SIGURO SGR-AC-C180W Používateľská príručka

Typ
Používateľská príručka
SGR-AC-C180W
SGR-AC-F180W
SGR-AC-H180W
SGR-AC-I160W
Mobile Air Condition
Mobile Air Condition
Mobile Klimatisierung
Mobilní klimatizace
Mobilná klimatizácia
Mobil klímaberendezések
EN Translation of the operating instructions from the original language.
DE Übersetzung der Bedienungsanleitung aus der Originalsprache.
CZ Návodkpoužitívoriginálnímjazyce.
SK Prekladnávodunapoužitiezoriginálnehojazyka.
HU Ahasználatiutasításfordításaeredetinyelvről.
ENGLISH 8
Safety information 8
Service instructions 11
Technical parameters 17
Installation 18
Control via control panel 19
Control via remote control 20
Control via the application 22
Other functions 23
Cleaning and maintenance 24
Troubleshooting 25
DEUTSCH 28
Sicherheitshinweise 28
Dienstanweisungen 31
Technische Parameter 39
Installation 40
Steuerung über das Bedieneld 41
Bedienung über die Fernbedienung 42
Bedienung über die App 44
Weitere Funktionen 45
Reinigung und Wartung 47
Problemlösung 48
ČESKY 51
Bezpečnostní informace 51
Servisní návod 54
Technické parametry 60
Instalace 61
Ovládání prostřednictvím ovládacího panelu 62
Ovládání prostřednictvím dálkového ovládání 63
Ovládání prostřednictvím aplikace 65
Další funkce 66
Čištění a údržba 67
Řešení problémů 68
SLOVENSKY 71
Bezpečnostné informácie 71
Servisný návod 74
Technické parametre 81
Inštalácia 82
Ovládanie prostredníctvom ovládacieho panelu 83
Ovládanie prostredníctvom diaľkového ovládania 84
Ovládanie prostredníctvom aplíkácie 86
Ďalšie funkcie 87
Čistenie a údržba 88
Riešenie problémov 89
MAGYAR 92
Biztonsági információk 92
Javítási útmutató 95
Műszaki paraméterek 102
Telepítés 103
Működtetés a működtető panelről 104
Működtetés a távirányító segítségével 105
Működtetés mobil alkalmazásból 107
Egyéb funkciók 108
Tisztítás és karbantartás 109
Problémamegoldás 110
1
2
3
11
Cool
Dry
Fan
Timer Sleep
Swing
Speed
C/ F
4
5
9
6
7
810
12 13 14
Scan the QR code to download the app.
Scannen Sie diesen QR-Code, um die App herunterzuladen.
ProstaženíaplikacesinaskenujtetentoQRkód.
NastiahnutieaplikáciesinaskenujtetentoQRkód.
AzalkalmazásletöltéséhezolvassabeeztaQRkódot.
Scannez ce code QR pour télécharger l’application.
Scansionare questo QR code per scaricare l’app.
ScanațiacestcodQRpentruadescărcaaplicația.
Android iOS
Cool
Dry
Fan
Timer Sleep
Swing
Speed
C/ F
12345678910
1
32
4
5
6
7
8
9
10
11
Cool
Dry
Fan
Timer Sleep
Swing
Speed
C/ F
15 16
1A 1B
1C 1D
1E 1F
2A 2B
2C
EN
EN - 8
Thank you for purchasing a SIGURO appliance. We are grateful for
your trust and are pleased to introduce the device to you on the
following pages and introduce you to all its functions and uses.
We believe in a fair and responsible company, and therefore we only work
with suppliers who meet our strict criteria of protecting the interests of their
employees, preventing their abuse and providing fair working conditions.
If you need help with extensive maintenance or repair of the product, which
requires intervention in its internal parts, our authorized service is available
at the email address siguro@alza.cz or operators at the seller's info line. For
your convenience in solving any problems with the product, we have unied
these contact points and the above contacts can be used in the event of any
complaints or post-warranty service.
SAFETY INFORMATION
Please read this manual carefully before use and
keep it for future reference.
TYPE Local air conditioner
This appliance contains ammable refrigerant.
If the refrigerant leaks and comes in contact with re or heated
parts, a harmful gas is formed and there is a risk of re.
Read this manual thoroughly before using the appliance.
Additional information is available in the operating instructions
and service manual.
Service personnel are obliged to read the operating instructions
and service instructions carefully before putting the appliance into
operation.
1. This appliance is intended for use by children 8 years of age and older
and persons with reduced physical, sensory or mental capabilities, or lack
of experience and knowledge, provided they have been given supervision
or instruction concerning use of the appliance in a safe manner and
understand the potential hazards
2. Cleaning and user maintenance must not be performed by children
without supervision.
3. Children must not play with the device.
ENGLISH
EN
EN - 8 EN - 9
ENGLISH
4. This appliance is intended for use by experts or trained personnel in
shops, light industry and agriculture, or for commercial use by lay
persons.
5. If the power cord is damaged, it must be replaced by the manufacturer,
its service agent or similarly qualied persons in order to avoid a
dangerous situation.
6. The appliance must be installed in accordance with national installation
regulations.
7. WARNING: The appliance must be installed, operated and stored in a
room with a oor area of more than: 10 m2 for 9000 BTU model SGR-AC-
C180W; 12 m2 for 12000 BTU model SGR-AC-F180W; 13 m2 for 14000 BTU
model SGR-AC-H180W; and 13 m2 for 16000 BTU model SGR-AC-I160W.
8. While the appliance is in operation, ensure that there is sufcient free
space around it for proper air circulation. The minimum distance of the
appliance from walls, obstacles, etc. is 50 cm.
9. This appliance is intended for indoor use only. Do not use it outdoors.
10. WARNING: Do not cover the ventilation openings or obstruct them.
11. The appliance must only be serviced as recommended by the
manufacturer.
12. Unventilated spaces in which the appliance is installed must be designed
in such a way that any refrigerant leak does not accumulate and does
not create a re or explosion hazard.
13. WARNING: The appliance must be stored in a well-ventilated area where
the room size corresponds to the room size specied for its operation.
14. WARNING: The appliance must be stored in a room where there is no
open re (e.g. gas appliance in operation) and ignition sources (e.g.
electric heater in operation).
15. The appliance must be stored in such a way as to avoid the possibility of
mechanical damage.
16. Before connecting the plug to the electrical outlet, make sure that the
voltage indicated on the type plate of the appliance corresponds to the
voltage in the outlet.
17. Plug the appliance into a properly grounded outlet only. Do not use
extension cords or power adapters.
18. Do not touch the appliance with wet hands.
19. Do not expose the appliance to dripping or splashing water or other
liquids.
20. To prevent the risk of electric shock, do not immerse the appliance,
power cord, or plug in water or other liquids.
21. Do not leave the appliance unattended while it is in operation. Do not tilt
or otherwise manipulate the appliance while it is in operation.
22. Make sure that the appliance is installed, operated and stored at
a sufcient distance from sources of re, ammable or explosive
substances.
23. Do not place any objects on the appliance, do not sit on it or climb on it.
24. Do not insert ngers or other objects into the inlet and outlet openings.
25. Do not use the appliance if it has fallen, is damaged or shows signs of
damage.
EN
EN - 10
26. Do not unplug the power cord from the outlet while the appliance is
operating.
27. Always switch off the appliance and disconnect the plug from the
electrical outlet if you are not going to use the appliance, if you want
to move it, if you are going to clean it, if it is to be serviced, if you are
assembling or disassembling it, etc.
28. Always unplug the power cord by pulling on the plug, not the cord. There
is a risk of damage to the power cord and power outlet.
29. Keep the appliance clean. Follow the instructions in this operating
manual. Do not use any harsh cleaning agents, chemicals, solvents, etc.
30. Do not damage, repair, modify or deform the appliance in any way. If the
appliance is damaged, malfunctions or shows signs of damage switch it
off and contact an authorized service center.
31. Store the appliance in a vertical position.
Specic safety instructions for appliances with R290
refrigerant
FAILURE TO FOLLOW THESE WARNINGS CAN
CAUSE BURNS, DEATH, INJURY OR DAMAGE TO
PROPERTY.
1. This appliance is only designed for use with R290 as the specied
refrigerant.
2. WARNING: Do not use any means to speed up the defrosting process or
cleaning other than those recommended by the manufacturer.
3. The appliance must be stored in a room where ignition sources are not
permanently in operation (e.g. open ame, gas appliance in operation,
electric heating system in operation).
4. Do not puncture or incinerate the appliance.
5. Be aware that refrigerants do not have to be smelled.
6. The appliance must be installed, operated and stored in a room with a
oor area of more than: 10 m2 for 9000 BTU model SGR-AC-C180W; 12 m2
for 12000 BTU model SGR-AC-F180W; 13 m2 for 14000 BTU model SGR-AC-
H180W; and 13 m2 for 16000 BTU model SGR-AC-I160W.
7. The appliance must be installed in accordance with national installation
regulations.
8. The refrigerant is located in a closed circuit. Only a qualied technician
may service!
9. Do not release refrigerant into the atmosphere.
10. Refrigerant R290 is ammable and heavier than air.
11. It usually collects close to the ground, but fans can suck it in and put it
into circulation.
12. If refrigerant is released or suspected leaked, untrained personnel must
not be allowed to try to nd the cause.
13. The refrigerant used in the appliance is odorless.
14. The fact that the refrigerant is odorless does not mean that there could
be no leakage.
15. If a leak occurs, immediately evacuate all persons from the room, ensure
EN
EN - 10 EN - 11
adequate ventilation and inform the local re department of the location
of the propane gas leak.
16. Do not allow people to return to the room until a qualied service
technician arrives and the technician conrms that it is possible to return
to the room safely.
17. It is forbidden to use open ames, cigarettes or other sources of ignition
in the vicinity of the appliance.
18. The components are designed for refrigerant and are non-ammable
and non-igniting. Components must always be replaced with identical
original spare parts.
SERVICE INSTRUCTIONS
WARNING:
Any person involved in or participating in work on the refrigeration
circuit should have a valid certicate from an industry-accredited
assessment body that ofcially approves his/her competence to
safely handle refrigerants to an industry-recognized specication.
WARNING:
Service must only be performed as recommended by the manu-
facturer. Maintenance and repairs require the assistance of addi-
tional professional personnel competent to use ammable refrig-
erant.
If you do not understand some parts or need help, contact the
manufacturer's service department.
1. Service information
Please observe these warnings when servicing the appliance with R290 refrigerant.
1.1 Workspace control
Prior to working on a system containing ammable refrigerants, safety checks are nec-
essary to ensure that the risk of ignition is minimized. The following precautions must
be observed before repairing the cooling system.
1.2 Work procedure
The work must be carried out in a controlled manner so as to minimize the risk of
ammable gases or vapors being present during the work.
1.3 Total workspace
The entire maintenance crew and others working on site must be instructed about the
nature of the work performed. Work in conned spaces must be avoided. The space
around the workplace must be divided into sections. It must be ensured that indoor
conditions are safe by inspecting ammable materials.
1.4 Checking the presence of refrigerant
The room must be inspected with an appropriate refrigerant detector before and
during work to ensure that technicians are aware of the potentially ammable atmos-
phere. It must be ensured that the use of leak detection equipment is suitable for use
on ammable refrigerants, that is, non-sparking, appropriately sealed or inherently
EN
EN - 12
safe.
1.5 Presence of re extinguisher
If any work is to be carried out on the refrigeration equipment or associated parts in
warm area, a suitable re extinguishing system must be available. The re extinguisher
must be powder or CO2 in the vicinity of the lling area.
1.6 No sources of ignition
No person performing work on the refrigeration system that involves exposing any
piping that contains or has contained ammable refrigerant shall use any sources of
ignition in a way that could lead to a risk of re or explosion. All possible sources of
ignition, including cigarette smoking, should be kept away from the installation, repair,
removal and disposal site during which ammable refrigerant may be discharged into
the surrounding area. Prior to work, the area around the equipment must be inspect-
ed to ensure that there is no risk of re or ignition. "No smoking" signs must be posted.
1.7 Ventilated space
It must be ensured that the room is open or adequately ventilated before the system
is disrupted or work in warm environment is carried out. The ventilation intensity must
last for the duration of the work. Ventilation should safely disperse any discharged
refrigerant and preferably vent it to the atmosphere.
1.8 Inspection of cooling equipment
If electrical components are changed, these components must be suitable for this
purpose and meet the correct specications. The manufacturer's maintenance and
service instructions must always be followed. If in doubt, contact the manufacturer's
technical department for assistance.
The following checks must be carried out on installations containing ammable refrig-
erants:
The volume of the ll is in accordance with the size of the room in which the parts
containing the refrigerant are installed;
Ventilation units and outlets are working at full capacity and are not blocked;
If an indirect refrigeration circuit is used, the second circuit must be checked for
the presence of refrigerant;
The marking of the device must always be visible and legible; markings and marks
which are not legible must be xed;
Refrigeration pipes or components are installed in locations where they are
unlikely to be exposed to any substances that may corrode refrigerant-containing
components unless the components are constructed of materials that are
intrinsically corrosion-resistant or are adequately protected against corrosion.
1.9 Inspection of electrical components
Repairs and maintenance of electrical components must include safety checks and
inspections of the components. If a malfunction occurs that could compromise safety,
then no power supply must be connected to the circuit until the fault has been satis-
factorily resolved. If the malfunction cannot be repaired immediately, it has to contin-
ue working; an appropriate temporary solution must be used. This must be reported to
the owner of the facility so that all parties know about it.
Initial safety checks must ensure:
That the capacitors are discharged: this must be done in a safe way to avoid the
possibility of sparking;
That no electrical components and wiring is exposed when lling, restoring and
cleaning the system;
That grounding is not interrupted.
EN
EN - 12 EN - 13
2. Repairs of sealed components
2.1 During the repair of sealed components, all electrical supply must be
disconnected from the equipment being worked on before the sealed covers
are removed, etc. If it is absolutely necessary to have the equipment switched on
during service, then a continuously operating leak detector has to be placed in the
most critical location to warn of a potentially dangerous situation.
2.2 Special care must be taken to ensure that work on electrical components does
not alter the cover to such an extent as to affect the level of protection. This must
include damage to the cables, excessive number of connections and terminals
not made to the original specication, damage to the seals, incorrect design of
the seals, etc. It must be ensured that the device is installed securely. It must
be ensured that the seals or sealing materials are not degraded in such a way
that they no longer serve the purpose of preventing the entering of ammable
materials. Spare parts must comply with the manufacturer's specication. The use
of a silicone seal may suppress the effectiveness of some types of leak detection
devices. Internally safe components do not have to be disconnected before they
can be worked on.
3. Repairs of internal safe components
No permanent inductive or capacitive loads shall be applied to the circuit without
ensuring that the permissible voltage and current permitted for the equipment used
are not exceeded.
Internally safe components are the only types that can be worked on in a ammable
environment, even if they are live. The test equipment must be correctly dimensioned.
Parts are replaced only by parts specied by the manufacturer. Other parts may ignite
the refrigerant if it leaks into the environment.
4. Wiring
Check that the wiring is not exposed to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The inspection must also
take into account the effects of aging or permanent vibrations from sources such as
compressors or fans.
5. Detection of ammable refrigerants
Under no circumstances may potential sources of ignition be used to search for or
detect refrigerant leaks. The halogen burner (or any other detector using open ame)
must not be used.
6. Leak detection methods
The following leak detection methods are considered acceptable for systems contain-
ing ammable refrigerants.
Electronic leak detectors must be used to detect ammable refrigerants, but their sen-
sitivity may not be adequate or may require recalibration. (The detection device must
be calibrated in a refrigerant-free space). It must be ensured that the detector is not a
potential source of ignition and is suitable for the refrigerant used. The leak detection
device must be set to the percentage of LFL refrigerant and must be calibrated to the
refrigerant used and the appropriate gas percentage (maximum 25%) conrmed.
Leak detection uids are suitable for use with most refrigerants, but the use of chlo-
rine-containing detergents must be avoided because chlorine can react with the
refrigerant and corrode copper piping.
If a leak is suspected, all open res must be eliminated / extinguished.
If a refrigerant leak is found, which requires brazing; all refrigerant must be removed
EN
EN - 14
from the system or separated (by closing the valves) in the part of the system remote
from the leak. The system must then be purged with oxygen-free nitrogen (OFN), both
before and after the brazing process.
7. Removal and pumping
Conventional procedures must be used if the cooling circuit is disturbed due to repairs
- or for any other reason. However, it is important to keep to the best method due to
ammability. The following procedure must be followed:
remove the refrigerant;
purge the circuit with inert gas;
pump away;
purge again with inert gas;
open the circuit by cutting or brazing.
The circuit lling must be taken to the correct collection cylinders. The system must be
"ooded" with OFN (oxygen-free nitrogen) to make the unit safe. The procedure may
need to be repeated several times. Compressed air or oxygen must not be used for this
task.
Flooding can be achieved by breaking the vacuum in the system using OFN and
continuing to ll until the operating pressure is reached, then venting to air, and nally
reducing to vacuum. This process must be repeated while the refrigerant is in the
system. When the last OFN charge is used, the system must be vented to atmospheric
pressure to allow the work to be done. This operation is absolutely necessary if brazing
is to be performed on the piping.
It must be ensured that the outlets are not close to any source of ignition and that
ventilation is provided.
8. Filling procedure
In addition to conventional lling procedures, the following requirements must be
met.
Care must be taken to ensure that using the lling equipment does not
contaminate the various refrigerants. Hoses or piping must be as short as possible
to minimize the amount of refrigerant contained in them.
The cylinders must be held vertically.
It must be ensured that the cooling system is grounded before lling the system
with refrigerant.
When lling is complete, the system must be labeled (if it does not already have a
label).
Extreme care must be taken to ensure that the cooling system is not overlled.
It must be pressure tested with OFN before relling the system. The system must be
tested for leaks after lling but before starting operation. A verication test must be
carried out before leaving the installation site.
9. Taking out of operation
Before performing this procedure, it is essential that the technician is fully acquaint-
ed with the equipment and all its details. Good practice is recommended to remove
all refrigerant safely. Oil and refrigerant samples must be taken before this operation
begins, if analysis is required before the regenerated refrigerant can be used again. It
is essential that electricity is available before starting this activity.
Introduction to the device and its operation.
Electrical disconnection of the system.
Before initiating the procedure, it must be ensured that:
mechanical equipment for handling the refrigerant cylinders was available if
EN
EN - 14 EN - 15
required;
all personal protective equipment was available and used correctly;
the removal procedure was constantly under the supervision of a competent
person;
collection devices and cylinders complied with the relevant standards.
Drain the cooling system if possible.
If it is not possible to achieve a vacuum, a manifold is made so that the refrigerant
can be taken from different parts of the system.
It must be ensured that the cylinder is placed on the scale before the collection
takes place.
The collection device is switched on and the manufacturer's instructions are used.
Do not overll the cylinders. (Not more than 80% of the liquid content).
The maximum operating pressure of the cylinder is not exceeded, even
temporarily.
When the cylinders are properly lled and the process is completed, it is ensured
that the cylinders and equipment are immediately removed from the installation
site and all separation valves on the equipment are closed.
The removed refrigerant must not be lled into another cooling system until it has
been cleaned and inspected.
10. Labelling
The appliance must get a label stating that it has been taken out of service and does
not contain refrigerant. The label must be dated and signed. It shall be ensured that
the equipment has labels indicating that the equipment contains a ammable refrig-
erant.
11. Removal
When refrigerant is removed from the system, either for service or decommissioning,
good practice recommends removing all refrigerants safely.
When transferring refrigerant to the cylinders, make sure that only the appropriate
refrigerant removal cylinders are used. It must be ensured that the correct number of
cylinders is available to contain the total ll of the system. All cylinders to be used must
be designed for the refrigerant to be removed and marked with a label for this re-
frigerant (i.e. special refrigerant collection cylinders). The cylinders must be complete
with a safety valve and holding shutoff valves in good working order. Empty collection
cylinders are drained and if possible cooled before collecting.
The collecting equipment must be in good working order with a set of instructions for
the equipment at hand and must be suitable for collecting ammable refrigerants. In
addition, a set of calibrated scales must be available in good working order. The hoses
must be complete with detachable couplings without leakage and in good condition.
Before using the collecting device, it must be checked that it is in a satisfactory operat-
ing condition, has been properly maintained and that all associated electrical com-
ponents are sealed to prevent ignition in the event of refrigerant discharge. In case of
doubt, consult the manufacturer.
The drained refrigerant must be returned to the refrigerant supplier in the correct
collecting cylinder and with the relevant agreed waste shipment letter. Refrigerants
do not mix in the collection units and especially not in the cylinders.
If compressors or compressor oils are to be removed, ensure that they have been
pumped to an acceptable level to ensure that ammable refrigerant does not remain
in the lubricant. The pumping out procedure must be performed before the com-
pressor is returned to the supplier. Only electric compressor housing heating must be
used to speed up this process. When oil is drained from the system, it must be safely
disposed of.
EN
EN - 16
Description of the appliance
1 Control panel
2 Outlet opening with adjustable slats
3 Front cover
4 Inlet lter grille guard
5 Air lter
6 Upper drain opening
7 Flexible hose connection opening
8 Bottom drain opening
9 Handles (located on both sides)
10 Castors
11 Flexible hose
12 Hose inlet adapter
13 Hose outlet adapter
14 Remote control
15 Drain hose
16 Window mounting kit (window sealing foil, Velcro)
Control panel
1 POWER button: used to turn the air conditioner on/off
2 MODE button: used to select an operating mode
3 Operating mode indicator lights
4 SLEEP button: used to turn on/off the sleep mode
5 / buttons: used to set temperature or timer.
6 Digital display: shows temperature and set time of the timer
7 SWING button: used to set the angle of the vertical slats.
8 Fan speed set indicator lights
9 SPEED button: used to set the fan speed
10 TIMER button: used to turn on/off the timer function and Wi.
Remote control
1 Digital display
2 button: On/Off
3 COOL button: selection of the cooling operating mode
4 DRY button: selection of the drying operating mode
5 FAN button: selection of the fan operating mode
6 / buttons: setting the required temperature and time.
7 TIMER button: switching to timer function setting mode
8 SPEED button: setting the fan speed
9 SWING button: slats oscillation turning on/off
10 SLEEP button: sleep functionm selection
11 °C/°F button: switching of the temperature units
3
EN
EN - 16 EN - 17
TECHNICAL PARAMETERS
Parameters/
Model
SGR-AC-
C180W SGR-AC-
F180W SGR-AC-
H180W SGR-AC-
I160W
Cooling capacity 9 kBtu / hr 12 kBtu / hr 14 kBtu / hr 16 kBtu / hr
Rated voltage 220–240 V ~ 220–240 V ~ 220–240 V ~ 220–240 V ~
Rated frequency 50 Hz 50 Hz 50 Hz 50 Hz
Cooling power 1003 W 1337 W 1560 W 1712 W
Energy con-
sumption 4.5 A 5.9 A 6.9 A 7.5 A
EER cooling
factor 2.6 2.6 2.6 2.7
Dehumidica-
tion capacity 21.8 l/day 28.8 l/day 31 l/day 35 l/day
Capacity of the
built-in conden-
sation tank
650 ml 650 ml 650 ml 650 ml
Refrigerant type
and ll R290 / 190 g R290 / 240 g R290 / 270 g R290 / 265 g
Air ow volume
(high / medium /
low speed)
370 m3/h
350 m3/h
310 m3/h
400 m3/h
360 m3/h
330 m3/h
400 m3/h
360 m3/h
330 m3/h
440 m3/h
410 m3/h
380 m3/h
Noise ≤ 65 dB (A)
(high setting) ≤ 65 dB (A)
(high setting) ≤ 65 dB (A)
(high setting) ≤ 65 dB (A)
(high setting)
Maximum al-
lowable value
of excessive
working pres-
sure: Suction /
discharge part
of the cooling
circuit
0.7 / 3.2 MPa 0.7 / 3.2 MPa 0.7 / 3.2 MPa 0.7 / 3.2 MPa
Dimensions 76.2x35.3x47
cm
76.2x35.3x47
cm
76.2x35.3x47
cm
76.2x35.3x47
cm
Weight 27.5 kg 29 kg 30 kg 32 kg
Operating tem-
perature (cool-
ing) 16 °C to 32 °C 16 °C to 32 °C 16 °C to 32 °C 16 °C to 32 °C
Recommended
room size 12-18 m218-25 m220-28 m225-32 m2
The declared noise emission value of the appliance is ≤ 65 dB (A), which represents the
EN
EN - 18
sound power level A with respect to the reference sound power of 1 pW.
INSTALLATION
Unpacking portable air conditioner
Remove the portable air conditioner and all its accessories from the package. Before
disposing of the packaging, be sure to remove all components. Check if the portable
airconditioner and accessories for damage.
Placing the portable air conditioner
If the air conditioner was transported inclined at an angle greater than 45 °, leave it
free standing in an upright position for at least 24 hours after unpacking.
Place the air conditioner on an level and solid surface. Select such a place where suf-
cient air circulation will be ensured while the power outlet is easily accessible for quick
disconnection. The minimum distance from walls or other obstacles is at least 50 cm.
Ensure that the air intake holes and discharge are not blocked.
Warning: Never install portable air conditioner in close proximity to walls, drapes or
other objects that could prevent inlet or air removal.
Do not place the portable air conditioner where:
it will be near heat sources such as radiators, oor heating outlets, stoves or other
equipment that produce heat;
it will be in direct sunlight;
the environment is too dusty;
is insufcient ventilation such as cabinets or libraries;
is uneven surface.
Warning: The appliance must be installed, operated and stored in a room with a oor
area of more than: 10 m2 for 9000 BTU model SGR-AC-C180W; 12 m2 for 12000 BTU
model SGR-AC-F180W; 13 m2 for 14000 BTU model SGR-AC-H180W; and 13 m2 for 16000
BTU model SGR-AC-I160W. Do not place the appliance to places where ammable gas
could leak.
Flexible hose installation
The exible hose must be connected to the portable air conditioner and lead out of
the room, since it can contain excess heat and moisture.
Warning: Never change the exible hose for another type or add an extension. This
can cause efciency reduction or even shutting down air conditioner due to low back-
pressure.
When installing a exible hose, proceed as follows:
1. On one end of the exible hose insert the input adapter - see Figure 1 A.
2. On the other end of the exible hose attach the output adapter - see Figure 1 B.
3. Use the input adapter to connect the exible hose to the outlet opening at the rear
of the air conditioner - see Figure 1 C.
Installing a set for attachment to the window
1. Open the window on which you want to install the sealing foil.
EN
EN - 18 EN - 19
2. Remove the underlying tape from the Velcro and glue the Velcro on those parts of
the window and the frame where there are no hinges - see Figure 1 D. Make sure
the window can be easily closed even after Velcro is glued on.
3. Attach the sealing foil to the Velcro so that the opening to which the exible hose
will be inserted is easily accessible - see Figure 1 E.
4. Make sure there is no gap between the window and seal where the air could
escape. The window attachment kit is designed to be suitable for installation in
most types of windows (both horizontal and vertical - see Figure 1 F).
5. Carefully unroll the exible hose. Do not bend the exible hose excessively.
6. Open the built-in Velcro and insert the exible hose into the opening.
7. Close the Velcro tightly
Note: After using is nished, remove the exible hose, remove the sealing foil and close
the window.
CONTROL VIA CONTROL PANEL
On / Off
Plug the power cord for a power outlet and open the air outlet slats.
Press POWER to start the portable air conditioner. The power indicator light turns on.
The portable air conditioner starts in the default mode.
If you will not use portable air conditioner, press the POWER button and the air condi-
tioner switches to standby mode. The power light indicator turns off. Pull out the plug
from the power outlet to turn the air conditioner off completely.
Warning: Never remove the power cord plug from the power outlet while the portable
air conditioner is in operation.
Note: Wait 2-3 minutes before switching on the air conditioner. This prevents possible
damage to the air conditioner.
Operating mode selection
Press repeatedly MODE and select the operating mode: cooling – fan – drying. Every
time you press the MODE button, the light indicator of the selected operating mode
will light up.
For more information on operating modes, see "CONTROL VIA REMOTE CONTROL".
Fan speed setting
Press repeatedly SPEED and select the required speed: low – medium – high. Every
time you press the SPEED button the light indicator of the selected speed will light up.
Timer function
Portable air conditioner has two timer function modes - automatic shutoff and auto
power. In Auto Shutdown mode, the portable air conditioner automatically turns off
after the set timer time has elapsed. In Auto Switch mode, the portable air conditioner
automatically turns on after the timer time is elapsed.
While the portable air conditioner is operating, press the TIMER button and using the
/ buttons set the shutoff time after which the portable air conditioner turns off. You
can set the timer time from 1 to 24 hours.
While the portable air conditioner is in stanby mode, press the TIMER button and us-
EN
EN - 20
ing the / button set the time after which the portable air conditioner turns on. You
can set the timer time from 1 to 24 hours.
Sleep function
Press SLEEP to turn on the sleep function. Press again to cancel the function.
For more information about the sleep function see "CONTROL VIA REMOTE CON-
TROL".
Oscillation function
Press SWING to start movement of the slats up and down. Press again to cancel the
function.
CONTROL VIA REMOTE CONTROL
The remote control is supplied with inserted batteries from the manufacturer. To use
the remote control, remove the protective foil from the battery compartment. This
protects the batteries from discharge and damage during transport.
If you want to use the remote control, point it to the signal receiver on the appliance.
The maximum range of signal sent from the remote control is 6 m. If obstacles are
located between the remote control and the appliance, the signal cannot be transmit-
ted.
If the inserted batteries are empty they must be replaced with the same type. Proceed
as follows:
1. Remove the battery compartment cover.
2. Remove the empty batteries and insert two new AAA batteries. Observe correct
polarity when inserting a battery.
3. Replace the cover.
If you will not use the remote control for a long time, we recommend removing the
batteries. If the batteries leaked into the interior of the remote control, it could damage
it.
Warning:
Never combine alkaline and rechargeable batteries. Never put batteries in re, short
circuit or damage them in any way. After the end of their lifetime, discard them in en-
vironmentally friendly manner. Never dispose of batteries in household waste.
On / Off
After connecting the plug in the power outlet press the button to turn on the porta-
ble air conditioner.
The portable air conditioner starts in the default mode.
IF YOU WILL NOT USE THE PORTAble air conditioner, press the button and the con-
ditioner switches to stanby mode. The power light indicator turns off. Pull out the plug
from the power outlet to turn the air conditioner off completely.
Warning: Never remove the power cord plug from the power outlet while the portable
air conditioner is in operation.
Note: Wait 2-3 minutes before switching on the air conditioner. This prevents possible
damage to the air conditioner.
Operating mode selection
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116

SIGURO SGR-AC-C180W Používateľská príručka

Typ
Používateľská príručka