor.
Circulator anti-blocking function: an operation cycle is actvated every 24 hours.
Switching o for long periods
In case of absence for long periods of time, set the function selector (3 -  g. 1) to
(OFF). Turn the main system switch OFF.
Close the fuel and water taps of the heating.
In this case, anti-frost device is deactivated: drain the systems, in case of risk of
frost.
4.3 Light signals and faults
The control panel has three LEDs that indicate the boiler operating status:
Green LED
Flashing
Flashing (0.5 seconds on, then 3.5 seconds o ) = boiler in standby, there is no
ame.
Flashing (0.5 seconds on, then 0.5 seconds o ) = temporary shutdown of the
appliance due to the following automatic-reset faults:
- water pressure switch (standby time 10 minutes approximately)
- transitory waiting for ignition.
In this phase, the boiler waits for restoration of working conditions. If after the
standby time, the boiler does not restore regular operation, the shutdown will
be permanent and the signal light will be red.
Fixed green
there is  ame, the boiler works regularly.
Red LED
If the red LED lights up, this indicates the presence of a fault; the monitor shows
a code interpreted as follows:
To restore operation (deactivate alarms):
Faults A 01-02-03
Position the function selector (3 -  g.1) to (OFF), wait 5-6 seconds then set it
to ON position.
If the reset attempts do not reactivate the boiler, contact the Technical Assistan-
ce Centre.
Fault A 04
In addition to the fault code, the digital display shows the symbol .
Check the pressure value indicated by the water gauge:
if it is less than 0.3 bar, position the function selector (3 -  g.1) to (OFF) and
adjust the  lling tap of the system until the pressure reaches a value between 1
and 1.5 bar.
Then position the function selector (3 -  g.1) to the ON position.
The boiler will perform one purge cycle lasting approximately 2 minutes.
If pressure drops are frequent, request the intervention of the Technical Assi-
stance Service.
Fault A 06
Contact the Technical Assistance Centre.
Fault A 07
Contact the Technical Assistance Centre.
Fault A 08
Contact the Technical Assistance Centre.
Fault A 09 with  xed red LED lit
Position the function selector (3 -  g.1) to (OFF), wait 5-6 seconds then set it
to the ON position.
If the reset attempts do not reactivate the boiler, request the intervention of the
Technical Assistance Service.
Fault A 09 with  ashing red and green LEDs
The boiler is equipped with an auto-diagnostic system which, based on the total
number of hours in certain operating conditions, can signal the need to clean
the primary exchanger (alarm code 09 with  ashing red and green LEDs and  ue
gas meter >2,500). Once the cleaning operation has been completed, using the
special kit supplied as an accessory, the total hour meter will need to be reset to
zero as follows:
- switch o the power supply
- remove the housing
- loosen the  xing screw then turn the instrument panel
- loosen the  xing screws on the cover (F) to access the terminal board ( g. 13)
- while the boiler is powered up, press and hold the CO button ( g. 23) for at
least 4 seconds, to check the meter has been reset, power down then power
the boiler; the meter reading is shown on the monitor after the “-C-” sign.
Live electrical parts (230 V AC).
Note: the meter resetting procedure should be carried out after each in-depth
cleaning of the primary exchanger or if this latter is replaced. To check the status
of the total hour meter, multiply the reading by 100 (e.g. reading of 18 = 1800
total hours; reading of 1 = 100 total hours).
The boiler continues to operate normally even when the alarm is activated.
Fault A77
This is an automatic-reset fault, if the boiler does not restart, contact the Techni-
cal Assistance Centre.
Flashing yellow LED
Combustion analysis in progress.
DESCRIPTION DISPLAY CODE RED LED YELLOW LED GREEN LED
Flame lockout A01 ON OFF OFF
Limit thermostat intervention A02 ashes OFF OFF
Fan fault A03 ON OFF OFF
Water pressure switch fault A04 ON OFF ON
Domestic hot water NTC probe fault (not available) A06 ashes OFF ashes
Fault on heating delivery NTC probe or delivery-return di e-
rential circuit-breaker A07 ON OFF OFF
Fault on heating return NTC probe or return-delivery di e-
rential circuit-breaker A08 ON OFF OFF
Intervention of thermal safety device on  ue gas probe A09 ON OFF OFF
Flue gas NTC probe or heat exchanger cleaning A09 ashes OFF ashes
False  ame A11 ashes OFF OFF
Low temperature thermostat fault (not available) A77 ON OFF OFF
Combustion analysis procedure in progress ACO OFF  ashes OFF
8
4.4 Alarm records
The ALARM RECORDS” function starts automatically once the display has been
on for 2 hours, or immediately by setting the P1 parameter to 1.
The records include all the latest alarms, up to a maximum of 5 alarms, and they
are displayed in sequence by pushing and releasing the P1 button on the di-
splay board. If the records are empty (P0=0) or if tracking the same is disabled
(P1=0), the display function is not available.
Alarms are displayed in reverse order compared to the order in which they oc-
curred: this means that the last alarm generated is the  rst to be displayed. To
delete the alarms records, simply set parameter P0 to 0.
NOTE: To get to the P1 button the cover on the control panel must be removed
and the display board must be identi ed ( g. 29).
PROGRAMMING PARAMETERS
Functioning of the display can be personalised by programming three parame-
ters:
Parameter Default Description
P0 0 Deletion of alarms records
(0 = records empty / 1 = records not empty)
P1 0
Immediate activation of alarm record manage-
ment
(0 = delayed records management activated / 1 =
immediate records management activated
P2 0 Do not change
When button P1 on the display ( g. 29) is held down for at least 10 sec, the pro-
gramming procedure is activated. The three parameters, with their respective
values, are shown in rotation on the display ( g. 30). To edit a parameter value,
simply push the P1 button again when the required parameter is displayed, and
then hold it down until the value switches from 0 to 1 or vice-versa (approx. 2
sec).
The programming procedure is closed automatically after 5 minutes, or if there
is an electrical power failure
4.5 Boiler con guration
There is a series of jumpers (JPX) available on the electronic board which enable
the boiler to be con gured.
To access the board, proceed as follows:
- turn o the main switch on the system
- loosen the  xing screws on the housing, move the base of the housing
forwards and then upwards to unhook it from the chassis
- undo the  xing screws (E) from the instrument panel ( g. 11)
- loosen the screws (F -  g. 13) to remove the cover of the terminal board
(230V)
JP1 Calibration
JP2 Do not use
JP3 Calibration (see paragraph on Adjustments”)
JP4 Do not use
JP5 Jumper must be inserted
JP6 Do not use
JP7 Do not use
JP8 Jumper must be inserted
The boiler foresees jumpers JP5 and JP8 inserted as standard
4.6 Adjustments
The boiler has already been adjusted by the manufacturer during production. If
the adjustments need to be made again, for example after extraordinary main-
tenance, replacement of the gas valve, or conversion to another gas, observe
the following procedures.
The adjustment of the maximum and minimum output, and of the maximum
and minimum heating and of slow switch-on, must be made strictly in the se-
quence indicated, and only by quali ed personnel only:
- disconnect the boiler from the power supply
- move the function selector to the Service Area and turn it fully clockwise ( g.
26)
- loosen the  xing screws (E) on the instrument panel ( g. 11)
- lift then turn the instrument panel towards you
- loosen the xing screws on the cover (F) to access the terminal board ( g. 13)
- insert the jumpers JP1 and JP3 ( g. 32)
- power up the boiler
The three LEDs on the instrument panel  ash simultaneously and the display
shows ADJ” for approximately 4 seconds
Next change the following parameters:
1 - Absolute maximum
2 - Minimum
3 - Heating maximum
4 - Slow switch-on
as follows:
- turn the heating water temperature selector to set the required value
- press the CO button ( g. 23) and then skip to the calibration of the next para-
meter.
Live electrical parts (230 V AC).
The following icons light up on the monitor:
1. during absolute maximum calibration
2. during minimum calibration
3. during heating maximum calibration
4. during slow switch-on calibration
End the procedure by removing jumpers JP1 and JP3 to store these set values
in the memory.
The function can be ended at any time without storing the set values in the me-
mory and retaining the original values as follows:
- remove jumpers JP1 and JP3 before all 4 parameters have been set
- set the function selector to (OFF)
- cut the power supply 15 minutes after it is connected.
Calibration can be carried out without powering up the boiler.
By turning the function knob, the monitor automatically shows the
number of rotations, expressed in hundreds (e.g. 25 = 2,500 rpm).
The function for visualizing the setting parameters is activated by the function
selector in ON position, by pressing the CO button on the circuit board, either
with or without request for heat.
This function cannot be activated when connected to a remote control.
Upon activating the function the setting parameters are visualized in the order
given below, each for 2 seconds. Each parameter is displayed together with its
corresponding icon and fan rotation speed measured in hundreds.
1. Absolute Maximum
2. Minimum
3. Max. heating
4. Slow ignition P
5. Max. preset heating
GAS VALVE CALIBRATION
- Connect the boiler to the power supply
- Open the gas tap
- Set the function selector (3 -  g. 1) to (OFF) (monitor o )
- Loosen the screws (E -  g. 11), remove the housing, then lower the instrument
panel towards you
- Loosen the  xing screws on the cover (F) to access the terminal board ( g. 13)
- Press the CO button ( g. 23)
Live electrical parts (230 V AC).
- Wait for burner ignition.
The display shows ACO” and the yellow LED  ashes. The boiler operates at
maximum heat output.
The combustion analysis” function remains active for a limited time (15 min);
if a delivery temperature of 90°C is reached, the burner is switched o . It will
be switched back on when this temperature drops below 78°C.
- Insert the analyser probe in the ports provided in the air distribution box, after
removing the screws from the cover ( g. 33)
- Press the combustion analysis” button a second time to reach the number of
rotations corresponding to the maximum domestic hot water output (table
1); the yellow LED continues to  ash while the red LED is  xed
- Check the CO2 value: (table 3) if the value does not match the value given in
the table, use the gas valve maximum adjustment screw
- Press the combustion analysis” button a third time to reach the number of
rotations corresponding to the minimum output (table 2); the yellow LED
continues to  ash while the green LED is  xed
- Check the CO2 value: (table 4) if the value does not match the value given in
the table, use the gas valve minimum adjustment screw
- To exit the combustion analysis” function, turn the control knob
- Remove the  ue gas probe and re t the plug
- Close the instrument panel and re t the housing.
The combustion analysis” function is automatically deactivated if the board trig-
gers an alarm. In the event of a fault during the combustion analysis cycle, carry
out the reset procedure.
table 1
MAXIMUM NUMBER
OF FAN ROTATIONS METHANE
GAS (G20)
LIQUID GAS
(G31) G25
Heating 48 47 48 rpm
9
table 2
MINIMUM NUMBER
OF FAN ROTATIONS
METHANE
GAS (G20)
LIQUID GAS
(G31) G25
14 14 14 rpm
table 3
Max. CO2
METHANE
GAS (G20)
LIQUID GAS
(G31) G25
8,8 10 8,8 %
table 4
Min. CO2
METHANE
GAS (G20)
LIQUID GAS
(G31) G25
8,8 10 8,8 %
4.7 Gas conversion ( g. 34)
Conversion from a family gas to other family gas can be performed easily also
when the boiler is installed.
This operation must be carried out by professionally quali ed personnel.
The boiler is designed to operate with methane gas (G20) according to the pro-
duct label.
It is possible to convert the boiler to another gas, using the special kit.
For disassembly, refer to the instructions below:
- remove power supply from the boiler and close the gas tap
- remove the casing
- remove the gas pipe (A) -  g. 34
- remove the nozzle (B) -  g. 34 - contained in the gas train, and replace it with
the one supplied
- reassemble the gas train
- re-power the boiler and turn on the gas tap
Conversion must be carried out by quali ed personnel.
After conversion, adjust the boiler again (observing the Adjust-
ments” section) and apply the new identi cation label contained in
the kit.
4.8 Checking the combustion parameters (chimney sweep fun-
ction)
To carry out the combustion analysis, proceed as follows:
- turn the function selector in OFF position
- turn the chimney sweep selector from position to position ( g. 25) .
Live electrical parts (230 V AC).
- Wait for burner ignition (about 6 seconds). The display shows ACO”, the yel-
low LED  ashes and the boiler operates at maximum heat output.
- insert the analyser probe in the ports provided in the air distribution box, after
removing the screws from the cover ( g. 33)
- check that the CO2 values match those given in the table, if the value shown is
di erent, change it as indicated in the chapter entitled “Gas valve calibration.
- perform the combustion check.
Then:
- remove the analyser probe and close the sockets for combustion analysis with
the special screw
The ue gas analysis probe must be fully inserted as far as possible.
IMPORTANT
- Even during the combustion analysis phase, the function that switches the
boiler o when the water temperature reaches the maximum limit (about
90°C) remains enabled.
- The combustion analysis function remains active for 15 minutes; it is possible
to interrupt it in advance moving the chimney sweep selector in position.
5 MAINTENANCE
To ensure product characteristics and e ciency remain intact and to comply
with prescriptions of current regulations, it is necessary to render the appliance
to systematic checks at regular intervals.
When carrying out maintenance work, observe the instructions given in the
“Warnings and safety” chapter.
Turn o the appliance to carry out the maintenance of the structure near the  ue
discharge connections or devices, and their accessories. Once the interventions
are completed, a quali ed technician must check that the pipes and the devices
work correctly.
IMPORTANT: before carrying out any cleaning or maintenance operation of the
appliance, use the appliance and system switch to interrupt power supply and
close the gas supply turning the tap placed on the boiler.
Routine maintenance
This normally means the following tasks:
- removing any oxidation from the burner;
- removing any scale from the heat exchangers;
- removing any residue from the condensate drainage pipe;
- checking and cleaning the drainage pipes;
- checking the external appearance of the boiler;
- checking the ignition, switch-o and operation of the appliance, in both do-
mestic water mode and heating mode;
- checking the seal on the gas and water couplings and pipes;
- checking the gas consumption at maximum and minimum output;
- checking the position of the ignition- ame detection glowplug;
- checking the gas failure safety device.
Do not clean the appliance or its parts with easily in ammable substances (e.g.
benzine, alcohol, etc.).
Do not clean panels, painted parts or plastic parts with paint thinner.
Panel cleaning must be carried out only with soapy water.
Extraordinary maintenance
These tasks restore appliance operation in accordance with the design and regu-
lations - e.g. following the repair of an accidental fault.
This normally means:
- replacement
- repair
- overhaul of components
These tasks require special means, equipment and tools.
During the initial installation phase, or in the event of extraordinary
maintenance, you are advised to activate the procedure to discharge air
from the heating circuit and boiler (see the relevant paragraph).
6 SERIAL NUMBER
Heating function
Qn Nominal heat delivery
Pn Nominal heat output
IP Degree of Protection
Pms Maximum heating pressure
T Temperature
ŋ Performance
NOx NOx class
Qn =
N.
230 V ~ 50 Hz 165 W
NOx:
Gas type: Gas category:
kW
Pms = 3 bar T= 90 °C
Pn =
η
B23P-B53P-C13-C23-C33-C43-C53-C63
C83-C13x-C33x-C43x-C53x-C63x-C83x
Condensing Boiler
IP
kW
10
1A GENERAL WARNINGS AND SAFETY
The instruction manual is an integral part of the product and it must therefo-
re be kept carefully and must accompany the appliance; if the manual is lost
or damaged, another copy must be requested from the Technical Assistance
Service.
Boiler installation and any other assistance and maintenance operations
must be carried out by quali ed personnel according to the provisions
of local legislation.
For installation, it is advisable to contact specialised personnel.
The boiler must only be used for the application foreseen by the
manufacturer. The manufacturer shall not be liable for any damage to
persons, animals or property due to errors in installation, calibration,
maintenance or due to improper use.
The safety and automatic adjustment devices must not be modi ed,
during the system life cycle, by the manufacturer or supplier.
This appliance produces hot water, therefore it must be connected to
a heating system and/or a domestic hot water mains, compatible with
its performance and output.
In case of water leakage, close the water supply and contact the Techni-
cal Assistance Service immediately.
In case of absence for long periods time, close the gas supply and switch
o the electrical supply main switch. If there is a risk of frost, drain the
boiler.
From time to time check that the operating pressure of the hydraulic
system does not go below 1 bar.
In case of failure and/or malfunctioning, deactivate the appliance, and
do not try to repair or operate directly on it.
Appliance maintenance must be carried out at least once a year:
scheduling it with the Technical Assistance Service will avoid wasting
time and money.
Boiler use requires strict observation of some basic safety rules:
Do not use the appliance in any manner other than its intended pur-
pose.
It is dangerous to touch the appliance with wet or damp body parts
and/or when barefoot.
Under no circumstances cover the intake grids, dissipation grids and
ventilation vents in the installation room with cloths, paper or any other
material.
Do not use electrical switches, telephone or any other object that
causes sparks if there is a smell of gas. Ventilate the room by opening
doors and windows and close the central gas tap.
Do not place anything in the boiler.
Do not perform any cleaning operation if the appliance is not discon-
nected from the mains power supply.
Do not cover or reduce ventilation opening of the room where the
generator is installed.
Do not leave containers and in ammable products in the installation
room.
Do not attempt to repair the appliance in case of failure and/or mal-
functioning.
It is dangerous to pull or twist the electric cables.
Children or unskilled persons must not use the appliance.
Do not carry out operations on sealed elements.
For better use, remember that:
- periodic external cleaning with soapy water not only improves its appea-
rance but also preserves panelling from corrosion, extending its life cycle;
- if the wall-mounted boiler is enclosed in a hanging unit, leave at least 5 cm
for ventilation and maintenance;
- installation of a room thermostat will greatly improve comfort, a more ra-
tional use of the heat and energy saving; the boiler can also be connected
to a programmable timer in order to control the switching on and o of the
appliance during the day or week.
USER GUIDE
2A STARTUP AND OPERATION
NIBE GBM 10-15 wall-mounted condensation boiler isdesigned for the produc-
tion of heating hot water for close vent tank
The control panel ( g. 1) contains the main boiler control and management fun-
ctions.
The heater must be controlled by the manafer device by means of a
controlcontact.
The appliance comes ready to be connected to the manager device,
therefore if this cable is not connected there is no possibility to switch
on the heater.
When the cable is connected to heater the manager device becomes
the master control for on and o status of the heater.
The main input given to the heater is only the on-o signal; the target  ow tem-
perature of the heateris 80 °C not modi able.
The reset of the alarms must be done directly on the heater control board rota-
ting the main selector as described in the speci c section.
3A  SWITCHING ON THE APPLIANCE
Switch on the boiler as follows:
- open the gas tap under the heater by turning it anti-clockwise
- open any water taps installed between heater and tank
- turn on the general switch of the system and then turn the function selector
(3 -  g.1) to ON positon.
After being powered, the boiler begins an automatic vent cycle lasting approxi-
mately 2 minutes.
During this phase the three LEDs light up alternatively and the symbol is
shown on the display ( g. 22).
Working the boiler
The heater remains on stand-by until the burner ignites as a result of a demand
for heat from the manager device.
The indicator LED (1 -  g.1), located on the left-hand side of the panel, lights up
with a  xed green light to indicate the  ame is present.
The heater continues to work until the temperature (80 °C) have been reached
and the demand for heat remains activated, then returns to stand-by”.
In the event of a starting or operating fault, the boiler performs a “SAFETY STOP”:
the green indicator LED on the control panel goes out, a fault code  ashes on
the display control board and a red indicator LED lights up in the event of a
shutdown.
To identify the fault codes and reset the boiler, consult the light symbols and
faults section .
Reset function
To reset the boiler, turned the function selector (3 -  g.1) to , wait for 5-6 se-
conds and then move it to the ON position and check that the red indicator LED
has gone out.
At this point, the boiler starts automatically if correct operating conditions have
been restored; when the burner ignites, the indicator led lights up wit  xed gre-
en light and the display indicates the instantaneous operating temperature.
If the boiler continues not to work, call in the local Technical Assi-
stance Service.
4A SWITCHING OFF
Temporary switch-o
In case of absence for short periods of time, set the function selector (3 -  g.1)
to (OFF).
In this way (leaving the electricity and fuel supplies enabled), the boiler is pro-
tected by the following systems:
Anti-frost device: when the temperature of the water in the boiler falls below
5°C, the circulator and, if necessary, the burner are activated at minimum output
levels to bring the water temperature back to the values for safety (35°C). During
the anti-frost cycle, the symbol ( g. 28) appears on the digital monitor.
Circulator anti-blocking function: an operation cycle is activated every 24 hours.
Switching o for long periods
In case of absence for long periods of time, set the function selector (3 -  g.1)
to (OFF).
Turn the main system switch OFF.
Close the fuel and water taps of the heating.
In this case, anti-frost device is deactivated: drain the systems, in case of risk of
frost.
11
5A LIGHT SIGNALS AND FAULTS
The control panel has three LEDs that indicate the boiler operating status:
Green LED
Flashing
Flashing (0.5 seconds on, then 3.5 seconds o ) = boiler in standby, there is no
ame.
Flashing (0.5 seconds on, then 0.5 seconds o ) = temporary shutdown of the
appliance due to the following automatic-reset faults:
- water pressure switch (standby time 10 minutes approximately)
- transitory waiting for ignition.
In this phase, the boiler waits for restoration of working conditions. If after the
standby time, the boiler does not restore regular operation, the shutdown will
be permanent and the signal light will be red.
Fixed green
there is  ame, the boiler works regularly.
Red LED
If the red LED lights up, this indicates the presence of a fault; the monitor shows
a code interpreted as follows:
To restore operation (deactivate alarms):
Faults A 01-02-03
Position the function selector (3 -  g.1) to (OFF), wait 5-6 seconds then set it
to ON position.
If the reset attempts do not reactivate the boiler, contact the Technical Assistan-
ce Centre.
Fault A 04
In addition to the fault code, the digital display shows the symbol .
Check the pressure value indicated by the water gauge:
if it is less than 0.3 bar, position the function selector (3 -  g.1) to (OFF) and
adjust the  lling tap of the system until the pressure reaches a value between 1
and 1.5 bar.
Then position the function selector (3 -  g.1) to the ON position.
The boiler will perform one purge cycle lasting approximately 2 minutes.
If pressure drops are frequent, request the intervention of the Technical Assi-
stance Service.
Fault A 06
Contact the Technical Assistance Centre.
Fault A 07
Contact the Technical Assistance Centre.
Fault A 08
Contact the Technical Assistance Centre.
Fault A 09 with  xed red LED lit
Position the function selector (3 -  g.1) to (OFF), wait 5-6 seconds then set it
to the ON position.
If the reset attempts do not reactivate the boiler, request the intervention of the
Technical Assistance Service.
Fault A 09 with  ashing red and green LEDs
The boiler is equipped with an auto-diagnostic system which, based on the total
number of hours in certain operating conditions, can signal the need to clean
the primary exchanger (alarm code 09 with  ashing red and green LEDs and  ue
gas meter >2,500). Once the cleaning operation has been completed, using the
special kit supplied as an accessory, the total hour meter will need to be reset to
zero as follows:
- switch o the power supply
- remove the housing loosening the  xing screw then turn the instrument pa-
nel
- loosen the  xing screws on the cover (F) to access the terminal board ( g. 13)
- while the boiler is powered up, press and hold the CO button ( g. 23) for at
least 4 seconds, to check the meter has been reset, power down then power
up the boiler; the meter reading is shown on the monitor after the “-C-” sign.
Live electrical parts (230 V AC).
Note: the meter resetting procedure should be carried out after each in-depth
cleaning of the primary exchanger or if this latter is replaced. To check the status
of the total hour meter, multiply the reading by 100 (e.g. reading of 18 = 1800
total hours; reading of 1 = 100 total hours).
The boiler continues to operate normally even when the alarm is activated.
Fault A77
This is an automatic-reset fault, if the boiler does not restart, contact the Techni-
cal Assistance Centre.
Flashing yellow LED
Combustion analysis in progress.
12
TECHNICAL DATA
DESCRIPTION NIBE GBM 10-15
Nominal heat delivery in heating mode kW 15,00
kcal/h 12.900
Nominal heat output (80/60°) kW 14,61
kcal/h 12.565
Reduced nominal heat delivery (50°/30°) kW 15,62
kcal/h 13.429
Reduced heat delivery kW 3,50
kcal/h 3.010
Reduced heat output (80°/60°) kW 3,41
kcal/h 2.929
Reduced heat output (50°/30°) kW 3,62
kcal/h 3.112
Nominal Range Rated heat output (Qn) kW 15,00
kcal/h 12.900
Minimum Range Rated heat output (Qm) kW 3,50
kcal/h 3.010
Useful e ciency (Pn max - Pn min) % 97,4 - 97,3
E ciency 30% (47° return) % 100,9
Sedbuck 2005 (G 20 - G 31) % 90,08 - 90,74
Sdbuck SAP 2009 (G 20 - G 31) % 88,93 - 89,55
Useful e ciency Pn max - Pn min (50°/30°) % 104,1 - 103,4
Useful e ciency 30% (30° return) % 108,2
Average Range Rated e ciency Pn (80°/60°) % 97,5
Average Range Rated e ciency Pn (50°/30°) % 104,7
Electric power W 55
Category II2H3P
Category FR II2Esi3P
Category DE II2ELL3P
Power supply voltage V - Hz 230-50
Degree of Protection IP X5D
Pressure drops on  ue with burner on % 2,38
Pressure drops on  ue with burner o % 0,110.07
Heating operation
Pressure - maximum temperature bar 3-90
Minimum pressure for standard operation bar 0,25-0,45
Pump: maximum head available see graph at page 87
Gas pressure
Methane gas nominal pressure (G 20) mbar 20
Natural gas nominal pressure (G 25) mbar 20(DE)-25(FR)
LPG liquid gas nominal pressure (G 31) mbar 37(50 DE-AT)
Hydraulic connections
Heating input - output Ø 3/4”
Water tank delivery - output Ø 3/4”
Gas input Ø 3/4”
Boiler dimensions
Height mm 740
Width mm 400
Depth of housing mm 340
Boiler weight kg 30
Flow rate (G20-G25) G20 G25
Air capacity Nm3/h 19,105 18,752
Flue gas capacity Nm3/h 20,610 20,502
Mass  ow of  ue gas (max-min) gr/s 6,920-1,615 6,932-1,617
Flow rate (G31)
Air capacity Nm3/h 19,051
Flue gas capacity Nm3/h 19,633
Mass  ow of  ue gas (max-min) gr/s 6,628-1,546
Fan performance
Residual head of concentric pipes 0.85m Pa 55
Residual head separated pipes 0,5 m Pa 65
Residual head of boiler without pipes Pa 75
13
DESCRIPTION NIBE GBM 10-15
Concentric  ue gas discharge pipes
Diameter mm 60-100
Maximum length m 7,8
Drop due to insertion of a 45°/90° bend m 1,3/1,6
Hole in wall (diameter) mm 105
Concentric  ue gas discharge pipes
Diameter mm 80-125
Maximum length m 14,85
Losses for a 45°/90° bend m 1/1,5
Hole in wall (diameter) mm 130
Separate  ue gas discharge pipes
Diameter mm 80
Maximum length m 70+70
Losses for a 45°/90° bend m 1/1,5
Installation B23P–B53P
Diameter mm 80
Maximum length of drainage pipe m 115
NOx class class 5
Emission values at max. and min. rate of gas G20*
Maximum - Minimum CO s.a. less than ppm 100 - 5
CO2%8,8 - 8,8
NOx s.a. lower than ppm 20 - 23
Flue gas temperature °C 65 - 59
* Check performed with concentric pipe ø 60-100, length 0,85m - water temperature 80-60°C
DESCRIPTION Methane gas (G20) Methane gas (G25) Propane (G31)
Lower Wobbe index (at 15°C-1013 mbar) MJ/m3S 45,67 37,38 70,69
Net Calori c Value MJ/m3S 34,02 29,25 88
Supply nominal pressure mbar (mm W.C.) 20 (203,9) 20 (203,9) (DE)
25 (254,9) (FR)
37 (377,3)
50 (509,9) (DE-AT)
Supply minimum pressure mbar (mm W.C.) 10 (102,0) 18 (183,5)
Diaphragm (number of holes) Number 1 1 1
Diaphragm (diameter of holes) mm 4,4 5,0 3,5
Heating maximum gas capacity Sm3/h 1,59 1,85
kg/h 1,16
Heating minimum gas capacity Sm3/h 0,37 0,43
kg/h 0,27
Number of fan rotations with slow switch-on rpm 3.700 3.000 3.700
Maximum number of fan rotations (heating) rpm 4.800 4.800 4.700
Minimum number of fan rotations (heating) rpm 1.400 1.400 1.400
MULTIGAS TABLE
14
1  AVERTISSEMENTS ET SÉCURITÉS
La chaudière est construite avec une grande attention des détails et
chaque pièce est véri ée a n de protéger les utilisateurs et les instal-
lateurs de toute lésion. Après avoir travaillé sur le produit, le personnel
quali é doit véri er le câblage électrique, en particulier la partie dénudée
des conducteurs, qui ne soit pas sortir du bornier, en évitant tout contact
possible avec des parties sous tension dudit conducteur.
Ce manuel d'instruction est partie intégrante du produit : assurez-vous
qu'il reste toujours avec l'appareil, même en cas de cession à un autre
propriétaire ou utilisateur, ou en cas de mise en place sur un autre système
de chau age. En cas de perte ou de dommage, contacter votre Service
technique après-vente pour en obtenir un nouvel exemplaire.
L'installation de la chaudière et toute autre opération d'assistance et de
maintenance doivent être réalisées par un personnel quali é selon les
réglementations en vigueur.
Il est conseillé à l'installateur d'informer l'utilisateur sur le fonctionnement
de l'appareil et sur les règles fondamentales de sécurité.
Cette chaudière ne doit être utilisée que pour quoi elle a été conçue. Le
fabricant décline toute responsabilité contractuelle et non-contractuelle
en cas de lésions aux personnes ou animaux ou dommages aux biens
dérivant d'erreurs faites pendant l'installation, le réglage et la mainte-
nance et d'une utilisation incorrecte.
Après avoir enlevé l'emballage, assurez-vous que le contenu est en bon
état et complet. Autrement, contactez le distribution auprès duquel vous
avez acheté l'appareil.
La sortie de la vanne de sécurité doit être raccordée à un système de
collecte et de purge adapté. Le fabricant décline toute responsabilité
pour les dommages causés du fait d'une éventuelle opération réalisée
sur la vanne de sécurité.
Jeter tous les matériaux d'emballage dans les récipients adaptés dans
les centres de collecte correspondants.
Jeter les déchets en veillant à ne pas endommager la santé humaine et
sans employer de procédures ou méthodes susceptibles d'endommager
l'environnement.
Pendant l'installation, informer l'utilisateur que :
en cas de fuites d'eau, il faut couper l'alimentation en eau et avertir le
service technique après-vente immédiatement.
- il est nécessaire de véri er périodiquement que la pression de fonc-
tionnement du système hydraulique est supérieure à 1 bar. Si nécessaire,
réinitialiser la pression comme indiqué dans le paragraphe intitulé «
Remplissage du système »
- si la chaudière n'est pas utilisé pendant un long moment, les opérations
suivantes sont recommandées :
- tourner l'interrupteur principal de l'appareil et l'interrupteur principal
du système en position « o »
- fermer les robinets de combustible et d'eau du système de chau age
- purger le système de chau age pour éviter le gel.
Pour des raisons de sécurité, il faut toujours se souvenir que :
La chaudière ne doit pas être utilisée par des enfants ou des personnes
handicapées sans surveillance
il est dangereux d'activer des dispositifs électriques ou appareils (comme
des commutateurs, des appareils domestiques, etc) si vous sentez des
odeurs de gaz ou de fumées. En cas de fuites de gaz, aérez la pièce en
ouvrant les portes et les fenêtres ; fermer le robinet de gaz principal ;
contacter immédiatement le service après-vente technique ou un per-
sonnel professionnellement quali é
ne pas toucher la chaudière pieds nus, ou si des parties de votre corps
sont humides ou mouillées
avant toute opération de nettoyage, débrancher la chaudière du réseau
d'alimentation électrique en tournant l'interrupteur à deux positions et
l'interrupteur du panneau de commande principal en position « OFF »
Il est interdit de modi er les dispositifs de sécurité et de réglage sans la
permission et les instructions correspondantes du fabricant
il est interdit de tirer, débrancher, ou de tordre les câbles électriques
qui sortent de la chaudière, même quand ils sont déconnectés de
l'alimentation générale
éviter de couvrir ou de réduire la taille des ouvertures de ventilation dans
la salle d'installation
Dans certaines parties du manuel, certains symboles sont utilisés :
ATTENTION = actions demandant une certaine prudence et une
préparation adéquate
INTERDIT = pour les actions qui NE DOIVENT PAS être réalisées
MANUEL D'INSTALLATION
ne pas laisser de récipients et substances in ammables dans la salle
d'installation
conserver les matériaux d'emballage hors de portée des enfants
il est interdit d'obstruer le point de drainage de condensat
2  DESCRIPTION
Unité de chaudière à condensation murale alimentée au gaz comme chau age
de secours pour la pompe à chaleur NIBE.
Dans un système de chau age avec pompe à chaleur, de l’énergie supplémentai-
re sera requise lorsque les températures extérieures sont extrêmement basses.
Au lieu d’utiliser un chau age de secours électrique, l’énergie requise peut être
fournie avec la nouvelle unité de condensation alimentée au gaz NIBE GBM 10-
15. Elle soutient la pompe à chaleur quand cela est nécessaire, il n’est donc pas
nécessaire d’avoir des chau ages électriques supplémentaires.
Cela réduit considérablement les conditions requises en énergie primaire pour
un chau age de secours et cela augmente le rendement énergétique de la pom-
pe à chaleur.
NIBE GBM 10-15 est une chaudière à condensation alimentée au gaz qui module
son émission de manière variable dans la gamme de 3,5 à 15 kW, de sorte que
l’émission requise soit toujours ajustée de manière variable conformément aux
besoins actuels.
Un dispositif de gestion extérieur e ectue toutes les fonctions de gestion
énergétiques pertinentes, en allumant et en éteignant le NIBE GBM 10-15 à tra-
vers un contact par contrôle. Ainsi, vous pouvez être sûrs quil y a toujours su -
samment de chaleur pour chau er vos pièces et votre eau chaude - et que tout
le système fonctionnera au rendement optimal.
Cette combinaison est idéale pour les rénovations où il y a des connexions de
gaz existantes ou dans les nouveaux immeubles, où les connexions électriques
sont limitées.
L’unité de chaudière à condensation alimentée au gaz NIBE GBM 10-15 est
fournie prête à la connexion, avec une pompe de circulation et un kit de mon-
tage intégrés.
Un réglage et une installation incorrects annuleraient la garantie du fabricant.
Si vous avez des questions, n’hésitez pas à contacter notre service clients tech-
nique.
3  INSTALLATION
3.1 - Réglementations en matière d’Installation
L’installation doit être réalisée par un personnel quali é, conformément aux
réglementations locales. La chaudière a une protection qui garantit un fonction-
nement correct avec une gamme de température de 0°C à 60°C.
Le site d’installation pour le chau age de secours à condensation doit respecter
les conditions requises minimales suivantes :
Position d’installation
Le NIBE GBM 10-15 doit être installé près du réservoir selon le schéma d’instal-
lation (voir page 17).
– A n de permettre l’accès à l’intérieur de la chaudière pour des opérations
d’entretien ordinaire, les distances d’installation minimums doivent être re-
spectées : au moins 50 mm de chaque côté ( g. 9).
Installer le chau age sur une paroi solide en utilisant une plaque murale
fournie
Salle d’installation
Il n’y a pas de conditions particulières pour la ventilation de la pièce d’installa-
tion pour des opérations indépendantes de ventilation (en utilisant un système
air/gaz de combustion).
Dans des opérations dépendantes de la ventilation et indépendantes de la
ventilation limitées, la salle d’installation doit être dotée d’une ouverture de
ventilation à l’air libre conformément à la législation.
Pour des opérations dépendantes de la ventilation et indépendantes de la
ventilation conditionnelles, la salle d’installation doit être dénuée de vapeurs
agressives (par exemple laque pour les cheveux, perchloro-éthylène, tétrach-
lorure de carbone), de formation de poussières lourdes et d’humidité atmo-
sphérique élevée (par exemple lavage domestique).
3.1 Installation de l’unité
Hypothèse :
– Le site d’installation suit des réglementations spéci ques au pays, ainsi que
les conditions requises minimales décrites au paragraphe 3.1.
Installation:
Le NIBE GBM 10-15 est une chaudière à condensation murale de type C, cet ap-
pareil est conçu pour être utilisé avec le réservoir et il peut être installé dans
n’importe quel type de pièce et il nexiste aucune limite quant à la ventilation ou
au volume. Pour l’installation, consulter le projet à la page 17.
En fonction de l’accessoire d’évacuation des fumées qui est utilisé, il est classé
dans les catégories suivantes B23P; B53P; C13,C13x; C23; C33,C33x; C43,C43x;
C53,C53x; C63,C63x; C83,C83x.
F
15
Pour positionner correctement la chaudière, garder à l’esprit que :
elle ne doit pas installée au dessus d’une cuisinière ou d’un autre appareil de
cuisson
il est interdit de laisser des substances in ammables dans la pièce
isoler convenablement les parois sensibles à la chaleur (par exemple : en bois)
La position et la taille des connecteurs d’eau sont indiquées en détails :
M puissance du réservoir d’eau 3/4”
G raccord de gaz 3/4”
R retour de réservoir d’eau 3/4”
Installer comme suit ( g. 8) :
placer la plaque de support de la chaudière (A) sur la paroi et utiliser un niveau
pour véri er qu’elle est parfaitement horizontale
marquer 4 trous pour  xer la plaque de support de chaudière
– véri er les mesures puis percer les trous dans la paroi en utilisant une perceu-
se et la taille correcte de foret
–  xer la plaque à la paroi
accrocher la chaudière sur la plaque de support
assembler les tuyaux hydrauliques et le robinet de gaz en utilisant le joint
– brancher l’appareil
Il est recommandé d’intercaler des robinets d’eau entre la chaudière et
le réservoir pour des opérations de maintenance.
3.2 Caractéristiques de l’eau du circuit de chau age
Assurez-vous que les caractéristiques de l’eau satisfont les paramètres indiqués
dans le tableau.
Paramètres um Eau dans le réservoir HPSU
PH 7÷8
Dureté °F 15÷20
Aspect limpide
Il est conseillé de remplir le réservoir avec de l’eau douce lors du premier rem-
plissage d’eau.
3.3 Récupération des condensats
Pendant le fonctionnement normal, la chaudière produit de la condensation qui
est récoltée dans un piège situé dans le boîtier d’air de la chaudière.
Utiliser le tuyau en caoutchouc fourni pour raccorder la sortie du piège à une
collecte d’eau usée adaptée et décharger le système, conformément à la législa-
tion en cours. La ligne de connexion de sortie doit avoir un joint garanti.
Le fabricant nest pas responsable des dommages provoqués par l’absence d’un
système de récupération.
Raccord de gaz
Avant de raccorder l’appareil au réseau du tuyau de gaz, véri er ce qui suit :
Les réglementations en vigueur sont satisfaites.
Le type de gaz utilisé est le même que celui réglé pour le fonctionnement de
l’appareil.
Les tuyaux sont propres.
Le gaz doit être envoyé vers l’extérieur. Il est recommandé d’installer un  ltre
convenablement dimensionné sur la ligne de gaz si le gaz du réseau contient
de petites particules solides. Après l’installation, assurez-vous que tous les joints
ont été rendus étanches conformément aux pratiques d’installation standards.
3.4 Connexion électrique ( g. 4)
Pour accéder au câblage électrique et aux bornes, procéder comme suit :
- éteindre l’interrupteur principal sur le système
- défaire les vis de  xation (D) sur le logement ( g. 10)
- déplacer la base du logement vers l’avant puis vers le haut pour le décrocher
du châssis
- défaire la vis de  xation (E) du panneau de commande ( g. 11)
- levez puis tournez le panneau de commande vers vous
- détachez le couvercle sur le boîtier ( g. 12)
- la borne pour le contact de commande est située sur le côté gauche, la raccor-
der au dispositif de gestion ( g. 12)
Le contact doit être sans potentiel pour une entrée basse tension.
Remonter le capot sur le panneau de commande et brancher l’appareil à l’ali-
mentation électrique avec un commutateur présentant une distance d’au moins
3,5 mm (EN 60335-1, catégorie III) entre chaque  l.
L’appareil fonctionne avec un courant alternatif de 230 Volt/50 Hz, il a une entrée
de puissance de 55 W et est conforme à la norme EN 60335-1.
Connecter la chaudière à un circuit de terre sûr conformément à la législation
en vigueur.
Utiliser le câble électrique pour connecter la chaudière à l’alimentation générale.
Si le câble électrique doit être remplacé, utilisez un câble de type HAR H05V2V2-
F, de 3 x 0,75 mm2, avec un diamètre extérieur maximum de 7 mm.
L’installateur est responsable d’assurer une mise à la terre appropriée de
l’appareil; le fabricant décline toute responsabilité pour tout dommage
dérivant d’une mise à la terre incorrecte ou omise.
Les connexions phase et neutre (L-N) sont également à respecter.
Le conducteur de terre doit être plus long de 2 cm que les autres.
La chaudière fonctionne en alimentation phase-neutre ou phase-phase.
Pour l’alimentation  ottante, sans conducteur mis à la terre, il est nécessaire d’u-
tiliser un transformateur d’isolation avec un enroulement secondaire à la terre.
Ne pas utiliser de tuyaux de gaz et/ou d’eau pour la mise à la terre des appareils
électriques.
3.5 Remplissage du chau age
Remplissage du chau age
Après avoir e ectué les raccords hydrauliques, remplir le réservoir ; cela doit être
fait pendant que l’installation est froide.
Le remplissage du chau age sera e ectué automatiquement quand le réservoir
est rempli.
- Remplir le réservoir en utilisant les instructions ad hoc
- Ouvrir les robinets d’eau entre le chau age et le réservoir
- Connecter le tuyau mince fourni avec la chaudière à la vanne située sur le
boîtier d’air (B -  g. 15) a n de décharger l’eau dans un récipient extérieur.
- Alimenter la chaudière en laissant le robinet de gaz fermé.
- Le chau age démarre un cycle automatique pour la décharge d’air à l’intérieur
du circuit
- Utiliser une clé CH11 pour ouvrir lentement la vanne d’évent manuelle située
sur le boîtier de distribution d’air ( g. 15)
- Laisser l’eau et les bulles d’air sortir de la vanne
- Seule de l’eau sort du tuyau près de la vanne manuelle.
- Ouvrir le robinet de gaz et allumer la chaudière.
REMARQUE : la chaudière est automatiquement purgée via les deux soupa-
pes de purge automatiques A et E ( g. 14), positionnée sur le circulateur et à
l’intérieur du boîtier de distribution d’air respectivement. Si vous rencontrez
des problèmes pour purger la chaudière, procéder comme décrit dans le para-
graphe 3.11.
3.6 Drainage du chau age
Avant de démarrer le drainage du chau age, éteignez l’alimentation électrique
en éteignant le commutateur principal du système.
Fermer les robinets hydrauliques entre le chau age et le réservoir
Desserrer manuellement la vanne de vidange du système (D) et en utilisant le
tuyau fourni, drainer la chaudière.
3.7 Purge de l’air du circuit de chau age et du réchau eur
Pendant la phase d’installation initiale, ou en cas de maintenance extraordinaire,
vous êtes informé de réaliser la séquence suivante d’opérations :
1. Utiliser une clé CH11 pour ouvrir la vanne d’évent manuelle située au des-
sus du boîtier de distribution d’air ( g.15). Connecter le tube (fourni avec la
chaudière) à la vanne, de sorte que l’eau puisse être drainée dans un réci-
pient extérieur.
2. Ouvrez le robinet de remplissage du système situé sur l’unité hydraulique
jusqu’à ce que l’eau commence à sortir de la vanne.
3. Allumez l’alimentation électrique à la chaudière, en laissant le robinet de
gaz fermé.
4. Activez une demande de chaleur par le biais de l’entrée de commande de-
puis le dispositif de gestion.
5. Poursuivez la séquence jusqu’à ce quil n’y ait plus que de l’eau qui s’écoule
de la vanne d’aération manuelle et que le  ux d’air se soit arrêté. Fermez la
vanne d’aération manuelle.
6. Véri ez que le niveau de pression du système est correct (le niveau idéal est
d’1 bar).
7. Fermez le robinet de remplissage du système.
8. Ouvrez le robinet de gaz et allumez la chaudière.
3.8 Décharge de gaz de combustion et aspiration d’air
Respecter la législation locale concernant la décharge de gaz de combustion.
Les gaz de combustion sont déchargés d’un ventilateur centrifuge situé à
l’intérieur de la chambre de combustion et le panneau de commande véri e
constamment qu’il fonctionne correctement. La chaudière est fournie sans le kit
de décharge de gaz de combustion/aspiration d’air, puisqu’il est possible d’uti-
liser les accessoires pour un appareil avec une chambre scellé à air sou é qui
s’adapte mieux aux caractéristiques de l’installation.
Pour l’extraction de gaz de combustion et le rétablissement de l’air de combu-
stion de la chaudière, il est essentiel de n’utiliser qu’un tuyau certi é. La con-
nexion doit être réalisée correctement comme indiqué dans les instructions
fournies en standard avec les accessoires de gaz de combustion .
De multiples appareils peuvent être connectés à un tuyau de fumée unique à
condition que chaque appareil soit de type à chambre scellée.
La chaudière est un appareil de Type C (chambre scellée) et doit donc avoir une
connexion sûre au tuyau de décharge de gaz de combustion et au tuyau d’aspi-
ration d’air de combustion ; ils transportent tous deux leur contenu à l’extérieur
et sont essentiels pour le fonctionnement de l’appareil.
Nous recommandons d’utiliser le gaz de combustion NIBE correspondant. Ils sa-
tisfont toutes les conditions requises et sont également équipés de joints étan-
ches à l’acide spéci ques.
16
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0 102030405060708090100110120130140150160170
Longueur de tuyau d'aspiration (m)
Longueur de tuyau de décharge (m)
CONFIGURATIONS DE SORTIES POSSIBLES FIG. 21
B23P/B53P Aspiration intérieure et évacuation extérieure
C13-C13x Évacuation via refoulement mural concentrique. Les tuyaux peuvent
quitter la chaudière indépendamment mais les sorties doivent être concentri-
ques ou su samment proches pour être soumis à des conditions de vent simi-
laires (sur 50 cm)
C23 Évacuation concentrique dans un conduit de fumées commun (aspiration et
évacuation dans le même conduit)
C33-C33x Évacuation via refoulement concentrique au plafond. Sorties comme
pour C13
C43-C43x Évacuation et aspiration dans des conduits de fumées communs
séparés, mais soumis à des conditions de vent similaires
C53-C53x Évacuation et aspiration séparées murales ou au plafond et en zones
avec des pressions di érentes. Les tubes de décharge et d’aspiration ne doivent
jamais être positionnées sur des parois opposées
C63-C63x Tuyaux de refoulement et d’aspiration vendus et certi és séparément
(1856/1)
C83-C83x Refoulement via conduit de fumées traditionnel et tuyau d’aspiration
mural
C93-C93x Refoulement au plafond (similaire à C33) et aspiration d’air par un con-
duit de fumées simple
INSTALLATION FORCÉE EN OUVERTURE TYPE B23P/B53P
Tuyau de décharge de gaz de combustion ø 80 mm ( g. 17)
Le tuyau de décharge de gaz de combustion peut être dirigé dans la direction
la plus adaptée selon les exigences de l’installation. Pour l’installation, suivre les
instructions fournies avec le kit.
Dans cette con guration, la chaudière est raccordée au tuyau de décharge de
gaz de combustion (ø 80 mm) à travers un adaptateur (ø 60-80 mm).
Dans ce cas, l’air de combustion est prélevé de la salle d’installation de la
chaudière (qui doit être une salle technique adaptée avec une ventilation
correcte).
Des tuyaux de sortie de décharge non isolés sont des sources potentielles
de danger.
Disposer le tuyau de décharge de gaz de combustion de sorte qu’il ait
une pente de 1% vers la chaudière.
La chaudière adapte automatiquement la ventilation au type d’installation
et à la longueur du tuyau.
longueur maximale du tuyau d’échappement
de gaz de combustion ø 80 mm
chute de pression
45° pliure 90° pliure
115 m 1 m 1,5 m
*« Longueur droite » signi e sans pliure, bornes de drainage ou joints.
INSTALLATION  SCELLÉ  TYPE C
La chaudière doit être raccordée aux tuyaux de décharge concentriques ou de
gaz de combustion double et les tuyaux d’aspiration d’air, tous deux menant aux
portes extérieures. La chaudière ne doit pas être actionnée sans eux.
TUYAUX CONCENTRIQUES Ø 60100 MMFIG.18
Les tuyaux concentriques peuvent être placés dans la direction la plus adaptée
selon les exigences de l’installation, en se conformant aux longueurs maximales
indiquées dans le tableau.
Disposer le tuyau de décharge de gaz de combustion de sorte qu’il ait
une pente de 1% vers la chaudière.
Des tuyaux de sortie non isolés sont des sources potentielles de danger.
La chaudière adapte automatiquement la ventilation au type d’installation
et à la longueur du tuyau.
Ne jamais obstruer ou bloquer le tuyau d’aspiration d’air de combustion.
Pour l’installation, suivre les instructions fournies avec le kit.
Horizontal
longueur droite *
tuyau concentrique ø 60-100 mm
chute de pression
45° pliure 90° pliure
7,8 m 1,3 m 1,6 m
*« Longueur droite » signi e sans pliure, bornes de drainage ou joints.
Vertical
longueur droite *
tuyau concentrique ø 60-100 mm
chute de pression
45° pliure 90° pliure
8,8 m 1,3 m 1,6 m
*« Longueur droite » signi e sans pliure, bornes de drainage ou joints.
Tuyaux concentriques (ø 80-125)
Pour cette con guration, le kit adaptateur spécial doit être installé. Les tuyaux
concentriques peuvent faire face à la direction la plus adaptée pour les exigences de
l’installation. Pour linstallation, suivre les instructions fournies avec les kits de chau-
dières à condensation spéci ques.
longueur droite
tuyau concentrique ø 80-125 mm
chute de pression
45° pliure 90° pliure
14,85 m 1,0 m 1,5 m
*« Longueur droite » signi e sans pliure, bornes de drainage ou joints.
Tuyaux doubles (ø 80 mm) ( g. 19)
Les tuyaux doubles peuvent faire face à la direction la plus adaptée aux exigen-
ces de l’installation.
Pour l’installation, suivre les instructions fournies avec le kit d’accessoire spéci -
que pour les chaudières à condensation.
Disposer le tuyau de décharge de gaz de combustion de sorte qu’il ait
une pente de 1% vers la chaudière.
La chaudière s’adapte automatiquement à la purge du type d’installation
et à la longueur des tuyaux. Ne pas obstruer ou bloquer les tuyaux en
aucune façon
Consulter les graphiques pour trouver les longueurs maximales du tuyau
individuel.
L’utilisation de tuyaux plus longs réduit la puissance de la chaudière.
longueur droite maximum
tuyaux doubles ø 80 mm
chute de pression
45° pliure 90° pliure
70+70 m 1,0 m 1,5 m
*« Longueur droite » signi e sans pliure, bornes de drainage ou joints.
4  DÉMARRAGE ET OPÉRATION
La chaudière à condensation murale NIBE GBM 10-15 est conçue pour la produc-
tion d’eau chaude de chau age pour fermer le réservoir d’aération
Le panneau de commande ( g. 9) contient le contrôle de chaudière principal et
les fonctions de gestion.
Le chau age doit être contrôlé par le dispositif de gestion au moyen d’un
contact de contrôle.
L’appareil est prêt à être connecté au dispositif de gestion, donc, si ce
câble n’est pas connecté, il n’y a pas de possibilité d’allumer le chau age.
Quand le câble est raccordé au chau age, le dispositif de gestion devient
le contrôle principal pour un état allumé et éteint du chau age.
Lentrée principale donnée au chau age est seul le signal on-o ; la température
de  ux cible du chau age est de 80 °C non modi able.
La réinitialisation des alarmes doit être e ectuée directement sur la carte de
commande du chau age en tournant le sélecteur principal comme décrit dans
la section spéci que.
4.1 - Allumage de l’appareil
Allumer la chaudière comme suit :
- ouvrir le robinet de gaz sous le chau age en le tournant dans le sens contraire
aux aiguilles ;
- ouvrir des robinets d’eau installés entre le chau age et le réservoir
- allumer le commutateur général du système et puis tourner le sélecteur de
fonction sur la position ON.
Après avoir été alimenté, la chaudière commence un cycle d’aération automati-
17
que, la chaudière commence un cycle d’aération automatique durant approxi-
mativement 2 minutes.
Pendant cette phase, les trois LED s’allument alternativement et le symbole
est indiqué sur l’écran ( g. 22).
Fonctionnement de la chaudière
Le chau age reste en stand-by jusqu’à ce que le brûleur s’allume du fait d’une
demande de chaleur du dispositif de gestion.
La led de signalisation (1 -  g. 1), située sur le côté gauche du panneau, s’allume
avec une lumière verte  xe pour indiquer que la  amme est présente.
Le chau age continue de fonctionner jusqu’à ce que la température (80°C) -  g.
24 - ait été atteinte et que la demande de chaleur reste activée, puis revient en
« stand-by ».
Dans le cas d’une panne au démarrage ou en fonctionnement, la chaudière ef-
fectue un « ARRÊT DE SÉCURITÉ » : la led de signalisation verte sur le panneau de
commande s’éteint, un code de panne clignote sur le panneau de commande et
une led de signalisation rouge ( g. 27) s’allume en cas de panne.
Pour identi er les codes de panne et réinitialiser la chaudière, consulter les
symboles lumineux et la section des pannes.
Fonction réinitialisation
Pour réinitialiser la chaudière, tourner le sélecteur de fonction (3 -  g. 1) à ,
atteindre 5-6 secondes puis le déplacer sur la position ON et véri er que la led
de signalisation rouge s’est éteinte ( g. 27).
À ce stade, la chaudière démarre automatiquement si des conditions de fon-
ctionnement correctes ont été rétablies ; quand le brûleur s’allume, les témoins
de signalisation s’allument en vert  xe et l’écran indiquent la température de
fonctionnement instantanée.
Si la chaudière continue de ne pas fonctionner, appelez le Service technique
après-vente.
4.2 Arrêt
Arrêt temporaire
En cas d’absence pour de cours laps de temps, régler le sélecteur de fonction
(3 -  g. 1) sur (OFF).
De cette façon (en laissant l’alimentation électrique et l’alimentation en combu-
stible activées), la chaudière est protégée par les systèmes suivants:
Dispositif antigel : quand la température d’eau de la chaudière descend en des-
sous de 5°C, le circulateur et, au besoin, le brûleur sont activés à la puissance
minimale pour reporter la température de l’eau à des valeurs de sécurité (35°C).
Pendant le cycle antigel, le symbole ( g. 28) apparaît sur l’écran numérique.
Fonction anti-blocage circulateur : un cycle de fonctionnement est activé toutes
les 24 heures.
Arrêt pendant de longues périodes
En cas d’absence pour de longs laps de temps, régler le sélecteur de fonction
(3 -  g. 1) sur (OFF).
Éteignez l’interrupteur du système principal.
Fermer les robinets de combustible et d’eau du chau age.
Dans ce cas, la fonction antigel est désactivée : vider les systèmes, en cas de risque
de gel.
4.3 Signaux lumineux et pannes
Le panneau de commande a trois témoins qui indiquent l’état de fonctionne-
ment de la chaudière :
Témoin vert
Clignotant
Clignotant (0,5 seconde allumé, puis 3,5 secondes éteint) = chaudière en stand-
by, il n’y a pas de  amme.
Clignotant (0,5 seconde allumé, puis 0,5 seconde éteint) = arrêt temporaire de
l’appareil dû aux pannes réinitialisation automatique suivantes :
- pressostat d’eau (temps de standby environ 10 minutes)
- attente transitoire pour l’allumage.
Pendant cette phase, la chaudière attend le rétablissement des conditions de
fonctionnement. Si après le temps de standby, la chaudière ne rétablit pas le fon-
ctionnement régulier, l’arrêt sera permanent et le témoin du signal sera rouge.
Vert xe
il y a une  amme, la chaudière fonctionne régulièrement.
Témoin rouge
Si le témoin rouge s’allume, cela indique la présence d’une panne ; l’écran mon-
tre un code interprété comme suit :
Pour rétablir le fonctionnement (désactiver les alarmes):
Anomalies A 01-02-03
Positionnez le sélecteur de fonction (3 -  g.1) sur (OFF), attendre 5-6 secon-
des puis placez-le en position ON.
Si les tentatives de déblocage ne réactivent pas la chaudière, demander l’inter-
vention du Service après-vente.
Anomalie A04
En plus du code d’anomalie, l’a cheur numérique visualise le symbole .
Véri er la valeur de la pression indiquée par l’indicateur du niveau d’eau:
Si elle est inférieure à 0,3 bar, positionnez le sélecteur de fonction (3 -  g.1) sur
(OFF) et réglez le robinet de remplissage du système jusqu’à ce que la pression
atteigne une valeur comprise entre 1 et 1,5 bar.
Puis positionnez le sélecteur de fonction (3 -  g.1) en position ON.
La chaudière e ectuera un cycle de purge durant environ 2 minutes.
Si les chutes de pression sont fréquentes, demander l’intervention du service
Technique Après-vente.
Anomalie A06
Demander l’intervention du Service après-vente.
Anomalie A07
Demander l’intervention du Service après-vente.
Anomalie A08
Demander l’intervention du Service après-vente.
Panne A 09 avec témoin rouge  xe allumé
Positionnez le sélecteur de fonction (3 -  g.1) sur (OFF), attendez 5-6 secon-
des puis réglez-le sur la position ON.
Si les tentatives de déblocage ne réactivent pas la chaudière, demander l’inter-
vention du Service Après-vente.
Anomalie A 09 avec témoins rouge et vert clignotants
La chaudière est équipée d’un système d’auto-diagnostic qui, sur la base du
nombre total d’heures dans certaines conditions de fonctionnement, peut
signaler la nécessité de nettoyer l’échangeur primaire (code alarme 09 avec
témoins rouge et vert clignotants et dispositif de mesure des gaz de combustion
>2 500). Une fois le nettoyage terminé, remettre à zéro le compteur horaire avec
DESCRIPTION CODE D'AFFI-
CHAGE TÉMOIN ROUGE TÉMOIN JAUNE TÉMOIN
VERT
Blocage amme A01 Allumée OFF OFF
Intervention du thermostat limite A02 clignote OFF OFF
Panne de ventilateur A03 Allumée OFF OFF
Panne pressostat d'eau A04 Allumée OFF Allumée
Panne sonde NTC eau chaude domestique (non disponible)
A06 clignote OFF clignote
Panne sur sonde NTC de distribution de chauffage ou inter-
rupteur différentiel de retour-distribution A07 Allumée OFF OFF
Panne sur sonde NTC de retour de chauffage ou interrupteur
différentiel distribution-retour A08 Allumée OFF OFF
Intervention du dispositif de sécurité thermique sur sonde de
gaz de combustion A09 Allumée OFF OFF
Nettoyage sonde NTC de gaz de combustion ou échangeur
thermique A09 clignote OFF clignote
Fausse amme A11 clignote OFF OFF
Panne thermostat basse température (non disponible) A77 Allumée OFF OFF
Procédure d'analyse de combustion en cours ACO OFF clignote OFF
18
le kit spécial fourni en observant la procédure suivante:
- éteindre l’alimentation
- enlever le carter
- desserrer la vis de  xation puis tourner le panneau de commande
- desserrer les vis de  xation sur le capot (F) pour accéder au bornier ( g. 13)
- tandis que la chaudière est alimentée, appuyer sur le bouton CO et le main-
tenir enfoncé ( g. 23) pendant au moins 4 secondes, pour véri er que le
système de mesure a été réinitialisé, éteindre, puis rallumer la chaudière ; la
lecture du débitmètre est visualisée sur l’a cheur après le symbole « -C- ».
Pièces électriques sous tension (230 V AC).
REMARQUE: La procédure de remise à zéro du compteur doit être réalisée après
chaque nettoyage en profondeur de l’échangeur primaire ou si ce dernier est
remplacé. Pour contrôler l’état du compteur, multiplier la lecture par 100 (ex.
lecture de 18 = 1800 heures; lecture de 1 = 100 heures).
La chaudière continue à fonctionner normalement même lorsque l’alarme est
activée.
Anomalie A77
C’est une anomalie de remise à zéro automatique- si la chaudière ne redémarre
pas, contactez le Centre technique après-vente.
Témoin jaune clignotant
Analyse de combustion en cours.
4.4 Registres des alarmes
La fonction « REGISTRES DES ALARMES » commence automatiquement une fois
que l’écran a été allumé pendant 2 heures ou immédiatement en réglant le pa-
ramètre P1 sur 1.
Les registres comprennent toutes les dernières alarmes, jusqu’à un maximum
de 5 alarmes, et elles sont a chées en séquence en appuyant et en relâchant le
bouton P1 sur le panneau d’a chage. Si les registres sont vides (P0=0) ou si leur
suivi est désactivé (P1=0), la fonction d’a chage n’est pas disponible.
Les alarmes sont a chées dans l’ordre contraire à celui dans lequel elles sont
apparues : cela signi e que la dernière alarme générée est la première a chée.
Pour e acer le registre des alarmes, il su t de régler le paramètre P0 sur 0.
REMARQUE: Pour accéder au bouton P1, le capot sur le panneau de commande
doit être enlevé et le panneau d’a chage doit être identi é ( g. 29).
PARAMÈTRES DE PROGRAMMATION
Le fonctionnement de l’écran peut être personnalisé en programmant trois pa-
ramètres :
Par. Panne Description
P0 0 Suppression des registres d'alarmes
(0 = registres vides / 1 = registres non vides)
P1 0 Activation immédiate de la gestion du registre
d'alarme (0 = gestion des registres retardée acti-
vée / 1 = gestion immédiate des registres activée
P2 0 Ne pas changer
Quand le bouton P1 à l’écran ( g. 29) est maintenu enfoncé pendant au moins 10
sec, la procédure de programmation est activée. Les trois paramètres, avec leurs
valeurs respectives, sont indiquées en rotation à l’écran ( g. 30). Pour éditer une
valeur de paramètre, il su t de rappuyer sur le bouton P1 quand le paramètre
requis est a ché, puis le maintenir enfoncé jusqu’à ce que la valeur passe de 0 à
1 ou inversement (environ 2 sec).
La procédure de programmation est automatiquement fermée après 5 minutes,
ou en cas de panne électrique
4.5 Con guration de la chaudière
Il existe une série de cavaliers (JPX) disponibles sur la carte électronique qui per-
mettent la con guration de la chaudière.
Pour accéder à la carte, procéder comme suit:
- éteindre l’interrupteur principal sur le système
- desserrer les vis de  xation sur le logement, déplacer la base du logement en
avant puis vers le haut pour le décrocher du châssis
- défaire les vis de  xation (E) du panneau de commande ( g. 11)
- desserrer les vis (F -  g. 13) pour enlever le capot du bornier (230V)
JP1 Réglage
JP2 Ne pas utiliser
JP3 Réglage (voir le paragraphe sur les « Réglages »)
JP4 Ne pas utiliser
JP5 Le cavalier doit être inséré
JP6 Ne pas utiliser
JP7 Ne pas utiliser
JP8 Le cavalier doit être inséré
La chaudière prévoit que les JP5 et JP8 soient insérés en standard
4.6 Réglages
La chaudière a été préréglée en usine par le fabricant en phase de production.
Si les réglages doivent être refaits, par exemple après une maintenance extraor-
dinaire, le remplacement de la vanne de gaz, ou la conversion vers un autre gaz,
respecter les procédures suivantes.
Les réglages de la puissance maximum et minimum, de chau age maximum
et minimum et de l’allumage lent doivent être réalisés dans l’ordre indiqué et
exclusivement par le personnel quali é:
- couper la tension de la chaudière
- déplacer le sélecteur de fonction sur Zone de Service et le tourner totalement
dans le sens des aiguilles d’une montre ( g. 26)
- desserrer les vis de  xation (E) sur le panneau de commande ( g. 11)
- levez puis tournez le panneau de commande vers vous
- desserrer les vis de  xation sur le capot (F) pour accéder au bornier ( g. 13)
- insérer les cavaliers JP1 et JP3 ( g. 32)
- mettre la chaudière sous tension
Les trois témoins sur le panneau de commande clignotent simultanément et
l’écran a che « ADJ » pendant environ 4 secondes
Modi er ensuite les paramètres suivants:
1 - Maximum absolu
2 - Minimum
3 - Chau age maximum
4 - Allumage lent
comme suit:
- tourner le sélecteur de réglage de la température de l’eau de chau age pour
con gurer la valeur requise
- appuyer sur le bouton CO ( g. 23) et passer au réglage du paramètre suivant.
Parties électriques sous tension (230 V AC).
Les icônes suivantes s’allument sur le moniteur:
1. pendant le réglage du maximum absolu
2. durant le réglage du minimum
3. durant le réglage du chau age maximum
4. durant le réglage de l’allumage lent
Achever la procédure en retirant les cavaliers JP1 et JP3 a n de mémoriser les
valeurs con gurées.
La fonction peut être achevée à tout moment sans mémoriser les valeurs con -
gurées et en maintenant les valeurs originales comme suit:
- retirer les cavaliers JP1 et JP3 avant que les 4 paramètres aient été con gurés
- régler le sélecteur de fonction sur (OFF)
- couper l’alimentation 15 minutes après la connexion.
Le réglage peut être réalisé sans alimenter la chaudière.
En tournant le bouton de fonction, l’écran montre automatiquement le
nombre de rotations, exprimé en centaines (par ex. 25 = 2 500 trs/mn).
La fonction pour visualiser les paramètres de réglage est activée par le sélecteur
de fonction en position ON, en appuyant sur le bouton CO sur la carte de circuit,
avec ou sans demande de chaleur.
Cette fonction ne peut pas être activée si la commande à distance est branchée.
Lors de l’activation de la fonction, les paramètres de réglage sont visualisés dans
l’ordre indiqué ci-dessous, chacun pendant 2 secondes. Chaque paramètre est
a ché avec son icône correspondante et la vitesse de rotation du ventilateur
mesurée en centaines
1. Maximum absolu
2. Minimum
3. Chau age maximum
4. Allumage lent P
5. Chau age préréglé max.
RÉGLAGE DE LA VANNE DE GAZ
- Brancher la chaudière à l’alimentation électrique
- Ouvrir de robinet de gaz
- Régler le sélecteur de fonction (3 -  g. 1) sur (OFF) (écran éteint)
- Desserrer les vis (E -  g. 11), enlever le logement, puis baisser le panneau de
commande vers vous
- Desserrer les vis de  xation sur le capot (F) pour accéder au bornier
( g. 13)
- Appuyer sur le bouton CO ( g. 23)
Pièces électriques sous tension (230 V AC).
- Attendre l’allumage du brûleur.
Lécran indique « ACO » et le témoin jaune clignote. La chaudière fonctionne à
la puissance thermique maximum.
La fonction « analyse de combustion » reste active pendant une durée limitée
19
(15 min); si une température de refoulement de 90°C est atteinte, le brûleur
est éteint. Il est rallumé lorsque la température descend en dessous de 78°C.
- Insérer la sonde de l’analyseur dans les ori ces ménagés dans le boîtier de
distribution d’air, après avoir enlevé les vis du capot ( g. 33)
- Appuyer sur le bouton « analyse de combustion » une seconde fois pour at-
teindre le nombre de rotations correspondant à la puissance maximale de
l’eau chaude sanitaire (tableau 1) ; le témoin jaune continue de clignoter pen-
dant que le rouge est  xe
- Contrôler la valeur CO2: (tableau 3) si la valeur ne correspond pas à la valeur
fournie dans le tableau, utiliser la vis de réglage de maximum de la vanne de
gaz
- Appuyer sur le bouton « analyse de combustion » une troisième fois pour at-
teindre le nombre de rotations correspondant à la puissance minimale (table-
au 2) ; le témoin jaune continue de clignoter pendant que le vert est  xe
- Contrôler la valeur CO2: (tableau 4) si la valeur ne correspond pas à la valeur
fournie dans le tableau, utiliser la vis de réglage de minimum de la vanne de
gaz
- Pour sortir de la fonction « analyse de combustion », tourner la poignée de
commande
- Retirer la sonde de fumée et replacer le bouchon
- Fermer le panneau de commande et replacer le logement.
La fonction « analyse de combustion » est automatiquement désactivée si la
carte déclenche une alarme. En cas d’anomalie au cours du cycle d’analyse de
combustion, e ectuer une procédure de déblocage.
tableau 1
RÉGIME MAXIMUM
DU VENTILATEUR
MÉTHANE
(G20)
GAZ LIQUIDE
(G31) G25
Chau age 48 47 48 rpm
tableau 2
RÉGIME MINIMUM DU
VENTILATEUR
MÉTHANE
(G20)
GAZ LIQUIDE
(G31) G25
14 14 14 rpm
tableau 3
Max. CO2
MÉTHANE
(G20)
GAZ LIQUIDE
(G31) G25
8,8 10 8,8 %
tableau 4
Min. CO2
MÉTHANE
(G20)
GAZ LIQUIDE
(G31) G25
8,8 10 8,8 %
4.7 Conversion de gaz ( g. 34)
La conversion d’une famille de gaz à une autre peut être réalisée facilement éga-
lement quand la chaudière est installée.
Cette opération doit être réalisée par un personnel professionnellement quali é.
La chaudière est conçue pour fonctionner avec du gaz méthane (G20) selon l’éti-
quette du produit.
Il est possible de convertir la chaudière en un autre gaz, en utilisant le kit spécial.
Pour le démontage, consulter les instructions ci-dessous :
- couper l’alimentation électrique de la chaudière et fermer le robinet de gaz
- enlever le boîtier
- enlever le tuyau de gaz (A) -  g. 34
- enlever le gicleur (B) -  g. 34 - contenu dans la rampe de gaz et le remplacer
par celui fourni
- remonter la rampe de gaz
- réalimenter la chaudière et ouvrir le robinet de gaz
La transformation ne doit être faite que par du personnel quali é.
Après la conversion, régler à nouveau la chaudière (en observant la section
« Réglages ») et appliquer la nouvelle étiquette d’identi cation contenue
dans le kit.
4.8 Véri cation des paramètres de combustion (fonction de bala-
yage cheminée)
Pour e ectuer l’analyse de combustion, procéder comme suit :
- tourner le sélecteur de fonction en position OFF
- tourner le sélecteur de balayage cheminée de la position à la position ( g.
25) .
Pièces électriques sous tension (230 V AC).
- Attendre l’allumage du brûleur (environ 6 secondes). Lécran indique « ACO »,
le témoin jaune clignote et la chaudière fonctionne à la puissance thermique
maximale.
- insérer la sonde de l’analyseur dans les ori ces ménagés dans le boîtier de
distribution d’air, après avoir enlevé les vis du capot ( g. 33)
- véri er que les valeurs de CO2 correspondent au tableau, si la valeur indiquée
est di érente, la modi er comme indiqué dans le chapitre intitulé « Réglage
de la vanne gaz ».
- e ectuer le contrôle de la combustion.
Ensuite:
- enlever la sonde de l’analyser et fermer les prises pour l’analyse de combu-
stion avec la vis spéciale
La sonde d’analyse des gas de combustion doit être totalement
insérée aussi loin que possible.
IMPORTANT
- Même pendant la phase d’analyse de combustion, la fonction qui éteint la
chaudière quand la température de l’eau atteint la limite maximale (environ
90°C) reste activée.
- La fonction danalyse de combustion reste active pendant 15 minutes ; il est
possible de la couper par avance en déplaçant le sélecteur de balayage de
cheminée en position .
5 MAINTENANCE
Pour s’assurer que les caractéristiques du produit et le rendement restent intacts
et pour se conformer aux prescriptions des réglementations en vigueur, il est
nécessaire d’e ectuer des véri cations systématiques de l’appareil à intervalles
réguliers.
Lors des travaux d’entretien, respecter les instructions indiquées dans le chapitre
« Avertissements et sécurité ».
Éteindre l’appareil pour e ectuer l’entretien de la structure près des raccords
ou dispositifs de décharge de combustion et de leurs accessoires. Une fois les
interventions achevées, un technicien quali é doit véri er que les tuyaux et les
dispositifs fonctionnent correctement.
IMPORTANT: avant d’e ectuer une quelconque opération de nettoyage ou de
maintenance de l’appareil, utiliser l’interrupteur de l’appareil et du système pour
couper l’alimentation électrique et fermer l’alimentation de gaz en tournant le
robinet placé sur la chaudière.
Entretien ordinaire
Cela implique normalement les tâches suivantes :
- enlever toute trace d’oxydation du brûleur ;
- enlever le tartre des échangeurs thermiques ;
- enlever tout résidu du tuyau de drainage de condensat ;
- véri er et nettoyer les tuyaux de drainage ;
- véri er l’aspect extérieur de la chaudière ;
- véri er l’allumage, l’extinction et le fonctionnement de l’appareil, en mode
eau sanitaire et en mode chau age ;
- véri er le joint sur les raccords et tuyaux de gaz et d’eau ;
- véri er la consommation de gaz à la puissance maximale et minimale ;
- véri er la position de la bougie de détection de  amme d’allumage ;
- véri er le dispositif de sécurité en matière de gaz.
Ne pas nettoyer l’appareil ou ses pièces avec des substances facilement in am-
mables (par exemple essence, alcool, etc).
Ne pas nettoyer les panneaux, les pièces peintes ou les pièces en plastique avec
un diluant de peinture.
Le nettoyage du panneau doit être e ectué uniquement avec de l’eau savon-
neuse.
Entretien extraordinaire
Ces tâches rétablissent le fonctionnement de l’appareil conformément à sa con-
ception et aux réglementations - par exemple suite à la réparation d’une panne
accidentelle.
Cela signi e normalement :
- remplacement
- réparation
- remise en état des composants
Ces tâches nécessitent des moyens, un équipement et des outils spéciaux.
Pendant la phase d’installation initiale, ou en cas de maintenance ex-
traordinaire, nous vous conseillons d’activer la procédure pour décharger
de l’air du circuit de chau age et de la chaudière (voir le paragraphe
correspondant).
20
Qn =
N.
230 V ~ 50 Hz 165 W
NOx:
Gas type: Gas category:
kW
Pms = 3 bar T= 90 °C
Pn =
η
B23P-B53P-C13-C23-C33-C43-C53-C63
C83-C13x-C33x-C43x-C53x-C63x-C83x
Condensing Boiler
IP
kW
6 NUMÉRO DE SÉRIE
Fonction de chau age
Qn Débit calori que nominal
Pn Puissance calori que nominale
IP Degré de protection
Pms Pression thermique maximale
T Température
ŋ Performances
NOx Classe NOx
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

Nibe NIBE GBM 10-15 Installer And User Manual

Typ
Installer And User Manual

V iných jazykoch